Schneider Electric SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible Power Supply Instruction Manual

June 17, 2024
Schneider Electric

Operation Manual
Smart-UPS™ On-Line SRT
Uninterruptible Power Supply

SRT8KXLI/SRT8KRMXLI/SRT8KXLT/SRT8KRMXLT/SRT8KXLT-IEC
SRT8KRMXLT-IEC/SRT10KXLI/SRT10KRMXLI/SRT10KXLT/SRT10KRMXLT
SRT10KXLT-IEC/SRT10KRMXLT-IEC
208/220/230/240 Vac
Tower/Rack-Mount 6U

Product Description

The APC™ by Schneider Electric Smart-UPS™ On-Line SRT is a high performance uninterruptible power supply (UPS). The UPS helps provide protection for electronic equipment from utility power blackouts, brownouts, sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are completely discharged. This user manual is available on the enclosed Documentation CD and on the APC web site, www.apc.com.

General Information

Safety Messages
Read the instructions carefully to become familiar with the equipment before attempting to install, operate, service or maintain the UPS. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol to a Danger or Warning product safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
The addition of this symbol to a Warning or Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed.

CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.
NOTICE
NOTICE addresses practices not related to physical injury including certain environmental hazards, potential damage or loss of data.

Safety and General Information

  • Adhere to all national and local electrical codes.

  • All wiring must be performed by a qualified electrician.

  • Changes and modifications to this unit not expressly approved by APC could void the warranty.

  • This unit is intended only for indoor use in a controlled environment.

  • Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.

  • Be sure the air vents on this unit are not blocked. Allow adequate space for proper ventilation.

  • For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.

  • The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life.

  • Replace the battery immediately when the UPS indicates battery replacement is necessary.

  • The UPS will recognize as many as 10 external battery packs connected to the UPS.
    If more that 10 XLPBs are to used, the communication cables for XLPBs number 11 and over must be disconnected.
    Note: For each XLBP that is added, increased recharge time will be required.

  • The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.

  • The batteries are heavy. Remove the batteries before installing the UPS and external battery packs (XLBPs), in a rack.

  • Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the XLBPs.

  • Always install peripheral equipment above the UPS in rack-mount configurations.

  • Additional safety information can be found in the Safety Guide supplied with this unit.

Deenergizing safety
The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch circuit (mains). Before installing or servicing the equipment verify the following:

  • Mains circuit breaker is in the OFF position.
  • Internal UPS batteries are removed.
  •  XLBP battery modules are disconnected.

Electrical safety

  • For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a qualified electrician.
  • 230 V models only: In order to maintain compliance with the EMC directive for products sold in Europe, output cords attached to the UPS must not exceed 10 meters in length.
  • The protective earth conductor for the UPS carries the leakage current from the load devices (computer equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the UPS. The conductor must have the same size and insulation material as the grounded and ungrounded branch circuit supply conductors. The conductor will typically be green and with or without a yellow stripe.
  • The UPS input ground conductor must be properly bonded to protective earth at the service panel.
  • If the UPS input power is supplied by a separately derived system, the ground conductor must be properly bonded at the supply transformer or motor generator set.

Battery safety

  • Before installing or replacing the batteries, remove jewelry such as wristwatches and rings. High short circuit current through conductive materials could cause severe burns.
  • Do not dispose of batteries by burning them. The batteries may explode.
  • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.

Hardwire safety

  • Verify that all branch circuit (mains) and low voltage (control) circuits are deenergized, and locked out before installing cables or making connections, whether in the junction box or to the UPS.
  • Wiring by a qualified electrician is required.
  • Check national and local codes before wiring.
  • Strain relief is required for all hardwiring (not supplied). Snap in type strain reliefs are recommended.
  • All openings that allow access to UPS hardwire terminals must be covered. Failure to do so may result in personal injury or equipment damage.
  • Select wire size and connectors according to national and local codes.

General information

  • The UPS will recognize as many as 10 external battery packs connected to the UPS. However there is no limit to the number of XLBPs that can be used with the UPS.
    Note: For each XLBP added, increased recharge time will be required.

  • The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the chassis under the front bezel.

  • Always recycle used batteries.

  • Recycle the package materials or save them for reuse.

Product Overview

Specifications
For additional specifications refer to the APC web site, www.apc.com.
Environmental

Temperature Operating 0° to 40° C (32° to 104° F)
Storage -15° to 45° C (5° to 113° F)
Maximum Elevation Operating 0 – 3,000 m (0 – 10,000 ft)
Storage 0 – 15,000 m (0 – 50,000 ft)
Humidity 0% to 95% relative humidity, non-condensing
Protection Class IP 20 rating

Note: Charge the battery modules every six months during storage.
Environmental factors impact battery life. Elevated ambient temperatures, high humidity, poor quality mains power, and frequent short duration discharges will shorten battery  life.

Physical
The UPS is heavy. Follow all lifting guidelines.

Lifting guidelines >55 kg (>120 lb)
Unit weight without packaging 111.82 kg (246 lb)
Unit weight with packaging Rack-Mount models: 130 kg (286 lb)

Tower models: 126.82 kg (279 lb)
Unit dimensions without packaging Height x Width x Depth| 263 mm x 432 mm x 715 mm
10.35 in x 17 in x 28.15 in
Unit dimensions with packaging Height x Width x Depth| 461 mm x 600 mm x 1000 mm
18.2 in x 23.62 in x 39.4 in
The model and serial numbers are on a small label located on the rear panel.

