ELKO EP ATS-1DR Analog Clock With Daily User Manual
- June 9, 2024
- ELKO ep
Table of Contents
ATS-1DR
Analog time switch with daily program
User Manual
Characteristics
- The mechanical time switch is a simple and inexpensive alternative to digital time switches for controlling real-time heating, ventilation, cooling, lighting or pump systems:
- Daily program
- Selection of operating modes using a switch on the panel: switches automatically according to the set program closes permanently
- Power reserve after power faiture up to 100 hours, after fully charged.
Connection
Time setting – daily program
Do not turn against the of rotation of the programming dial
Description
- Transparent opening cover
- Output contact (1-2)
- Rotation of the programming dial
- Time indicator
- Operating mode switch
- Supply voltage terminals (L-N)
Settings
Minimum switching interval:
– daily, 15 minutes (1 segment)
High temperatures can aff ect the accuracy of the time switches
Push segments left – off Push segments to the right – on
Example:
10:00 … 11:00 ON
11:00 … 11:15 OFF
11:15 … 11:30 ON
11:30 … 12:00 OFF
12:00 … 13:00 ON
Operating mode
- = permanently closes
- = switches automatically according to the set program
Power reserve
Approximately 100 hours after being connected to the power supply, the power
reserve reaches it´s complete charge of 100 hours.
Technical parameters
TS-1DR
Supply
Supply terminals: | L-N |
---|---|
Supply voltage: | AC 230 V (50/60 Hz) |
Power consumption (max.): | 1.5 VA/1 W |
Supply voltage tolerance: | -10%;+10% |
Time circuit
Program: | daily |
---|---|
Number of switching segments: | 96 |
Minimum switching interval: | 15 mins |
Operating accuracy: | ±2s/day at 25 °C |
Power reserve: | max. 100 hrs |
Output
Number of contacts: | lx NO (AgCd015) |
---|---|
Rated current: | 16 A/AC1 |
Breaking capacity: | 4000 VA/AC1 |
Switching voltage: | 250VAC |
Mechanical life: | 100.000 ops. |
Electrical life (AC1): | 30.000 ops. |
Other information
Operating temperature: | -10 .. +50°C (14 .. 122 °F) |
---|---|
Storage temperature: | -10.. +50°C (14..122°F) |
Dielectric strength: | 4 kV (supply – output) |
Operating position: | any |
Mounting: | DIN rail EN 60715 |
Protection degree: | IP20 |
Overvoltage category: | III. |
Pollution degree: | 2 |
Cross-wire section – solid/stranded with ferrule (mm’): | max. lx 4, 2x 2.5/ |
max. lx 4(12 AWG)
Dimensions:| 90 x 18 x 66mm (3,55-x 0,71-x
Weight:| 70 g (2.5 oz)
Standards:| EN 61812-1, EN 60730
Warning
Device is constructed for connection in 1-phase network AC 230 V and must be
installed according to norms valid in the state of application. Connection
according to the details in this direction.
Installation, connection, setting and servicing should be installed by qualifi
ed electrician staff only, who has learnt these instruction and functions of
the device. This device contains protection against overvoltage peaks and
disturbancies in supply. For correct function of the protection of this device
there must be suitable protections of higher degree (A, B, C) installed in
front of them.
According to standards elimination of disturbancies must be ensured. Before
installation the main switch must be in position “OFF” and the device should
be de-energized. Don´t install the device to sources of excessive electro-
magnetic interference. By correct installation ensure ideal air circulation so
in case of permanent operation and higher ambient temperature the maximal
operating temperature of the device is not exceeded. For installation and
setting use screw-driver cca 2 mm. The device is fully-electronic –
installation should be carried out according to this fact. Nonproblematic
function depends also on the way of transportation, storing and handling. In
case of any signs of destruction, deformation, non-function or missing part,
don´t install and claim at your seller it is possible to dismount the device
after its lifetime, recycle, or store in protective dump.