Trudian 26 Wiegand Access Control Reader User Manual
- July 16, 2024
- Trudian
Table of Contents
Trudian 26 Wiegand Access Control Reader
Product Information
Specifications:
- Working voltage: DC12V
- Swipe distance: 0~4CM
- Working current: [insert value]
- Card reading type: IC card
- Communication mode: Wegen 26 / Wegen 34
- Issuing mode: management platform card issuing
- Working temperature: -20°C to 70°C
- Card capacity: 1000
- Relative humidity: 10% to 93%
- Open mode: swipe card, APP, remote, password (optional)
- Size: 86 86 8MM
- Installation method:
- Control box: hanging installation
- Reading head: 86 box embedded installation. Requires a depth of 50MM inside the style 86 box.
Product Usage Instructions
Wiegand Reader Installation Diagram:
Connect the signal line in the back of the read head device as shown in the
figure below.
Install the reading head device into the 86 box, ensuring it is embedded with
a depth of 50MM inside the style 86 box. Lock the screws to fix.
Snap together the read head panel and body, aligning the screw holes and
securing with anti-theft screws.
Wiring Instruction:
Operating mode | Wire color |
---|---|
DC12V | Red Line |
GND | Blace Line |
D0 | Green Line |
D1 | White Line |
WG34 LED/BZ | Yellow Line Blue Line |
Frequently Asked Questions
-
Q: What is the card capacity of the Wiegand Access Control Reader?
A: The card capacity is 1000. -
Q: What are the communication modes supported by the device?
A: The device supports Wegen 26 and Wegen 34 communication modes.
Product Overview
Parameter:
Working voltage | **** DC12V±10% |
---|---|
Swipe distance | 0~4CM。 |
Working current | **** 60mA±20mA |
Card reading type | **** IC card |
Communication mode | **** Wegen 26 / Wegen 34 |
Issuing mode | management platform card issuing |
Working temperature | **** -20℃~-70℃ |
Card capacity | 1000 |
Relative humidity | **** 10%~93% |
Open mode | swipe card, APP, remote, password (optional) |
Size | 86 86 8MM |
**** Installation method | Control box: hanging installation reading head : 86 |
box embedded installation.86 box requires a depth of 50MM inside
Wiegand Reader Installation diagram
- Connect the signal line in the back of the read head device as shown in the figure below.
- Install the reading head device into the 86 box, (note that you need to use the embedded wall inside the depth of 50MM style 86 box), lock the screws to fix, as shown in the figure below.
- Read the head panel and read the head body snap together, first from the upper snap down and then press the lower and bottom screw hole alignment; finally in the bottom of the anti-theft screw hole screwed on the countersunk head machine wire within the plum security screws fixed,as shown in the figure below.
Wiring instruction
Operating mode selection
Wire color | Function Description |
---|---|
Red Line | DC12V |
Blace Line | GND |
Green Line | D0 |
White Line | D1 |
Yellow Line | WG34 |
Blue Line | LED/BZ |
Notes
- Before powering up, you must confirm the voltage of the power supply and the positive and negative terminals of the power supply.
- When using external power supply, it is recommended to share the power ground with the controller power supply.
- Read the head to the control box wire, it is recommended to use 8-core shielded multi-strand twisted pair network cable.Three of the cores standby, if you do not need to read the head sound and LED light feedback legal card, may not be connected to LED/BZ line, Wegen data line D0 and D1 is recommended for each other better twisted pair, line cross-sectional area recommended 0.22 square millimeters or more, it is recommended that the wiring length does not exceed 100 meters, shielded wire connected to the control box motherboard GND, thickened or double stranded together a power supply to the reading head, help to enhance the performance of the reading head. .(You can also use other multi-core shielded Category 5 wire)