Battery

Battery type Maintenance free, leak proof, sealed, lead acid

Replacement battery module
This UPS has replaceable battery modules.
Refer to the appropriate replacement battery user manual for installation instructions.
Contact your dealer or go the APC web site, www.apc.com for information on replacement batteries.| APCRBC140
Number of battery modules| 4 battery modules
Voltage for each battery module Total voltage for the UPS Ah rating| 96 VDC
± 192 VDC
5.1 Ah per battery module
XLBP cable length| 500 mm (19.7 in)

Electrical

Models Rating
SRT8KXLT 8 kVA/8 kW

SRT8KRMXLT
SRT8KXLT- IEC
SRT8KRMXLT- IEC
SRT8KXLI
SRT8KRMXLI
SRT10KXLT| 10 kVA/10 kW
SRT10KRMXLT
SRT10KXLT- IEC
SRT10KRMXLT- IEC
SRT10KXLI
SRT10KRMXLI
Output

Output Frequency| 50 Hz/60 Hz ± 3 Hz
Nominal Output Voltage| SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI: 220Vac/230Vac/240Vac SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT: 208Vac/240Vac
SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC: 208Vac/240Vac
Input
Input Frequency| 40 Hz-70 Hz
Nominal Input Voltage| SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI: 220Vac/230Vac/240Vac SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT: 208Vac/240Vac
SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC: 208Vac/240Vac

Front panel features

  1. UPS Display Interface panel
  2. UPS battery compartment doors x2
  3. UPS battery connectors x4
  4. Bezels x2

Schneider Electric SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible
Power Supply - Front panel features

Rear panel features
Note: Refer to the table “Key to identify rear panel features” on page 8, that provides a key to the callout numbers for the rear panel graphics depicted in this manual.
SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT

Schneider Electric SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible
Power Supply - Rear panel features

SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC

Schneider Electric SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible
Power Supply - Rear panel features 2

SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI

Schneider Electric SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible
Power Supply - Rear panel features 3

Key to identify rear panel features

1 Network port Use the Network port to connect the UPS to the network.
2 Console port Use the Console port to configure the network

management features.
3| Universal I/O port| Use to connect:
•  Temperature sensor AP9335T (supplied)
•  Temperature/humidity sensor AP9335TH (not supplied)
•  Relay input/output connector AP9810 (not supplied), supports two input contacts and one output relay
4| USB port| The USB port is used to connect either a server for native operating system communications, or for software to communicate with the UPS.
Note: Serial and USB communication should not be used simultaneously. Use either the Serial Com or the USB port.
5| Serial Com| The Serial Com port is used to communicate with the UPS.
Use only interface kits supplied or approved by APC by Schneider Electric. Any other serial interface cable will be incompatible with the UPS connector.
6| EPO terminal| The Emergency Power Off (EPO) terminal allows the user to connect the UPS to a central EPO system.
7| Controllable outlet group 1, with circuit breaker| Connect electronic devices to these outlets.
In the event an overload condition occurs, disconnect nonessential equipment. Then reset the circuit breaker.
8| Controllable outlet group 2, with circuit breaker| Connect electronic devices to these outlets.
In the event an overload condition occurs, disconnect nonessential equipment. Then reset the circuit breaker.
9| Controllable outlet group 3, with circuit breaker| Connect electronic devices to these outlets.
In the event an overload condition occurs, disconnect nonessential equipment. Then reset the circuit breaker.
10| AC output inspection panel| Remove the panel to inspect the output terminal block wiring configuration. The terminal block is located behind the inspection cover.
Refer to “Wiring Specifications” on page 9 for hardwire specifications.
11| AC input inspection panel| Remove the panel to inspect the input terminal block wiring configuration. The terminal block is located behind the inspection cover.
Refer to “Wiring Specifications” on page 9 for hardwire specifications.
12| AC hardwire knockouts| Remove the 38.1 mm (1.5 in) knockout panels for AC input and output hardwiring. Install appropriate strain reliefs (not supplied).
13| Hardwire box input/output| Remove the box to connect input and output wires to the hardwire terminal blocks.
14| Chassis ground screws| The UPS and XLBPs have ground screws for connecting the ground leads. Prior to connecting a ground lead, disconnect the UPS from mains power.
15| External battery power and communication connectors| Use the external battery power and communication cables to connect the UPS and XLBP. XLBPs provide extended runtime during power outages.

The UPS will automatically recognize up to 10 external battery packs.

16| SmartSlot| The SmartSlot can be used to connect optional management accessories.
17| PRL COMM port| This port is not used with these products.
18| Reset button| Use the Reset button to restart the Network Management Interface.
Note: A restart of the Network Management Interface does not affect UPS operation.

Wiring Specifications
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL

  • Adhere to all national and local electrical codes.

  • Wiring should be performed by a qualified electrician.

  • Strain reliefs are not supplied with the unit. 38.1 mm (1 1/2 in) snap in type strain reliefs are recommended.

  • The UPS must be wired into a branch circuit, equipped with a circuit breaker rated as specified in the tables below.

  • Actual wire size must comply with required ampacity and national and local electrical codes.
    Select wire size based on wire insulation, installation method, and environmental conditions.

  • Recommended input terminal screw torque:
    16 mm2 or 6 AWG = 5.09 Nm (45 lbf-in)
    25 mm2 or 4 AWG = 5.09 Nm (45 lbf-in)
    4 mm2 or 12 AWG = 3.969 Nm (35 lbf-in)

Failure to follow these instructions can result in equipment damage and minor or moderate injury

Single Feed| | | | | |
---|---|---|---|---|---|---
System| Wiring| Number of Phases| Voltage| Current Full Load (nominal)| External Input Circuit Breaker Mains (typical)| Wire Size Mains (typical)
SRT8KXLT| Input| 1| 208/240 Vac| 47 A| 60 A / 2-pole| 16 mm2 or 6 AWG
Output| 1| 208/240 Vac| 40 A| | 16 mm2 or 6 AWG
SRT10KXLT| Input| 1| 208/240 Vac| 56 A| 70 A / 2-pole| 25 mm2 or 4 AWG
Output| 1| 208/240 Vac| 49 A| | 16 mm2 or 6 AWG
SRT8KXLI| Input| 1| 220/230/240 Vac| 44 A| 63 A / 2-pole| 16 mm2 or 6 AWG
Output| 1| 220/230/240 Vac| 38 A| | 16 mm2 or 6 AWG
Input| 3| 380/400/415 Vac| 15 A
44 A | 63 A / 4-pole| 16 mm2 or 6 AWG
Output| 1| 220/230/240 Vac| 38 A| | 16 mm2 or 6 AWG
SRT10KXLI| Input| 1| 220/230/240 Vac| 54 A| 80 A / 2-pole| 25 mm2 or 4 AWG
Output| 1| 220/230/240 Vac| 47 A| | 16 mm2 or 6 AWG
Input| 3| 380/400/415 Vac| 18 A
54 A
| 80 A / 4-pole| 25 mm2 or 4 AWG
Output| 1| 220/230/240 Vac| 47 A| | 16 mm2 or 6 AWG

  • Phase 1 (L1) current while in bypass mode

Dual Feed

System| Wiring| Number of Phases| Voltage| Current Full Load (nominal)| External Input Circuit Breaker Mains (typical)| External Input Circuit Bypass Mains (typical)| Wire Size Mains (typical)| Wire Size Bypass (typical)

SRT8KXLI

| Input| 1| 220/230/240 Vac| 44 A| 63 A / 2-pole| 63 A / 2-pole| 16 mm2 or 6 AWG| 16 mm2 or 6 AWG
Input| 3| 380/400/415 Vac| 15 A| 20 A / 4-pole| 63 A / 2-pole| 4 mm2 or 12 AWG| 16 mm2 or 6 AWG
Output| 1| 220/230/240 Vac| 38 A| | | 16 mm2 or 6 AWG| 16 mm2 or 6 AWG
SRT10KXLI| Input| 1| 220/230/240 Vac| 54 A| 80 A / 2-pole| 80 A / 2-pole| 25 mm2 or 4 AWG| 25 mm2 or 4 AWG
Input| 3| 380/400/415 Vac| 18 A| 25 A / 4-pole| 80 A / 2-pole| 4 mm 2 or 12 AWG| 25 mm2 or 4 AWG
Output| 1| 220/230/240 Vac| 47 A| | | 16 mm2 or 6 AWG| 16 mm2 or 6 AWG

Connect Equipment
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL

  • Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment.
  • Disconnect internal and external batteries before installing or servicing the UPS or connected equipment.
  • The UPS contains internal and external batteries that may present a shock hazard even when disconnected from the mains.
  • UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
  • Disconnect equipment from the UPS before servicing any equipment.
    Do not use the UPS as a safety disconnect.

Failure to follow these instructions can result in equipment damage and minor or moderate injury.

Note: The UPS batteries will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period.

  1. Connect the UPS to the building utility power. Refer to the UPS Installation Guide.
  2. Connect equipment to the outlets on the rear panel of the UPS.
    Refer to “Controllable Outlet Groups” on page 19.

Turn the UPS On/Off
The first time the UPS is turned on the Setup Wizard screen will run. Follow the prompts to configure UPS settings.
Refer to “Configuration” on page 15.
To turn on the UPS and all connected equipment, press the Power ON/OFF button on the display panel. Follow the prompts to either turn the UPS on immediately or after a delay, then press OK.
NOTE: When there is no input power and the UPS is off, the cold start feature can be used to turn on the UPS and connected equipment using battery power.
To perform a cold start press the Power ON/OFF button.
The display panel will illuminate and the Power ON/OFF button will illuminate red.
To turn on the output power press the Power ON/OFF button again. Select the prompt Turn ON with NO AC and press OK.
To turn output power off, press the Power ON/OFF button. Follow the prompts to either turn the UPS off immediately or after a delay, then press OK.
NOTE: Once the AC power has been turned off the UPS will continue operating on battery power for a short period of time. To remove power completely press the Power ON/OFF button. Follow the prompt to select Internal Power Off, then press OK.

UPS Display Interface

1| POWER ON/OFF button
Button illumination indications:
-No illumination, the UPS and the output power are off
-White illumination, the UPS and the output power are on
-Red illumination, the UPS is on and the output power is off|
---|---|---
2| Load icon
Disable/mute audible alarm icon
3| UPS status information
4| Operation mode icons
5| ESCAPE button
6| OK button
7| UP/DOWN buttons
8| Controllable outlet group status icons
9| Battery status icons
The icons on the LCD display interface screen may vary depending on the installed firmware version.

| Load icon: The approximate load capacity percentage is indicated by the number of load bar sections illuminated. Each bar represents 16% of the load capacity.
**| Mute icon: Indicates the audible alarm is disabled/mute.
UPS Status Information
The status information field provides key information on the status of the UPS. The Standard menu will allow the user to select one of the following screens. The Advanced menu will scroll through the following five screens.
Input Voltage Output Voltage Output Frequency Load
Runtime
In the case of a UPS event, status updates will be displayed defining the event or condition that has occurred.
The display screen illuminates amber to indicate a Warning and red to indicate an Alert depending on the severity of the event or condition.
Operation Mode Icons**

