BANNER R130C-8P22-KQ 8 Port 2 Channel PNP IO-Link Hub Instruction Manual

June 7, 2024
BANNER

BANNER R130C-8P22-KQ 8 Port 2 Channel PNP IO-Link Hub Instruction Manual

Product Information

Specifications

  • Model: R130C-8P22-KQ
  • Type:  Function Converter
  • Ports:  8 ports
  • IO-Link System
  • Inputs/Outputs:  2 per port
  • Control:  IO-Link
  • Connector:  Integral 4-pin M12 quick-disconnect connectors

Product Usage Instructions

  • Overview
    The R130C-8P22-KQ hub connects two discrete Input/Output channels to each of the eight unique ports, providing access to monitoring and configuring those ports with an IO-Link master. Host mirroring is available where a selected port input/output discrete signal can be routed to Pin 2 (male) on the PLC/Host connection.

  • Configuration
    Refer to the logic flow diagram in Figure 1 for each of the eight ports. Tables define the configuration for each pin.

    • Mechanical Installation
      Install the R130C to allow access for functional checks, maintenance, and service or replacement. Use fasteners of sufficient strength to prevent breakage. The mounting hole accepts M4 (#8) hardware. Avoid overtightening the mounting screw to prevent affecting performance.

Wiring
Connect according to the following pinout:

Port Female Pin Male Pin Description
1 1 11 18 V DC to 30 V DC
2 2 2 Discrete 2 (IN/OUT)
3 3 3 Banner-specific Ground
4 4 4 IO-Link

Frequently Asked Questions

  • Q: Where can I find the latest IODD files?
    A: For the latest IODD files, please refer to the Banner Engineering Corp website at: www.bannerengineering.com.

  • Q: What is the purpose of host mirroring?
    A: Host mirroring enables a selected port input/output discrete signal to be routed to Pin 2 (male) on the PLC/Host connection.

Features

  • Compact IO-Link hub that connects discrete inputs as Process Data In, and outputs a discrete value as received as Process Data Out
  • Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/OFF/Retriggerable One-shot, ON/ OFF Pulse-stretcher and Totalizer
  • Measurement Metrics: Count, Events Per Minute (EPM), and Duration
  • Discrete Mirroring: Discrete signals (In/Out) from all eight ports can be mirrored to any of the eight ports, Discrete Out, or the host white wire output
  • Discrete input/output are configured as PNP only
  • Rugged over-moulded design meets IP65, IP66, and IP67
  • Connects directly to a sensor or anywhere in line for ease of use
        • R130C IO-Link hubs are a quick, easy, and economical way to integrate non-IO-Link devices into an IO-Link system

Models

Model Function Type Control Connector
R130C-8P22-KQ Converter 8 ports, PNP, with 2 inputs/outputs per port IO-
Link Integral 4-pin M12 quick-disconnect connectors

Overview

The R130C-8P22-KQ hub connects two discrete Input/Output channels to each of the eight unique ports, providing access to monitoring and configuring those ports with an IO-Link master. Host mirroring is available where a selected port input/output discrete signal can be routed to Pin 2 (male) on the PLC/Host connection.

Configuration

  • Figure 1 details the logic flow for each of the eight ports, while the tables define the configuration for each pin.
  • For more information, see P/N 236036 R130C-8P22-KQ IO-Link Data Reference Guide and P/N 236037 R130C-8P22-KQ IODD Files.

Logic Flow

Measurements – Female Pins

Port   1-Port   8   Pin   Number: Description| IO Metric| Description
---|---|---
Pin   4     Discrete   1 __

Pin   2     Discrete   2

| Count Value| Running count of the received input pulses
Duration Value| Duration of the last input pulse in µs with 500 µs granularity

Continued from page 1

Port   1-Port   8   Pin   Number: Description| IO Metric| Description
---|---|---
| Events per Minute Value| Running count of the number of pulses received averaged over one minuteRange: 1 to 37,500
Reset Metrics| •   Do Not Reset•   Reset

Pin Configuration – Female Input

Port   1-Port   8   Pin   Number: Description| Name| Values
---|---|---
| Discrete I/O Selection| •   PNP Input•   PNP Output with Pull Down
| Discrete Delay Mode| •   Disabled•   On/Off Delay

•   On One-shot

•   Off One-shot

•   On Pulse-stretcher

•   Off Pulse-stretcher

•   Totalizer

•   Retriggerable On One-shot

•   Retriggerable Off One-shot

| Discrete Delay Timer 1| Discrete On Delay, One-shot, Pulse-Stretcher Time, or Totalizer Count
Pin   4     Discrete   1| Discrete Delay Timer 2| Discrete Off Delay or Totalizer Time
|
Pin   2     Discrete   2| Mirroring Enable| • Disabled•   Enabled
| Mirroring Port Selection| •   Port 1•   Port 2

•   Port 3

•   Port 4

•   Port 5

•   Port 6

•   Port 7

•   Port 8

| Mirroring Channel Selection| •   Pin 4 – Discrete 1•   Pin 2 – Discrete 2
| Mirroring Inversion| •   Not Inverted•   Inverted

