ELKO ep ZSR-30 Power Supply Instruction Manual
- June 6, 2024
- ELKO ep
Table of Contents
ELKO ep ZSR-30 Power Supply
Characteristics
Regulated stabilized power supply ZSR-30
- supply of various devices and appliances by safe voltage with fully galvanic sepa-ration from the main.
- input voltage: AC 230 V
- output voltage: DC 5-24 V stab., DC 24 V unstab. and AC 24 V
- exceeded current limit values is indicated by LED fl ashing
- when there is full short-circuit, output is disconnected, output – current is limited by an electronic fuse
- 3-MODULE, DIN rail
Power supply ZNP-10
- AC and DC output voltage 24V, non-stabilized
- power supply with fi xed output voltage
- protection against short-circuit and overload by a safety fuse
- input voltage: AC 230 V
- 3-MODULE, DIN rail mounting
Description
- Supply terminals
- Setting of output voltage DC
- AC output voltage
- DC unregulated output voltage and unstabilized
- DC output regulated voltage and stabilized
Connection
WARNING!
Total loads on all output terminals may not exceed this values: by supplying
230V… 253V – 8W from 230V… 207V output power is eaqualy decreesing onto 5W
Technical parameters
Supply voltage: | AC 230 V / 50 – 60 Hz |
---|---|
Input without load (max): | 6 VA / 1.2 W |
Input with load (max): | 20 VA / 20 W |
Supply voltage tolerance: | -15 %; +10 % |
Output voltage: | DC 5-24 V stab. DC 24 V nonstab. |
AC 24 V
|
DC 24 V nonstab.
AC 24 V
---|---|---
Output voltage-no load AC:| 32 V
Output voltage-no load DC:| 44 V
Fuse (in primar winding):| primary wind T100 mA
Wave of output voltage:| 300 mV| max. 3 V
Efficiency:| 75 %| x
Tolerance of output voltage:| ±5 %| x
Electronic fuse:| Towards black-out and
current overloading
|
x
Operating temperature: | -20.. +40°C (-4 °F to 104 °F) |
---|---|
Storing temperature: | -20.. +60°C (-4 °F to 140 °F) |
Electrical strenght (prim/sec): | 4 kV |
Protection degree: | IP40 from front panel / IP20 terminals |
Max. cable size (mm2): | solid wire max.1x 2.5 or 2x 1.5 / with sleeve max.1x |
1.5 (AWG 12)
Dimensions:| 90 x 52 x 65 mm (3.5˝ x 2˝ x 2.6˝)
Weight:| 398 g (14 oz.)| 368 g (13 oz.)
Standards:| EN 61204-1, EN 61204-3, EN 61204-7
WARNING!
Values of max. load are valid for (operational) temperature. Device is
constructed for connection for 1-phase main alternating-current voltage and
must be installed according to norms valid in existing state. Connection
according to the details in this direction. installation, connection, setting
and servicing should be installed by qualifi ed electrician staff only, who
learn this instruction and functions of the device.For right device protection
should be a fronted-end certain element. Before starting installation must be
main switch in position “SWITCH OFF” and device should be out of voltage.
Don´t install device to suppliers surcharge electromagnetic interference. By
right installation of device is provide good air circulation to don´t pass
maximal operating temperature,in case of higher ambient temperature and
permanent working. For installation and setting use screw-driver cca 2 mm. The
device is full-electronic – installation should be effected according to this.
Function without problems is too dependent on the previous type of
transportation, storing and manipulation. In case of any vestige of
destruction, deformation, non-function or missing part, don´t install and made
claim to seller. Product may be ,after passing operating time, disassembled,
recycled or puted on the protected tip.