LUTRON LQSE-4A5-230-D 4-Zone Phase Adaptive DIN Power Module
Buttons and LEDs in the unit are used for programming and troubleshooting.
If wiring is exposed when accessing buttons and LEDs, the unit must be
accessed by a certified electrician, following local codes.
Note: For additional information on unit operation and ratings,
Mounting
- Mount in a Lutron DIN panel (see 369788) or in an IP20 (minimum) enclosure with an integrated DIN rail (please refer to Lutron P/N 048466 at www.lutron.com).
- Mount with arrow pointing up to ensure adequate cooling.
- Electronic components make audible noise, mount where acceptable.
- Unit is 12 DIN modules (216 mm [8.5 in]) wide.
- Mount to DIN rail by pressing unit onto rail with clips pressed into remove from rail, pull clips out using a screwdriver.
Line Voltage Wiring
- Turn off power and wire line voltage to the unit as shown. DO NOT WIRE LIVE. Terminals will accept 2.5 mm² to 4.0 mm² (14 AWG to 10 AWG) wire.
- Apply power, “u” LED will light if unit is wired correctly.
Verify Wiring to the Load
Follow the steps below to verify there are no faults in the load or wiring.
- Turn off power and wire line voltage to the unit as shown. DO NOT WIRE LIVE.
- Wire loads directly to Line / Hot to bypass the unit and protect it from wiring faults. Note : If using a Lutron panel, use the bypass jumper included with the panel.
- Apply power and ensure that the desired loads power on without any faults.
Wire the Load to the Module
| | | | |
---|---|---|---|---|---
Load Type| | | | Zone 1| Zone 2, 3 and 4 (per zone)
LED 1| | | | 1.7 A (400 W)| 1.0 A (250 W)
| | | | |
Incandescent / Halogen, ELV| | | | 1 200 W| 800 W
| | | | |
| | | | |
Neon / Cold Cathode, MLV| | | | 800 VA
(600 W)
| 500 VA
(375 W)
- Ratings listed refer to the LED driver input current/wattage. Refer to Lutron.com/ledtool for compatibility testing results. Using LED fixtures that are not tested can result in the fixtures not turning-on or poor dimming quality. LED dimming performance can vary from fixture to fixture and cannot be guaranteed.
- Note : Derating may be required depending on panel installation details. For derating information, refer to Lutron product specification (3691155 for LQSE-4A5-230-D or 3691158 for QSNE-4A5-230-D), panel specification (369788) or DIN panel App Note #466 (048466) at www.lutron.com.
- Turn off power and wire line voltage to the unit as shown. DO NOT WIRE LIVE.
- Wire loads as shown. Terminals will accept 2.5 mm² to 4.0 mm² (14 AWG to 10 AWG) wire.
- Apply power.
- Note : Operation of a low-voltage circuit with lamps inoperative or removed may result in transformer overheating and premature failure. Lutron strongly recommends the following: a. Do not operate low-voltage circuits without operative lamps in place.
- Replace burned-out lamps as quickly as possible.
- Use transformers that incorporate thermal protection or fused transformer primary windings to prevent transformer failure due to overcurrent.
QS Link (IEC PELV)
- Turn off power while servicing unit.
- Wire QS Link to the unit as shown, note terminals 3 and 4 are twisted, screened pair. Recommended Lutron cable: QS-CBL-LSZH.
- Link may be daisy chained or t-tapped, length not to exceed 2 000 ft (610 m).
- Do not connect to terminal 2.
Manual Override Contact Closure Input (IEC PELV)
- If no external override control is required, leave a pre-installed jumper in CCI terminals.
- Turn off power while servicing the unit. Wire CCI as shown using 0.5 mm² to 4.0 mm² (20 AWG to 10 AWG) wire.
- A single-pole switch (provided by others) must be wired in place of the jumper.
- If opened, the unit will go to manual override light levels and not respond to inputs from other devices
- .When closed or jumpered, the unit will return to the settings or levels they were at prior to entering manual override.
LED Diagnostic Indicators
LED | Behavior | Description |
---|
Power
u
| Continuous on| Normal operation
Off| General system failure / No power; verify breaker is on
Rapid flash: 10 blinks/ sec| Unit failure: contact Lutron
Hi Temp Tc >
70 °C
| Off| Normal operation
1 second on, 7 seconds off| Unit is too hot, loads scaled to 25% power
Continuous on| Unit is too hot, loads turned off
Flashing: 1 blink / sec
| Unit was overheated and has now cooled to acceptable temperature. To clear error, press the “Input”, “Prog”, “ ▲ ” , and “ ▼ ” buttons simultaneously.
Prog
| Off| Device in Normal Mode
Flashing: 1 blink / sec| Device in Program Mode
Zone 1-4
| Off| Normal Operation: zone off
Continuous on| Normal Operation: zone on
1 blink, pause
| Zone selected for manual control; will timeout after 10 seconds
Output shorted or overloaded: verify wiring
2 blink, pause| Overvoltage: verify load type
3 blink, pause| Shorted component: verify wiring; contact Lutron
4 blink, pause| Over temperature: zone may be overloaded, all loads scaled to
25%
5 blink pause| Over temperature: zone may be overloaded, all loads turned off
Rapid flash: 10 blinks/ sec| Multiple errors: contact Lutron
CCI
| Continuous on| Normal operation
Rapid flash: 10 blinks/ sec| Manual override mode / Contact open / Jumper
missing
Verify Lights – On / Off
- “Zn” buttons: Press “Zn” button to select zone to control.
- “ ” and “▼” buttons: Turn loads on and off. Note : Unit will only turn on and off until load type is programmed
Verify Lights – Dimming (Optional)
- Press and hold “Prog” and “Input” button for 3 seconds.
- Press a “Zn” button to select a zone (will timeout after 10 seconds).
- Press “Opt” button repeatedly until Opt 2 is selected.
- Use the “ ” and “▼” buttons to select desired load type.
Load Types
| H: Auto (dim) – Phase detection
---|---
M: MLV (dim) – Leading-edge/forward-phase
L: ELV (dim) – Trailing-edge/reverse-phase
Note : All load type settings will be overwritten by
- system press and hold “Prog” and “Input” button for 3 seconds to exit setup.
Programming
- For LQSE-4A5-230-D programming: Use the HomeWorks Designer software.
- For QSNE-4A5-230-D programming: Standalone applications please refer to P/N 040384 (for iPod programming) at www.lutron.com; for Athena systems use Lutron Designer 20.4 or greater.
FAQs (Frequently Asked Questions)
- Can I use non-dim loads with this product? No, only dimmable loads may be used. Use a GRX-TVI if non-dim control is required.
- Can I use LED loads with this product? Yes, refer to www.lutron.com/ledtool for compatibility with dimmable LED light sources.
- Can I use multiple load types on one zone? No, only one load type may be used per zone.
- Can I control receptacles with this product? No, output must not be used to control receptacles.
- How do I know if the unit is dimming with forward-phase or reverse-phase dimming? Press the “Opt” button and look at the “Zone” LEDs: Solid on = reverse-phase OR 1 blink / second = forward-phase
- How do I know if the QS link is working properly? Press the “Opt” button. If the power “u” LED flutters periodically, the QS link is operating normally. If the “u” LED is flashing, there is a communication error or there are no other QS devices on the link.