**| On-Line mode: The UPS is supplying conditioned mains power to connected equipment.
**
| Bypass mode: The UPS is in Bypass mode and the connected equipment will receive mains power as long as the input voltage and frequency are within the configured limits.
**| Green mode : When in Green mode mains power is sent directly to the load.
In the event of a mains power outage, there will be an interruption in power to the load of up to 8 ms while the UPS switches to
On-Line or Battery mode.
When enabling
Green mode consideration should be given to devices that may be sensitive to power fluctuations.
**
| Battery mode: The UPS is supplying battery power to connected equipment.
Controllable Outlet Group Icons
**| Controllable Outlet Group Power Available: The number next to the icon identifies the specific outlet groups that have available power.
**
| Controllable Outlet Group Power Not Available: The number next to the icon identifies specific outlet groups that do not have available power.
Battery Status Icons
**| Battery Charge Status: Indicates the battery charge status.
**
| Battery Charge In Progress: Indicates the battery is charging.

UPS Display Interface operation
Use the UP/DOWN buttons to scroll through the options. Press the OK button to accept the selected option. Press the ESC button to return to the previous menu.

Menu overview
The UPS Display Interface has Standard and Advanced menu screens. The preference for Standard or Advanced menu selections is made during initial installation and can be changed at any time through the Configuration menu.
The Standard menus include the most commonly used options.
The Advanced menus provide additional options.
Note: Actual menu screens may differ by model and firmware version.

LCD display interface angle adjustment
The angle of the LCD display interface can be adjusted for ease in viewing the displayed messages.

  1. Remove the front bezel.
  2. Locate the button on the bottom of the display interface panel.
  3. Press the button and slide the bottom of the LCD display interface screen out. An audible click will be heard when the screen reaches the maximum angle.

Configuration Menu s Overview

Schneider Electric SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible
Power Supply - Configuration Menus Overview

Configuration

UPS Settings
There are four ways to select UPS configuration options.

  1. The first time the UPS is turned on the Setup Wizard screen will open. On each menu screen select the desired settings. Press OK after each UPS setting is selected.

Note: The UPS will not turn on until all of the settings have been configured.
Startup configuration

Function Description
Select the language required for the UPS Display Interface. Language

options will vary by model and firmware version.
Options:
•  English
•  Francais
•  Italiano
•  Deutch
•  Espanol
•  Portugues
•  Russian
| Available output voltage selection will vary depending on the model. Select the output voltage.
Options:
•  208 Vac
•  220 Vac
•  230 Vac
•  240 Vac
| The Standard menu options are the most commonly used options.
The Advanced menu options will be used by IT professionals who need detailed configuration and reporting information.

General settings
Configure these settings at any time, using the UPS Display Interface, or the Network Management web Interface.

| Parameters| Default Value| Options| Description
---|---|---|---|---
Config Menu UPS| Green Mode| Disabled| Disable Enable| Disable or enable Green mode operation
AC Setting| User Choice| 230 V, 220 V, 240V, 208 V| Set the output voltage for the UPS. This setting can only be changed when the UPS output is off.
These settings may vary depending on the UPS model.
Output Lower Acceptable Voltage| 184 V for 208 V output
198 V for 220 V output
207 V for 230 V output
216 V for 240 V output| 208 V – 169 to 184 V
220 V – 186 to 198 V
230 V – 195 to 207 V
240 V – 204 to 216 V| If the UPS input voltage is between the lower acceptable voltage and the higher acceptable voltage, the UPS will operate in Green mode when enabled.
Output Upper Acceptable Voltage| 220 V for 208 V output
242 V for 220 V output
253 V for 230 V output
264 V for 240 V output| 208 V – 220 to 235 V
220 V – 242 to 253 V
230 V – 253 to 265 V
240 V – 264 to 270 V| If the output voltage goes outside the acceptable range the UPS will switch from Green mode to On-Line mode or to Battery mode.
Output Frequency| Auto 50/60 ± 3 Hz| Auto 50/60 ± 3 Hz
50 ± 0.1 Hz
50 ± 3.0 Hz
60 ± 0.1 Hz
60 ± 3.0 Hz| Set the output frequency for the UPS.
Output Frequency Slew Rate| 1 Hz/Sec| 0.5 Hz/Sec
1 Hz/Sec
2 Hz/Sec
4 Hz/Sec| Select the rate of change for output frequency in Hertz per second.
Bypass Lower Acceptable Voltage| 160 V| 208 V – 160 to 184 V
220 V – 160 to 198 V
230 V – 160 to 207 V
240 V – 160 to 216 V| If the UPS input voltage is between the lower acceptable voltage and the higher acceptable voltage, the UPS can enter Bypass mode when enabled.
Bypass Upper Acceptable Voltage| 250 V for 208 V output
255 V for 220 V output
265 V for 230 V output
270 V for 240 V output| 208 V – 220 to 250 V
220 V – 242 to 264 V
230 V – 253 to 270 V
240 V – 264 to 270 V
Bypass Frequency Setting| Wider Frequency| Wider Frequency
Use O/P Frequency Setting| The setting Wider Frequency , enables Bypass mode operation for an input frequency range of 47-63 Hertz.
Battery Conserve Mode| Enable| Enable/Disable| When enabled this setting conserves battery by switching to Bypass source.
Disable Bypass| No| Yes/No| The UPS will not go to Bypass mode.
When UPS detects a fault the load will be dropped.
Low Runtime Warning| 150 seconds| 0 to 1800 seconds| The UPS will emit an audible alarm when the remaining runtime has reached this threshold.
Self Test Schedule| Startup + every 14 days since last test| Never Startup
Startup + 14 days Startup + 7 days| This is the interval at which the UPS will execute a

Self Test.

