GMLighting ELECTRONIC LED DRIVER Installation Guide
- June 7, 2024
- GMLighting
Table of Contents
GMLighting ELECTRONIC LED DRIVER Installation Guide
GENERAL
This LED driver is to be installed Indoor in accordance with Article 450 of the National Electric code (N.E.C.) . The LED driver must be installed in a well-ventilated area free from explosive gases and vapors. Proper operation requires the free flow of air. Only a qualified electrician should install this hardwired LED driver.
PRECAUTIONS BEFORE INSTALLING
Check the label and ensure the LED driver has the proper input voltage, output voltage and wattage for the job. Check the wire color to ensure they match the wiring diagram on this instruction sheet.
MOUNTING
Select a suitable location capable of supporting the weight of the LED driver.
INPUT CONNECTIONS/GROUNDING
Remove the wiring compartment knockouts and install strain reliefs.
With power turned off, route the input wires through a strain relief.
Plug Neutral, Live and grounding wires into the each terminal of white, black
and green wires from LED driver respectively.
The LED driver MUST be grounded in accordance with the N.E.C.
OUTPUT CONNECTIONS
Bring the lamp wires through the open knockout.
Single-channel output models:
Plug the LED positve (+) wire into terminal of red wire from LED driver.
Plug the LED negatve (–) wire into terminal of blue wire from LED driver.
Multi-channel output models:
Refer to their unit label and specification for each output connection.Please
note interconnection of outputs are not permitted.
QUICK SPECS
Input Voltage|
See Product Label
---|---
Output Voltage
Maximum Load
Operating Temp| -40° ~ 140°F (-40° ~ 60°C)
Environment| Dry and Damp Location / Indoor
INPUT VOLTAGE NOTE!
The input voltage: 120VAC to 277VAC
ENSURE to power the driver with the correct voltage!
INSTALLATION
TURNING OFF POWER
WARNING: Electric Shock Hazard. May result in serious injury or death.
Turn power OFF at circuit breaker prior to installation.
INSTALL COMPONENTS
-
LED Driver
-
Fixture
REMOVE WIRING COVER. WIRE DRIVER.
Pop off cover to access wiring compartment.
Remove knockouts with hammer and punch.
Attach load and control. Only use copper wiring. Refer to ‘System Diagrams’, and installation guides.
TURN POWER ON AT CIRCUIT BREAKER
Install Additional Components, Verify Connections and turn main power ON at breaker.
SYSTEM WORKING IMPROPERLY?
Turn power OFF at circuit breaker and verify all connections. Review WIRING and TROUBLESHOOTING
WIRING DIAGRAMS
The following diagrams are provided as example system designs. Install in accordance with national and local electrical code regulations.
-
SINGLE CHANNEL DIAGRAM
-
TWO-CHANNEL DIAGRAM
-
THREE-CHANNEL DIAGRAM
VOLTAGE DROP CHART
This chart indicates dc voltage at the beginning of your LED Linear Lighting Run.
Voltage Drop Chart for 24VDC
Wire Size
|
Distance
|
Load current in amp (per run)
---|---|---
1.25AMP
| 2.5AMP| 4.0AMP| 4.16AMP|
5.0AMP
18AWG
|
10ft
| 23.84| 2368| 23.49| 23.47| 23.36
25ft| 23.60| 23.20| 22.72| 22.67|
22.40
50ft
| 23.20| 22.40| 23.49| 23.47| 23.36
100ft| 22.40| 20.80| 18.88| 18.67|
17.60
200f
| 20.80| 17.60| 13.76| 13.35| 11.20
14AWG| 10ft| 23.94| 23.87| 23.80| 23.79|
23.75
25ft
| 23.84| 23.68| 23.49| 23.47| 23.37
50ft| 23.68| 23.37| 22.99| 22.95|
22.74
100ft
| 23.37| 22.74| 21.98| 21.90| 21.47
200f| 22.74| 21.47| 19.96| 19.80|
18.95
12AWG
| 10ft|
23.96
|
23.92
|
23.87
|
23.87
| 23.84
25ft
|
23.90
| 23.80| 23.68| 23.67| 23.60
50ft
| 23.80| 23.60| 23.36| 23.34| 23.21
100ft| 23.60| 23.21| 22.73| 22.68|
22.41
200f| 23.21| 22.41| 21.46| 21.36|
20.82
10AWG
|
10ft
|
23.98
| 23.95| 23.92| 23.92| 23.90
25ft
| 23.94| 23.88| 23.80| 23.79|
23.75
50ft
| 23.88| 23.75| 23.60| 23.58| 23.50
100ft| 23.75| 23.50| 23.20| 23.17|
23.00
200f| 23.50| 23.00| 22.40| 22.34|
22.00
Note: The results are based on an estimation under normal conditions.
TROUBLESHOOTING
Prior to troubleshooting, ensure all items are a compatible system and main power is turned ON.
Fixture does not illuminate|
- See ‘Wiring Diagrams’ and installation guides of all components.
- Ensure the system is wired correctly and polarities are correct.
- Ensure the driver and fixture have the same voltage specifications.
---|---
Fixture is flashing or flickering|
- Ensure all connections are properly secured.
- Ensure driver is not overloaded. An overloaded driver will cause the internal auto-reset to trip repeatedly.
- Ensure each output channel connected properly. No interconnection for outputs
Installation Trips Main Breaker|
- Check wiring for short circuit. If breaker continues to trip there may be a short in the driver. Call customer support for a replacement driver.
- Check AFCI for faults.
- Check for neutral or ground faults.