ICM870-32A
Soft Start DYNAMIC
START DELAY
BUIL TIN!
ICM870-32A Soft Start with Built In Start Capacitor
INSTALLATION, OPERATION & APPLICATION GUIDE
For more information on our complete range of American-made products – plus
wiring diagrams, troubleshooting tips and more, visit us at
www.icmcontrols.com
FEATURES
- Starting current reduction and self-learning algorithm
- Built-in start capacitor
- Over-current protection
- Over/under voltage monitoring
- Diagnostic indicators
- Sealed enclosure
SPECIFICATIONS
Semi-Conductor Soft-Start Motor Controller, Form 2, Bypassed Controller
- SCCR: 5kA
- Ue = 240 VAC
- Ui = 240 VAC
- Uimp = 4kv
- Pollution degree 3
Input (L1, L2) – 100-240 VAC 50/60Hz
- Over voltage limits: 115 VAC nominal = 140 VAC, 240 VAC nominal = 264 VAC
- Under voltage limits: 115 VAC nominal = 95 VAC, 240 VAC nominal =195 VAC
Outputs: Compressor
- Solid state/relay
- Current: Max. nominal = 32A
- Over current limits: ICM870-32A = 40A
Environmental:
- Ambient temperature: 40°C @ 32 FLA, 8 hour duty
- Storage temperature: -40°F to 149°F (-40°C to 65°C)
- Humidity: 0-95% non-condensing
- Enclosure: IP65
- Dimensions: 7.94” x 4.20” x 2.10”
- Screw hole center points: 7.36” x 2.97”
IMPORTANT SAFETY INFORMATION
HIGH VOLTAGE WARNING – Always turn off power at the main service panel before installing.
CAUTION: The ICM870-32A must be mounted in an area where it will not be
exposed to water or the elements. Exposure of the ICM87032A soft start to
water can cause failure of the control and is a risk for fire or other
electrical safety hazards.
Suitable for use on a circuit capable of delivering no more than 5,000 RMS
Symmetrical Amperes, 240 V maximum when protected by a circuit breaker with no
more than 60 A.
Installation of any ICM870-32A soft start must be done by a certified HVAC
technician or licensed electrician. All installations are to be done in
accordance with local, state, and national electrical codes.
WARNING: Using an undersized generator or invertor with the ICM870 soft
start can result in a dangerous condition. Always size your generator or
inverter appropriately for your application.
APPLICATION
The ICM870-32A is intended for Marine, Recreational Vehicle, HVAC and commercial applications. The ICM870-32A integrates compressor in-rush current over startup time, thus reducing peak current demand on a power supply source (such as a generator). The ICM870-32A will monitor system health including voltage, current, compressor startup and self integrity. Upon a fault condition, the ICM870-32A will halt operation and initiate a 4-minute anti- short cycle routine while providing diagnostic fault information by means of an LED indicator.
ICM870-32A COMPARABLE AMPERAGE CROSSES
The ICM870-32A model replaces amperage-corresponding models from the following manufacturers:
- Micro-Air (EasyStart)
- Dometic (SmartStart)
- Network RV (SoftStartRV)
- Hyper Engineerging (Sure-Start)
- Carlo Gavazzi (Smooth Starter)
STANDARD AND TEST RESULTS
- UL 60947-1
- UL 60947-4-2
- Altitude: 2000 m
- IP65
- CSA C22.2 NO. 60947-1
- CSA C22.2 NO. 60947-4-2
LED INDICATORS
START = Green
- RUN = Green
- FAULT = Red (flashing)
FLASH CODES
Flashes | Flash Conditions |
---|---|
1 | High or low voltage |
2 | Compressor not sensed or open fuse |
3 | High current |
4 | Compressor start error |
5 | Invalid operating frequency |
Rapid | Normal start delay active |
FOR RESIDENTIAL A/C’s
WIRING DIAGRAM (GENERAL LAYOUT)
FOR RV & MARINE A/C’s
WIRING DIAGRAM (GENERAL LAYOUT)
Special attention should be made with respect to the termination of the field wiring leads, only at terminals suitable for a 90°C wire at minimum.
TYPICAL INSTALLATION
NOTE: For Trane or American Standard units, T1 and T2 are labeled
differently from Figure 1. Wire according to Figure 3 for those units.
Step #1 Connect the (ICM870 RED WIRE) > to the run capacitor terminal
(c/common/T2). See Figure 3 for Trane and American Standard.
Step #2 a) Disconnect factory installed compressor run wire from the contactor
terminal (T2). See Figure 3 for Trane and American Standard.
b) Splice the (ICM870 BROWN WIRE) > to the compressor run wire previously
disconnected in (Step 2A)
If there is a Start Capacitor and/or Start Relay already in place, disconnect
them prior to installing the ICM870.
Step #3 Connect the (ICM870 BLUE WIRE) > to the run capacitor terminal
(herm/hermetic/start)
Step #4 Connect or splice the (ICM870 BLACK WIRE) > to the contactor terminal
(T1). See Figure 3 for Trane and American Standard.
WIRING DIAGRAM FOR TRANE & AMERICAN STANDARD HVAC UNITS
NOTE: On American Standard and Trane units, T1 & T2 are labeled differently from the ICM870 instructions. In those cases, wire as seen below.
INSTALLATION
Step #1 a) Disconnect factory installed compressor run wire from the common
run capacitor / L2 terminal
b) Splice the ICM870 BROWN WIRE > to the factory installed compressor run wire
previously disconnected in step #1A.
If there is a Start Capacitor and/or Start Relay already in place, additional
steps will be required to disconnect them.
Step #2 ICM870 RED WIRE > to the run capacitor (c/common/L2) terminal
Step #3 Connect the ICM870 BLUE WIRE > to the run capacitor
(herm/hermetic/start) terminal
Step #4 Splice the ICM870 BLACK WIRE > with the factory install compressor
Overload Switch wire (OL/L1)
WHICH MODEL DO I NEED?
ICM870-9A: For AC’s with a Compressor Rated Load Amps (RLA) of up to 9A
ICM870-16A: For AC’s with a Compressor Rated Load Amps (RLA) of 9.1-16A
ICM870-32A: For AC’s with a Compressor Rated Load Amps (RLA) of 16.1-32A
This chart reflects average conversions of Single-Phase Air Conditioning and
Heat Pump Tonnage, BTU’s, HP, and RLA. Please refer to your user manual or
service panel to determine your actual RLA before deciding which model ICM870
you need.
Air Conditioning & Heat Pump Loads – Average
Size | BTU | RLA | ICM870 Model |
---|---|---|---|
3 Ton * | 36,000 | 16 | 16A |
4 Ton | 48,000 | 22 | 32A |
5 Ton | 60,000 | 26 | 32A |
6 Ton | 72,000 | 32 | 32A |
- NOTE: for 3-ton units, use ICM870-32A if RLA exceeds 16A
7313 William Barry Blvd., North Syracuse, NY 13212
www.icmcontrols.com
LIAF312-2
800.365.5525