BEGA 84956K3 Compact Floodlight Instruction Manual
- June 10, 2024
- BEGA
Table of Contents
BEGA 84956K3 Compact Floodlight Instruction Manual
Technical amendments reserved
Instructions for use
Application
Compact floodlight with mounting box for permanent installations on a wall, under a ceiling or on a pillar.
Product description
Luminary made of aluminium alloy, aluminium and stainless steel BEGA Uninsured® coating technology Colour graphite or silver
Clear safety glass
Reflector surface made of pure aluminium Rotation range of floodlight 350°
Swivel range -20°/+90°
Mounting box with 2 fixing holes ø 6mm · 85mm spacing 2 cable entries for
through-wiring of mains supply cable ø 7-10.5mm, max. 5G1.5@
Connecting terminal 2.5@ with plug connection
Earth conductor connection BEGA Ultimate Driver®
Complies with flicker requirements in accordance with IEEE 1789,
DIN IEC/TR 63158, DIN IEC/TR 61547-1
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-264 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables BEGA Thermal
Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminary
Safety class I
Protection class IP 65
Dust-tight and protection against water jets Impact strength IK09
Protection against mechanical impacts < 10 joule
Safety mark
Conformity mark
Wind catching area: 0.058 m²
Weight : 5.0 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminary are subject to national safety
regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminary, the person responsible
for these modifications shall be considered the manufacturer.
Over voltage protection
The electronic components installed in the luminary are protected against over
voltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend
separate over voltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage; 71.1 W
Luminary connected wattage : 76.1 W
Rated temperature; ta=25 °C
Ambient temperature: ta max=40 °C
84 956K3
Module designation: LED-1244/930
Colour temperature: 3000 K
Colour rendering index: CRI >90
Module luminous flux : 10550 lm
Luminary luminous flux : 7837 lm
Luminary luminous efficiency: 103 lm/W
84 956K4
Module designation: LED-1244/940
Colour temperature: 4000 K
Colour rendering index: CRI >90
Module luminous flux: 10710 lm
Luminary luminous flux : 7956 lm
Luminary luminous efficiency: 104,5 lm/W
Lighting technology
Wide beam light distribution
Half beam angle 27°
For special lighting applications, an optical filter can be used to change the
symmetrical light cone into a flat beam light distribution.
Installation
LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or revamping.
Undo hexagon socket head screws (wrench size 3 mm) at the mounting box and
remove mounting plate.
Pass the power connecting cable through the cable entry in the mounting plate.
Note position of application of the mounting plate “arrow down”.
Fix the mounting plate with enclosed or any other suitable fixing material onto the mounting surface.
Be sure to use the gasket rings supplied.
Make earth conductor connection and electrical connection to the connecting terminal (plug connection).
For digital control please use the 2-pole plug connector DA, DA.
In case this connector is not used the luminaire will be operated at full light output.
Push plug into coupler as far as it will go.
Make sure that gasket is positioned correctly.
Place floodlight unit onto the mounting plate as displayed in the sketch,
align and screw together firmly.
Adjustment of beam direction:
Undo joint screw (hexagon socket head wrench size 5 mm) and set the desired
beam direction.
Tighten the joint screw.
Torque = 7Nm.
Cleaning · Maintenance
Clean luminary regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.
Maintenance
The connecting cable between mounting box and floodlight has to be inspected regarding obvious damages and has to be replaced by a qualified electrician only
Replacing the LED module
The designation of the LED module is noted on a separate label in the luminary
or on the underside of the specific LED module.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The replacement can be carried out by
a qualified person using standard tools.
Disconnect the system from the power supply.
Open the floodlight:
Loosen the back locking pin (hexagon socket wrench size 2mm) in the trim ring.
Remove the trim ring along with the safety glass and reflector by twisting it
anti-clockwise.
Replace LED module.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Place the trim ring with glass and reflector on the floodlight housing so that
the notches in the trim ring and luminaire housing sit on top of each other.
Twist on the trim ring clockwise as far as the stop. Screw in the locking pin.
Accessories
71 292 Optical filter flat beam
71282 Shield
71 287 Cylindrical shield
For the accessories a separate instructions for use can be provided upon request.
Spares
Trim ring graphite with glass: 25 000 236
Trim ring silver with glass: 25 000 237
LED power supply unit : DEV-0356/1400i
LED module 3000 K : LED-1244/930
LED module 4000 K : LED-1244/940
Reflector: 75 005 020
Gasket mounting box : 83 001 838
Gasket housing: 83 002 142
Gasket trim ring : 83 002 225
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>