Default Setting| No| Yes/No| Allows the user to restore the UPS factory default settings.
Reset Energy Meter| No| Yes/No| The Energy Meter stores information on UPS output energy usage.
The Reset feature allows the user to reset the Energy Meter to 0 kWh.
| Parameters| Default Value| Options| Description
---|---|---|---|---
Config Menu Battery| Install Date| Battery Installation Date| Month-Year| Enter the installation date of the RBCs.
Replacement Notification Time| 180 days| 0-360 days| To set the Near End of Life alarm, select the number of days before the estimated battery end of life.
When this date is reached the UPS will emit an alarm and a message will appear on the UPS Display Interface screen.
Example: Using the default value, the Near End of Life alarm will occur 180 days before the estimated end of life date.
Replacement Battery Alarm Time| 14 days| 0-180 days| The Near End of Life alarm can be muted.
Enter the number of days between the time a Near End of Life alarm is acknowledged and the next Near End of Life alarm occurs.
Config Menu Display| Language| English| English Francais Italiano Deutch Espanol Portugues Russian| Select the language required for the UPS Display Interface.
Language options will vary by model and firmware version.
Beeper Volume| Loud| Disable Enable
• Soft
• Medium
• Loud| When audible alarms are disabled, the UPS will never emit an audible alarm.
Select the volume level for alarms when Enable is selected.
LCD Back Light| Auto Dim| Always On Auto Dim Auto Off| To conserve energy, the LCD back light illumination dims or turns off when no events are active.
Full UPS Display Interface illumination returns when the UPS changes status as a result of an event or when any button on the UPS Display Interface is pressed.
LCD Setting| Optimal Values| Color Brightness Contrast| Adjust the brightness and contrast individually for each LCD back light color.


Menu Type

| User Choice| Standard Advanced| The Standard menus include the most commonly used options.
The Advanced menu options include all parameters.
| Parameters| Default Value| Options| Description
---|---|---|---|---
Config Menu Outlets| Power On Delay| 0 seconds| 0-1800 seconds| Select the amount of time the controllable outlet groups will wait between receiving the command to turn on and actual startup.
Power Off Delay| 90 seconds| 0-32767 seconds| Select the amount of time the controllable outlet groups will wait between receiving the command to shutdown and actual shutdown.
Reboot Duration| 8 seconds| 4-300 seconds| Select the amount of time the controllable outlet groups will remain off before the UPS will restart.
Minimum Return Runtime| 0 seconds| 0-32767 seconds| Select the amount of battery runtime that must be available before the controllable outlet groups will turn on using battery power, after a shutdown.
Loadshed On Battery| Disable| Disable Enable| To conserve battery power the UPS can disconnect power from controllable outlet groups not in use.
To configure the disconnect delay time for this feature use the Loadshed Time On Battery setting.
Loadshed Time On Battery| 5 seconds| 5-32767 seconds| Select the amount of time the controllable outlet groups will be allowed to function on battery power before shutdown.
Loadshed On Runtime| Disable| Disable Enable| To conserve battery power the UPS can disconnect power from controllable outlet groups when the Loadshed Runtime threshold is reached.
Loadshed Runtime| 0 seconds| 0-3600 seconds| When the selected runtime threshold is reached the UPS will shutdown the controllable outlet groups.
Loadshed Overload| Disable| Disable Enable| To conserve energy in the event of an overload condition greater than 105% output, the controllable outlet groups will immediately turn off. The controllable outlet groups will only turn on again with a manual restart command once the overload condition has been corrected.
Config Menu Network Manage| IP Address Mode| | Manual, DHCP, BOOTP| Refer to the Network Management Utility CD.
IP Address| Program IP, Subnet, Gateway

Controllable Outlet Groups

Controllable Outlet Groups provide battery backup power to connected equipment.
Overview
The controllable outlet groups can be configured using the Advanced menu options.
Refer to “General settings” on page 16.
The controllable outlet groups can be configured to independently turn off, turn on, shutdown, switch to Sleep mode, and reboot connected equipment.

  • Turn Off : Disconnect output power to connected equipment either immediately using the Turn Off Immediately feature or after a configured delay using the Turn Off With Delay feature.
    NOTE: Controllable outlet groups can be turned on only using the Turn On feature.

  • Turn On: Connect output power to connected equipment either immediately using the Turn On Immediately feature or after a configured delay using the Turn On With Delay feature.

  • Shutdown: Disconnects the power to connected equipment either immediately or after a configured delay.
    Equipment reconnects after a configured delay when mains power becomes available and other configured conditions are met.
    Each controllable outlet group can be configured separately to allow power sequencing for equipment connected to any controllable outlet group.

  • Reboot: Disconnect the power to connected equipment either immediately or after a configured delay.
    Reconnect equipment after a configured delay when either mains or battery power becomes available and other configured conditions are met.
    Each controllable outlet group can be configured separately to allow power sequencing for loads connected to any controllable outlet group.

  • Sleep: This mode is a reboot with an extended duration where a outlet(s) remain turned off.
    Disconnect the power to connected equipment either immediately or after a configured delay. Reconnect equipment after a configured delay when either mains or battery power becomes available and other configured conditions are met.
    Each controllable outlet group can be configured separately to allow power sequencing for equipment connected to any controllable outlet group.
    To configure Sleep mode use an external interface, such as the Network Management web interface.

  • Automatically turn off or shutdown when certain conditions occur, based on user configurations set using the Config Menu Outlets menus. Refer to “Configuration” on page 15

Connect controllable outlet groups

  • Connect critical equipment to one controllable outlet group.

