ICM CONTROLS ICM530 3-Phase Surge Protective Devices Instructions

June 4, 2024
ICM CONTROLS

ICM CONTROLS ICM530 3-Phase Surge Protective Devices

FEATURES

  •  NEMA Type 4X watertight plastic enclosure for outdoor and indoor installation
  • Green LED indicates surge protection present
  • Easily connects to electrical panel or disconnects for indoor and outdoor applications
  • UL Listed Type 1 or Type 2 SPD
  • Dimensions:
    4.30” x 4.10” x 2.30”

OVERVIEW

THE ICM530 are a series of Type 1 and Type 2 three-phase surge protective devices for three-phase Delta, three-phase Wye, or Delta High-leg configurations. When a surge occurs, the ICM three-phase surge protective device will absorb the surge up to the specified limitations of the device.
ICM incorporates superior thermally protected metal oxide varistor technology into the three-phase surge suppressors, which allows for safe disabling of the surge elements when a surge exceeds the thermal limits of the device. There is a single status light on the controls which identifies operational status when illuminated.
The ICM 3-phase surge protective device can be installed as a Type 1 or Type 2 device for both indoor and outdoor applications.

ICM530 (DELTA OR WYE CONFIGURATION)

  •  Service voltage (3-phase): 240 VAC Delta or 120/208 VAC Wye

  •  Short Circuit Current Rating (SCCR): 200 kA

  • Nominal discharge current (In): 20kA

  • Protection mode:
    • 3 for Delta configuration
    • 6 for Wye configuration (neutral tied to ground)

  • Maximum Continuous Operation Voltage (MCOV):
    L- N: (for Wye configuration only): 150 VAC

  • VPR:
    • Delta L-L: 1200 VAC Wye L-L: 1200 VAC Wye L-N: 700 VAC

  •  SPD type: Type 1 (can also be used in Type 2 applications)

  •  Surge protection technology: TFMOV

  •  Input power frequency: 5

REPLACES

  •  ABB: OVRHLDxx-120

  •  ASCO: 420120Y, 420240D

  •  Eaton: SP1-208Y, SP1-240D,
    SP2-208Y, SP2-240D

  •  ERICO (Critec): TDX50C120/208,
    TDX50C120/240D

  •  Intermatic: AG2083C3
    L5F13Y1DG1

  •  Leviton: 55208-ASA

  •  Siemens: TPS3D, TPS3C

  •  Square D: SDSA2040,
    SDSA2040D

ICM531 (DELTA OR WYE CONFIGURATION)

  • Service voltage (3-phase): 480 VAC Delta or 277/480 VAC Wye

  •  Short Circuit Current Rating (SCCR): 200 kA

  •  Nominal discharge current (In): 20kA

  •  Protection mode:
    • 3 for Delta configuration
    • 6 for Wye configuration (neutral tied to ground)

  •  Maximum Continuous Operation Voltage (MCOV):
    L- N: (for Wye configuration only): 350 VAC

  • VPR:
    • Delta L-L: 2500 VAC Wye L-L: 2500 VAC Wye L-N: 1200 VAC

  •  SPD type: Type 1 (can also be used in Type 2 applications)

  •  Surge protection technology: TFMOV

  •  Input power frequency: 50/60 Hz

  •  Dimensions: 4.30” x 4.10” x 2.30

REPLACES

  • ABB: OVRHLDxx-277

  •  ASCO: 420277Y, 420480D

  •  Eaton: SP1-480Y, SP1-480D,
    SP2-480Y, SP2-480D

  •  ERICO (Critec): TDX50C277/480

  •  Intermatic: AG4803C3,
    L5F13Y2DG1

  •  Leviton: 55480-ASA

  •  Siemens: TPS3E, TPS3F

  • Square D: SDSA2040,
    SDSA2040D

ICM532 (DELTA OR WYE CONFIGURATION)

  • Service voltage (3-phase): 600 VAC Delta or 347/600 VAC Wye

  •  Short Circuit Current Rating (SCCR): 200 kA

  • Nominal discharge current (In): 20kA

  • Protection mode:
    • 3 for Delta configuration
    • 6 for Wye configuration (neutral tied to ground)

  • Maximum Continuous Operation Voltage (MCOV):
    • L-L: 920 VAC L-N: (for Wye configuration only): 460 VAC

  • VPR:
    • Delta L-L: 2500 VAC Wye L-L: 2500 VAC Wye L-N: 1500 VAC

  •  SPD type: Type 1 (can also be used in Type 2 applications)

  •  Surge protection technology: TFMOV

  •  Input power frequency: 50/60 Hz

  •  Dimensions: 4.30” x 4.10” x 2.30”

REPLACES

  •  ASCO: 420347Y, 420600D

  •  Eaton: SP1-600Y, SP1-600D,
    AP2-600Y

  •  ERICO (Critec): TDX50C347/600

  •  Intermatic: AG6503, L5F13Y3DG1

  •  Siemens: TPS3L, TPS3G

  •  Square D: SDSA3650,
    SDSA3650D

ICM533 (DELTA HIGH-LEG CONFIGURATION)

  • Service voltage (3-phase): 120/240 VAC Delta High-Leg

  •  Short Circuit Current Rating (SCCR): 200 kA

  • Nominal discharge current: (In): 20kA

  • Protection mode: 3 for Delta configuration

  •  Maximum Continuous Operation Voltage (MCOV):
    • L-L: 300 VAC L-N: 150 VAC
    • H-L: 450 VAC H-N: 300 VAC

  •  VPR:
    • L-L: 1200 VAC L-N: 700 VAC
    • H-L: 1500 VAC H-N: 900 VAC

  • SPD type: Type 1 (can also be used in Type 2 applications)

  •  Surge protection technology: TFMOV

  • Input power frequency: 50/60 Hz

  •  Dimensions: 4.30” x 4.10” x 2.30”

REPLACES

  •  ASCO: 420240H

  •  Eaton: SPD050240H1

  •  Intermatic: AG2403C3,
    L5F13D1DG1

  •  Siemens: TPS3B

  •  Square D: SDSA2040D

7313 William Barry Blvd. North Syracuse, NY 13212
www.icmcontrols.com | 1-800-365-5525 | info@icmcontrols.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>