BITMAIN PW12V1 ANTPDU Antminer Power Cable Instruction Manual
- June 12, 2024
- BITMAIN
Table of Contents
BITMAIN PW12V1 ANTPDU Antminer Power Cable Instruction Manual
Product specification:
Product information | Name | ANTPDU |
---|---|---|
Model | PW12V1 | |
Input parameter | Input voltage | 346~480VAC,3P+N+PE |
Frequency | 50/60Hz | |
Input current | 3Phase 100A | |
Output parameters | Output rating | 83kW |
Output voltage | 3Phase 346~480VAC | |
Output voltage | 200~277VAC Single phase | |
Output bits | 12 Port 6pin+1Port 4pin | |
Protect Grade | IP20 | |
Working environment | Workingtemperature | -20~40℃ |
Working humidity | 5%~90%RH( Non-condensing) | |
Altitude | ≤2000m | |
Store environment | Storagetemperature | -40~70℃ |
Storage humidity | 5%~95%RH( Non-condensing) |
Certification
Overview
PW12V1 is a new generation of supercomputer power distribution unit. The product is equipped with 12 output ports, which can realize three-phase or single-phase voltage and current output of each output socket according to the actual needs of customers. Equipped with 125A three-phase hydraulic magnetic circuit breaker, the product can achieve overall overload protection, short circuit protection, the product provides each phase power LED status indication and three-phase load unbalance LED status indication. The product can adapt to the more complex working environment, through CB, cTUVus, CE-LVD and other safety certification.
Product installation
Preparation before installation
This power supply intelligent distribution unit PDU can only be installed and maintained by qualified professionals, and the installation location is a place that cannot be directly touched by human hands. Before installation, non-electric installation must be confirmed. The intactness of the entire PDU must be also checked. If any damage or damage to the appearance of the output terminals exists hence violating the basic requirements for product installation, please replace immediately or contact the manufacturer for replacement.
Start installation.
Install according to the electrical wiring diagram and PDU installation
requirements. Use cables that comply with the installation ground regulations
for connection. The total lead length should not exceed 3m, too long will
increase the impedance. The input fixed wire buckle specification is PG36, and
the input wire outer diameter should not exceed 32mm. L1, L2, L3, N
recommended 3AWG (or 25mm²) cable, crimp terminal 25-6 OT terminal. PE
recommended 4AWG (or 16mm²) yellow-green cable, crimp terminal 25-8 OT
terminal.
Inspection after switch on.
When the PDU output port is connected to all loads and the PDU circuit breaker
is closed, the three-phase current imbalance detection function is checked and
the LED lights up according to the actual detected current, and the
corresponding LED lights up when the N line current reaches the set value.
That is:
10A corresponds to the first LED light,
30A corresponds to two LEDs,
55A for three LEDs,
80A corresponds to four LEDs.
Note: LED light is only an alarm display, even if the light will not
affect the operation of the equipment, only to remind customers that each
phase load balance, three-phase imbalance will correspondingly increase the
overall loss, the need to adjust according to the current display is to try to
access the same number of miners in each group.
Outline Dimension
Wiring Schematic
Installation Schematic
Caution
PDU Installation Please try to install the outlets centered on the shelf so
that each cable is long enough to connect to the miner
According to the number and location of supercomputers to determine the number
and location of PDUs, and according to the direction of power lines to
determine the direction of PDU installation.
Tied together with the body of the PDU, tie in the snap connection of the
plug.
When the PDU needs to be mounted vertically as shown, each output plug must be
secured with a cable tie.
Three-phase unbalance alarm light schematic
Caution
When the red light is on, the user should pay attention to the current
imbalance display, need to check whether the server is load balanced, the
product should be used to test the load current imbalance light situation.