Pin Configuration – Male Output

Pin Number: Description Name Values
Host Mirroring Enable •   Disabled•   Enabled
•   Port 1
•   Port 2
•   Port 3
Pin   2 – Discrete Host Out Host Mirroring Port Selection

Port 4•   Port 5
| | •   Port 6
| | •   Port 7
| | •   Port 8
| Host Mirroring Channel Selection| •   Pin 4 – Discrete 1•   Pin 2 – Discrete 2
| Host Mirroring Inversion| •   Not Inverted•   Inverted
---|---|---
Host Mirroring Polarity| •   PNP•   NPN
Host Mirroring Output Type| •   Open Collector•   Push/Pull

IO-Link

  • IO-Link® is a point-to-point communication link between a master device and a sensor and/or light. It can be used to automatically parameterize sensors or lights and to transmit process data. For the latest IO-Link protocol and specifications, please visit www.io-link.com.
  • For the latest IODD files, please refer to the Banner Engineering Corp website at: www.bannerengineering.com.

Mechanical Installation

  • Install the R130C to allow access for functional checks, maintenance, and service or replacement. Do not install the R130C in such a way as to allow for intentional defeat.
  • Fasteners must be of sufficient strength to guard against breakage. The use of permanent fasteners or locking hardware is recommended to prevent the loosening or displacement of the device. The mounting hole (4.5 mm) in the R130C accepts M4 (#8) hardware.
  • See the figure below to help in determining the minimum screw length.

CAUTION:
Do not overtighten the R130C’s mounting screw during installation. Overtightening can affect the performance of the R130C.

Wiring

Status Indicators

The R130C 8-Port 2-Channel PNP IO-Link Hub has two matching amber LED indicators. There is also an additional amber LED specific to the IO-Link communications and a green power indication LED.

LED Indication Status
Discrete Device Amber LEDs Off Discrete In and Out are inactive
Solid Amber Discrete In or Out is active
IO-Link Communication Amber LED Off IO-Link communications are not present
Flashing Amber (900 ms On, 100 ms Off) IO-Link communications are active
Power Indicator Green LED Off Power off
Solid Green Power on

Specifications

  • Supply Voltage
    18 V DC to 30 V DC at 400 mA maximum (exclusive of load)

  • Power Pass-Through Current
    Not to exceed 4 amps total

  • Discrete Output Load Rating
    200 mA

  • Supply Protection Circuitry
    Protected against reverse polarity and transient voltages

  • Leakage Current Immunity
    400 µA

  • Indicators

    • Green:  Power
  • Amber:  2x Discrete In/Out statuses per 8 ports

  • Connections

    • (1) Integral 4-pin M12 male quick-disconnect connector
  • Construction

    • Connector Body:  PVC translucent black
  • Vibration and Mechanical Shock

    • Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)
  • Environmental Rating
    IP65, IP66, IP67 UL Type 1

  • Operating Conditions\ Temperature:  –40 °C to +70 °C (–40 °F to +158 °F) 90% at +70 °C maximum relative humidity (non-condensing)

  • Storage Temperature:  –40 °C to +80 °C (–40 °F to +176 °F)

Required Overcurrent Protection

WARNING:
Electrical connections must be made by qualified personnel according to local and national electrical codes and regulations.

  • Overcurrent protection is required to be provided by end product application per the supplied table.
  • Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply.
  • Supply wiring leads < 24 AWG shall not be spliced.
  • For dditional product support, go to www.bannerengineering.com.
  • Supply   Wiring   (AWG)| Required   Overcurrent   P
    rotection (A)
    | Supply
    Wiring   (AWG)| Required
    Overcurrent   Protection (A)
    ---|---|---|---
    20| 5.0| 26| 1.0
    22| 3.0| 28| 0.8
    24| 1.0| 30| 0.5
    ---|---|---|---

Certifications

Product Identification

FCC STATEMENT

FCC Part 15 Class B for Unintentional Radiators
(Part 15.105(b)) This equipment has been tested and found to comply with the limits for a Class B digital device, under part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used by the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and the receiver.
  • Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

(Part 15.21) Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.

Industry Canada ICES-003(B)
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.

Dimensions

All measurements are listed in millimetres [inches] unless noted otherwise.

Accessories

Cordsets

4-Pin Threaded M12 Cordsets—Double Ended

4-Pin Threaded M12 Male to 5-Pin Threaded M12 Female Splitter Cordset

Quick-Disconnect Caps

ACC-CAP M12-10

  • 10 Caps
  • Seal and protect exposed, unterminated cascade quick-disconnect connectors

Limited Warranty

Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or improper application or installation of the Banner product.

THIS LIMITED WARRANTY IS EXCLUSIVE AND INSTEAD OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER THE COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE. This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO THE BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.

Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to:
www.bannerengineering.com.

For patent information, see www.bannerengineering.com/patents.

© Banner Engineering Corp. All rights reserved.

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals