ICM CONTROLS ICM518 Surge Protective Device User Manual
- June 3, 2024
- ICM CONTROLS
Table of Contents
ICM CONTROLS ICM518 Surge Protective Device
Please follow all State, Local and National electrical codes when installing this product. Installation should only be done by a licensed electrician for Type 1 devices or a licensed HVAC technician for Type 2 devices.
ELECTRICAL SHOCK HAZARD – Before installing this unit, turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position.
- WARNING — No Serviceable Parts (Attention: Aucune pièce remplaçable ou reparable).
- WARNING — Shock hazard — Do not open (ATTENTION – RISQUE DE CHOC – NE PAS OUVRIR).
Maintenance
Periodically check the LED status on the SPD. If the Greenlight is OFF, the
protection is no longer available and the SPD needs to be replaced
immediately. 12 AWG stranded copper wire or larger required. Product contains
no serviceable parts. This device features an internal protection that will
disconnect the surge protective component at the end of its useful life but
will maintain power to the load – now unprotected.
Mode of Operation
The ICM518 is a UL Listed Type 1&2 Surge Protective Device for 240 VAC Split
Phase voltage configurations. When a surge occurs, the ICM518 will
absorb the surge up to the limits expressed in the specifications section of
this guide. The ICM518 incorporates thermal protection on the surge elements
(TMOV’s) which allows for safe disabling of the surge elements when a surge
exceeds the thermal limits of the device. The ICM518 has a status light on
the control which identifies operational status when illuminated. The ICM518
can be installed as a Type 1 or Type 2 device for both indoor and outdoor
applications. Suitable for use on a circuit capable of delivering not more
than 200kA RMS symmetrical amperes, 240V maximum (Convient à des circuits
produisant au plus 200kA RMS A eff.”, 240V maximum).
Installation Instructions
The conductors used to connect the SPD shall not be any longer than necessary and shall avoid unnecessary bends.
-
Turn off the main breaker and/or main power to the service disconnect.
-
Verify your mains voltage and match that with ICM518 ratings.
-
Remove the cover on service disconnect or the electrical panel.
-
Mount the ICM518 through the 3/4” conduit connection of the electrical panel.
-
Remove the retaining ring and washer on the ICM518.
-
Feed the wires into the electrical panel or service disconnect.
-
Re-secure the retaining ring and washer.
-
Route the white wire to the neutral lug and secure.
Wiring Type 1 installation
Route the two black wires to the appropriate L1 and L2 connections before the breaker panel as seen in the wiring diagram for Type 1 installation and according to your local, state, and national electrical codes.
Connect the white wire to the Neutral Bus
Wiring Type 2 installation
Route and connect the two black wires (L1 and L2) to the individual breakers on the circuit breaker panel as seen in the wiring diagram for Type 2 installation and according to your local, state and national electrical codes.
Connect the white wire to the Neutral Bus. -
Reinstall cover on service disconnect or the electrical panel.
-
Restore power; Green LED should be on indicating full protection.
Specifications
Description | Ratings |
---|---|
Service Voltage | Split Phase 240 VAC |
Short Circuit Current Rating (SCCR) | 200 kA |
Nominal Discharge Current (In) | 20 kA |
SPD Type | Type 1 (Can also be used in Type 2 applications) |
Surge Protection Technology | TFMOV |
Protection Mode | L1-L2, L1-N, L2-N |
VPR (Vpk) | VOLTS (V) MODE VPR (Vpk) |
240 L-L 1200
L-N 700
Maximum Continuous Operation Voltage (MCOV)| L-L: 300 VAC
L-N: 150 VAC
Input Power Frequency| 50/60Hz
Diagnostics| Green LED indicates surge protection present
Enclosure Rating| NEMA/Type 4X water tight plastic enclosure for outdoor
and indoor installation
Installation Point| Electrical panel/disconnect
Dimensions| 4.3” X 4.1” X 2.3”
Operating Temperature| -40°F to 185°F (-40°C to 85°C)
Operating Humidity| Less than 85%, noncondensing
Operating Altitude| Less than 2000 meters
Agency Certification and Approvals| ANSI/UL1449 4th Edition Listed
Device cULus Listed
Wiring Diagrams
Split Phase Configuration
ICM518 is a Type 1 and 2 SPD, designed to be compatible with a 240 VAC Split Phase configuration. Please check your supply voltage configuration and voltage levels before installing the ICM518 per wiring diagrams below
Note 1 :
For the ease of checking the SPD protection status, the LED display should
face outwards after installation has been complete.
Note 2:
ICM518 is a Type 1 and 2 SPD, designed to be compatible with 240 VAC Split
Phase configuration. Please check your supply voltage configuration and
voltage levels before installing the ICM518 per wiring diagram
Note 3:
When installing the Surge Protecting Device (SPD), avoid sharp bends in the
conduit and long line sets.
Keep the mounting conduit straight and short in length.
LIMITED LIFETIME PROTECTION WARRANTY
Review enclosed warranty information for full details & registration
information
For warranty registration, please go to
www.icmcontrols.com and click on Warranty
Registration
7313 William Barry Blvd., North Syracuse, NY 13212
www.icmcontrols.com