  • Connect peripheral equipment to the other controllable outlet groups.
    – To conserve battery runtime during a power outage, nonessential equipment can be configured to shut down.
    Use Loadshed Time on Battery Enable/Disable and Loadshed Time on Battery Setting defined in the General Settings section. Refer to “General settings” on page 16.
    – If equipment has dependent peripherals that must restart or shut down in a specific sequence, such as an ethernet switch that must restart before a connected server can be restarted, connect the devices to different outlet groups. Each controllable outlet group can be configured independently of the other groups.

  • Use the Configuration menus to configure how the controllable outlet groups will react in the event of a power outage.

Emergency Power Off

Overview
The Emergency Power Off (EPO) option is a feature that will immediately disconnect all connected equipment from mains power. The UPS will immediately shut down and will not switch to battery power.
Connect each UPS to the EPO switch. In configurations where multiple units are connected in parallel, each UPS must be connected to the EPO switch.
The UPS must be restarted for power to return to connected equipment. Press the ON/OFF button on the front panel of the UPS.

CAUTION
RISK OF DAMAGE TO EQUIPMENT OR PERSONNEL

  • Adhere to all national and local electrical codes.
  • Wiring must be performed by a qualified electrician.
  • Always connect the UPS to a grounded outlet.

Failure to follow these instructions can result in equipment damage and minor or moderate injury.

Normally open contacts

  1. If the EPO switch or relay contacts are normally open, insert the wires from the switch or contacts at pins 1 and 2 of the EPO terminal block. Use 16-28 AWG wire.
  2. Secure the wires by tightening the screws.
    If the contacts are closed, the UPS will turn OFF and power will be removed from the load.

Normally closed contacts

  1. If the EPO switch or relay contacts are normally closed, insert the wires from the switch or contacts at pins 2 and 3 of the EPO terminal block. Use 16-28 AWG wire.
  2. Insert a wire jumper between pins 1 and 2. Secure the wires by tightening the three screws at positions 1, 2, and 3.

If the contacts are opened, the UPS will turn OFF and power will be removed from the load.
Note: Pin 1 is the power source for the EPO circuit, it provides a few milliampere of 24 V power.
If the normally closed (NC) EPO configuration is used, the EPO switch or relay should be rated for “dry” circuit applications, the rating should be for low voltage and low current applications. This normally implies the contacts are gold plated.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect the EPO interface only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. SELV circuits are controlled by a switch or relay properly isolated from mains power. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a SELV circuit.

Use one of the following cable types to connect the UPS to the EPO switch.

  • CL2: Class 2 cable for general use.
  • CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
  • CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
  • CLEX: Limited use cable for use in dwellings and for use in raceways.
  • Installation in Canada: Use only CSA certified, type ELC, (extra low voltage control cable).
  • Installation in countries other than Canada and the USA: Use standard low voltage cable in accordance with national and local regulations.

Install a Ferrite Bead
The supplied ferrite bead must be installed between the supplied EPO terminal block and the EPO switch.

Schneider Electric SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible
Power Supply - Install a Ferrite Bead

Network Management Interface

Introduction
The UPS has a network port and console port that can be used to access the Network Management Interface. The Network Management Interface is very similar to an AP9630 Network Management Card (NMC) that is integrated into a UPS with one universal input/output port.
The Network Management Interface and the AP9630 NMC have the same firmware, operation modes and interaction with other APC products such as PowerChute Network Shutdown.
Refer to the Network Management Card utility CD supplied with this product.

Features
The Network Management Interface allows the UPS to function as a web based, IPv6 ready product.
The Network Management Interface can manage the UPS using multiple open standards such as:

Hypertext Transfer Protocol (HTTP) Secure SHell (SSH)
Simple Network Management Protocol versions 1 and 3 (SNMPv1, SNMPv3)

Hypertext Transfer Protocol over Secure Sockets layer (HTTPS)
File Transfer Protocol (FTP)| Secure Copy (SCP)
Telnet| Syslog
RADIUS|

The Network Management Interface:

  • Provides UPS control and Self Test scheduling features.
  • Provides data and event logs.
  • Enables you to set up notifications through event logging, e-mail, and SNMP traps.
  • Provides support for PowerChute Network Shutdown.
  • Supports using a Dynamic Host Configuration Protocol (DHCP) or BOOTstrap Protocol (BOOTP) server to provide the network (TCP/IP) values.
  • Supports use of Remote Monitoring Service (RMS).
  • Provides the ability to export a user configuration (.ini) file from a configured UPS, to one or more unconfigured UPS without conversion to a binary file.
  • Provides a selection of security protocols for authentication and encryption.
  • Communicates with StruxureWare Central and InfraStruxure Manager.
  • Supports one universal input/output port for connection to a:
    – Temperature probe, AP9335T (supplied)
    – Temperature/humidity sensor, AP335TH (optional)
    – Relay input/output connector that supports two input contacts and one output relay, AP9810 Dry Contact I/O Accessory (optional)

Related Documents
The Network Management Card Utility CD contains the following documentation:

  • UPS Network Management Card 2 User’s Guide
  • Network Management Card Upgrade Utilities
  • Security Handbook
  • PowerNet Management Information Base (MIB) Reference Guide

IP Address Configuration
The default TCP/IP configuration setting DHCP, assumes that a properly configured DHCP server is available to provide TCP/IP settings to the Network Management Interface.
If the Network Management Interface obtains an IPv4 address from a DHCP server, use the UPS Display Interface menus About/Interface, to see the address.
To setup a static IPv4 address use the UPS Display Interface Config menu. Set the IP address Subnet Mask and Gateway from the Config menu.
See the User’s Guide on the Network Management Card Utility CD for user information about the Network Management Interface and for setup instructions.

