ELKO ep PMS3-01 Ultra Slim PIR Motion Detector Owner’s Manual
- August 13, 2024
- ELKO ep
Table of Contents
ELKO ep PMS3-01 Ultra Slim PIR Motion Detector
Characteristics
- The PMS3-01 is a highly versatile and compact motion sensor designed for ceiling or surface mounting applications. With its ultra-slim design, the PMS3-01 seamlessly integrates into various environments, providing reliable and efficient motion detection capabilities.
- The sensor is powered by a 27 VDC power source, specifically the INELS BUS system, ensuring stable and efficient operation.
- The PMS3-0l utilizes a infrared for precise and reliable motion detection.
- The sensor provides a wide 360-degree detection angle, ensuring comprehensive coverage of the monitored area.
- The sensor’s reach is up to 6m max, allowing the user to install the unit at a height of 2.5 m-3.5 m, providing flexibility for different applications.
- The PMS3-01 includes a software function to set the sensor activation time in the IDM3 software.
- Designed to operate effectively in various environmental conditions, the sensor has a wide working temperature range of -10°( to +40°C, ensuring reliable performance in different settings.
- The PMS3-01 can be seamlessly integrated and combined with other INELS units using the IDM3 software. This allows for the implementation of additional logics and functions, enabling automation and customized control scenarios based on specific requirements.
- The PMS3-01 features a compact form factor with dimensions of 115 x 24 mm, facilitating easy installation and integration into different ceiling or surface mounting applications.
Description of device
- Lens
- BUS terminals
- Frame
Connection
Technical parameters
Function
Function | 360° |
---|---|
Time setting: | in IDM software |
Recommended installation height: | 2.5 – 3.5 m |
Communication
Terminals: | EIB Ø 0.3 – 0.8 mm2 |
---|---|
Interface: | installation INELS BUS |
Power supply
From INELS BUS: | 27 V DC, -20/+ 1 O %, 20 mA |
---|
Operating conditions
Work temperature: | -10 to 40 °C |
---|---|
Operation position: | free |
Installation: | celling/surface |
Dimension and weight
Dimension: | 115x24mm |
---|---|
Standards: | EN 63044-1 |
General Instructions
CONNECTION TO THE SYSTEM, INSTALLATION BUS
INELS 3 peripheral units are connected to the system through the BUS installation. Installation BUS conductors are connected to the terminal units to BUS+ and BUS- terminals, wires cannot be interchanged. For installation of BUS it is necessary to use a cable with a twisted pair of wires with a diameter of at least 0.8 mm, the recommended cable is INELS BUS Cable, whose features best meet the requirements of the BUS installation. Bearing in mind that in terms of all the properties is it is possible in most cases also use the cable JYSTY 1x2x0.8 or JYSTY 2x2x0.8, however it is not recommended as the best option. In the case of a cable with two pairs of twisted wires it is not possible to use the second pair of the other for modulated signal due to the speed of communications; it ‘is not possible within one cable to use one pair for one segment BUS and the second pair for the second segment BUS. For installation of BUS it is vital to ensure that it is kept at a distance from the power lines of at least 30 cm and must be installed in accordance with its mechanical properties. To increase mechanical resistance of cables we recommend installation into a conduit of suitable diameter. BUS topology installation is free except for the ring, wherein each end of the bus must terminate at the terminals BUS + and BUS- peripheral unit. While maintaining all the above requirements, the maximum length of one segment of the installation BUS can reach up to 300 m. Due to the data communication and supply of units in one pair of wires, it is necessary to keep in mind the diameter of wires with regards to voltage loss on the lead and the maximum current drawn. The maximum length of the BUS applies provided that they comply with the tolerance of the supply voltage.
CAPACITY AND CENTRAL UNIT
It is possible to connect to the central unit CU3-01M/02M or mini CU CU3-07/08/09/10M independent BUSes by means of terminals BUS1+, BUS1- or BUS2+, BUS2-. It is possible to connect to each BUS up to 32 units, so it is possible to connect directly to the central unit a total of 64 units. It is necessary to comply with the requirement of a maximum load of one BUS line – maximum up to 1000 mA current. When connecting units which draw greater than 1A, BPS3- 01 M with 3A sampling can be used. It is the sum of the rated currents of the units connected to the BUS line, other units can be connected using the units Ml3-02M (for CU3-01 M/02M), which generate further BUSes. These are connected to the CU3-01 M/02M unit via the system BUS EBM and you can connect a total of 8 units via EBM BUS to the central unit Ml3-02M.
SUPPLYING THE SYSTEM
For supplying power to system units, it is recommended to use the power source of ELKO EP titled PSM3-30/INELS, PSM3-60/INELS, PSM3-100/INELS or PS3-30/INELS . We recommend backing up the system with backup batteries.
GENERAL INFORMATION
To operate the unit, it is necessary that the unit is connected to a central unit CU3 series, connected to the central unit of the system CU3, or to a system that already contains this unit as its expansion to include further system. All unit parameters are set through the central unit CU3-0XM in the software IDM3. There is LED diode on the PCB for indication of supply voltage and communication with the central unit series CU3. In case that the RUN diode fl ashes at regular intervals, so there is standard communication between the unit and BUS. If the RUN diode lights permanently, so the unit is supplied from BUS, but there is no communication between BUS and unit. In case that RUN diode is OFF, so there is no supply voltage on the terminals BUS+ and BUS-.
Warning
Before the device is installed and operated, read this instruction manual carefully and with full understanding and Installation Guide SystemINELS 3. The instruction manual is designated for mounting the device and for the user of such device. It has to be attached to electro installation documentation. The instruction manual can be also found on a web site www.inels.com. Attention, danger of injury by electrical current! Mounting and connection can be done only by a professional with an adequate electrical qualification, and all has to be done while observing valid regulations. Do not touch parts of the device that are energized. Danger of life-threat! While mounting, servicing, executing any changes, and repairing it is essential to observe safety regulations, norms, directives and special regulations for working with electrical equipment. Before you start working with the device, it is essential to have all wires, connected parts, and terminals de-energized. This instruction manual contains only general directions which need to be applied in a particular installation. In the course of inspections and maintenance, always check (while de- energized) if terminals are tightened.
CUSTOMER SUPPORT
TECHNICAL SUPPORT
Email: support@inels.com
Mobil: +420 777 356 466
Tel.: +420 573 514 276, +420 573 514 211
Fax: +420 573 514 227
www.inels.com
Made in Czech Republic