Smart Battery Management

Definitions

  • Battery Module: A string of battery cells arranged to produce a battery assembly with a connector.
  • Replaceable Battery Cartridge (RBC): An APC battery cartridge consisting of two battery modules. Replacement RBCs can be ordered from the APC web site, www.apc.com.
  • Smart External Battery Pack (XLBP): An enclosure that contains RBC(s) and battery management electronics.
  • User Interface (UI): Any interface by which a user can interact with the system. This may include a UPS display interface, a network management interface or PowerChute™ Network Shutdown software.

NOTE: Do not use a battery that is not APC approved.
The system will not detect the presence of a non APC approved battery and may adversely affect the operation of the system.
Use of a non APC approved battery will void the manufacturer warranty.

Features
Smart Battery Management provides the following features:

  • Monitors and informs the user of the health of each RBC.
  • Monitors and shows on the UPS Display Interface screen, the date for the end of useful life for each RBC.
  • The UPS emits an alarm and shows a message on the UPS Display Interface screen to indicate the estimated battery end of life. On the UPS Display Interface screen the user can set the number of days before the alarm is heard and the message appears on the UPS Display Interface screen.
  • Automatically detects the addition or removal of XLBPs and RBCs.
  • Monitors the internal temperature of each XLBP and automatically adjusts the battery charging.

Maintenance

  • RBC maintenance: The APC RBC uses sealed lead acid battery cells and does not require maintenance.
  • Runtime Test (Calibration): This should be performed anytime the steady state load is changed significantly, for example a new server is added to or removed from the UPS load.
  • Battery health monitoring: The battery energy output and voltage are monitored to assess the health of the installed batteries when the UPS is operating on battery.
    Battery health monitoring is done during a UPS Self Test, a Runtime Calibration Test, and when the UPS is operating on battery power.
    The UPS can be configured to perform periodic, automatic Self Tests.

End of useful life

  • Near end of life notification: A warning message will appear on the UPS display interface screen when each RBC is approaching the end of its useful life. For configuration details refer to Replacement Notification Time and Replacement Battery Alarm Time.
    The estimated replacement date for each RBC is available through the UI.

  • Needs replacement notification: The UPS display interface screen shows when RBC replacement is required. The RBC must be replaced as soon as possible.
    When an RBC requires replacement, the UPS display interface may recommend that additional RBCs be replaced if they will soon reach the end of their useful life.

CAUTION: Continued operation after end of useful life notification may cause damage to the batteries.

  • Recycling: Remove the RBC from the XLBP. Recycle the RBC. Do not disassemble an RBC.

Replace the RBCs in a UPS
An RBC should only be disconnected or removed from the UPS temporarily as part of the battery replacement procedure.

  • Disconnect all connected battery modules in the UPS. Slide the RBCs out of the UPS.

  • Slide the new RBCs into the UPS and connect the battery modules to the UPS.

  • Securely connect each battery module. Press the battery connector into the UPS until it is firmly connected.
    A battery that is not fully connected will cause erratic UPS operation, abnormal error messages and connected equipment may not receive battery power during power outages.

  • After installing the RBC, the UPS display interface may prompt the user to verify the status of the replaced battery modules. If the battery module is new, respond YES. If the battery module is not new, respond NO.

Recommended actions after installing new RBCs

  • Verify that the UPS is connected to input power and the output power is turned on. Refer to the Operation section in this manual for instructions.

  • Verify that the UPS load is greater than 400 watts. This will appear on the UPS display interface screen.

  • Perform a UPS Self Test.

  • Verify on the UPS display interface that the installation dates for the replaced RBCs are set to the current date.
    The installation dates can be changed manually on the UPS display interface.
    If all RBCs have been replaced at the same time, all installation dates can be changed simultaneously.
    For configuration details refer to Battery Install Date on page 19 of this manual.

  • Allow the system to charge for 24 hours to ensure full runtime capability.

XLBP installation and replacement
Refer to the External Battery Pack Installation Guide for installation and replacement instructions.

Troubleshooting

Use the table below to solve minor installation and operation problems.
Refer to the APC web site, www.apc.com for assistance with complex UPS problems.
The UPS features firmware that can be upgraded.
Go to the APC web site, www.apc.com/Support, or contact your local Customer Care Center for more information.

Problem and Possible Cause Solution

UPS will not turn on or there is no output
The UPS is not connected to mains power.| Be sure the power cable is securely connected to the UPS and to the mains power supply.
The UPS display interface screen shows very low or no mains power.| Check the mains power supply to verify acceptable power quality.
There is an internal UPS alert or warning.| The UPS Display Interface screen will show a message to identify the alert or warning and corrective action.
UPS emits an audible alarm
Normal UPS operation when running on battery power.| The UPS is operating on battery power.
Refer to the status of the UPS as shown on the UPS Display Interface screen.
Press any key to mute all alarms.
The UPS emits an audible alarm and has a red or amber back light on the UPS Display Interface screen.| An Alarm or Warning condition exists.
Refer to the display interface screen for information.
UPS does not provide expected backup time
The UPS batteries are weak due to a recent power outage or they are near the end of service life.| Charge the batteries. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the batteries are near the end of service life, consider replacing the batteries even if the Replace Battery message is not displayed.
The UPS is experiencing an overload condition.| The connected equipment exceeds the specified maximum load. Refer to the APC web site, www.apc.com for product specifications.
The UPS will emit a sustained audible alarm until the overload condition is corrected.
Disconnect nonessential equipment from the UPS to correct the overload condition.
Problem and Possible Cause| Solution
---|---
UPS operates on battery power while connected to mains power
The input circuit breaker has tripped.| Reduce the load on the UPS. Disconnect nonessential equipment and reset the circuit breaker. Check the circuit breaker rating for the connected equipment.
There is very high, very low, or distorted input line voltage.| Navigate to the UPS Display Interface screen that shows input voltage. Verify that the input voltage is within specified operating limits.
If no input voltage is indicated on the UPS Display Interface screen, contact Customer Support through the APC web site, www.apc.com.
The UPS Display Interface screen shows the message Waiting for Minimum Runtime.| The UPS has been configured to operate for a specified period of runtime. The setting can be changed through the Config/UPS menus.
UPS Display Interface Status screen shows Overload and the UPS emits a sustained audible alarm
The UPS is experiencing an overload condition.| The connected equipment exceeds the maximum load rating for the UPS.
The UPS will emit a sustained audible alarm until the overload condition is corrected.
Disconnect nonessential equipment from the UPS to correct the overload condition.
UPS Display Interface Status screen shows UPS is operating in Bypass mode
The UPS received a command to operate in Bypass mode| No action is required.
The UPS has automatically switched to Bypass mode due to an internal UPS alert or warning.| The UPS Display Interface screen will show a message to identify the alert or warning and corrective action.
UPS Display Interface is red or amber and shows an alert or warning message The UPS emits a sustained audible alarm
The UPS has detected a problem during normal operation.| Follow the instructions on the UPS Display Interface screen. Press any key to mute all alarms.
The UPS Display Interface screen shows the message Disconnected Battery.| Be sure the battery cables are securely connected.
Perform a UPS Self Test to be sure the UPS detects all connected batteries.
To perform a UPS Self Test use the UPS Display Interface menu option Test and Diagnostics.
The UPS Display Interface screen shows the message Replace Battery.| Allow the battery to recharge for 24 hours.
To perform a Runtime test use the UPS Display Interface menu option Test and Diagnostics.
If the problem persists, replace all of the batteries.
Problem and Possible Cause| Solution
---|---
The UPS display turns red or amber, displays an alert message, and emits a sustained audible alarm Red illumination indicates a UPS alarm that requires immediate attention

Amber illumination indicates a UPS alarm that requires attention

There is an internal UPS alert or warning.

| Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.
The UPS is experiencing an overload condition.

| Reduce the load on the UPS. Disconnect nonessential equipment.
The Replace Battery alert is displayed
The battery has a weak charge.| Allow the battery to recharge for at least four hours. Then, perform a
UPS Self Test. If the problem persists after recharging, replace the battery.
The replacement battery is not properly connected.| Be sure the battery cable is securely connected.
UPS reports; Battery Sys Error 0800 or Needs Firmware Update
UPS reports; Battery Sys Error 0800 or Needs Firmware Update| The UPS system firmware must be updated to correct this problem.
** To update the UPS system firmware go to [www.apc.com/support.](http://www.apc.com/support) Select Search the Knowledge Base and search for FA164737**.
Follow the instructions to upgrade the firmware.

Transport

  1. Shut down and disconnect all connected equipment.
  2. Disconnect the unit from mains power.
  3. Disconnect all internal and external batteries (if applicable).
  4. Follow the shipping instructions outlined in the Service section of this manual.

Service

If the unit requires service, do not return it to the dealer. Follow these steps:

  1. Review the Troubleshooting section of the manual to eliminate common problems.

  2. If the problem persists, contact APC Customer Support through the APC web site, www.apc.com.
    a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
    b. Call APC Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
    c. If the unit is under warranty, the repairs are free.
    d. Service procedures and returns may vary internationally. Refer to the APC web site for country specific instructions.

  3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.

  4. Before shipping, always disconnect all battery modules in a UPS or external battery pack.

  5. Write the RMA# provided by Customer Support on the outside of the package.

  6. Return the unit by insured, prepaid carrier to the address provided by Customer Support.

Limited Factory Warranty

Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship for a period of three (3) years excluding the batteries, which are warranted for two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or part thereof does not extend the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation, testing, operation or use of the product contrary to SEIT recommendations of specifications. Further, SEIT shall not be liable for defects resulting from:

  1. unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed.

EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF  SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT OR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the APC web site: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.

APC™ by Schneider Electric Worldwide Customer Support
Customer support for this or any other APC™ by Schneider Electric product is available at no charge in any of the following ways:

  • Visit the APC web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests.
    www.apc.com (Corporate Headquarters)
    Connect to localized APC web site for specific countries, each of which provides customer support information.
    www.apc.com/support/
    Global support searching APC by Schneider Electric Knowledge Base and using e-support.

  • Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail.
    – Local, country specific centers: go to www.apc.com/support/contact for contact information.
    – For information on how to obtain local customer support, contact the APC by Schneider Electric representative or other distributor from whom you purchased your APC by Schneider Electric product.

© 2015 APC by Schneider Electric. APC, the APC logo, PowerChute, and Smart-UPS are owned by
Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their
respective owners.

06/2015
EN 990-4506C

Documents / Resources

| Schneider Electric SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible Power Supply [pdf] Instruction Manual
SRT8KRMXLT-IEC, SRT8KXLI, SRT8KRMXLI, SRT8KXLT, SRT8KRMXLT, SRT10KXLI, SRT10KRMXLI, SRT10KXLT, SRT10KRMXLT, SRT10KRMXLT APC Smart UPS On Line SRT Uninterruptible Power Supply, SRT10KRMXLT, APC Smart UPS On Line SRT Uninterruptible Power Supply, Line SRT Uninterruptible Power Supply, Uninterruptible Power, Power SupplySupply
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals