BANNER R95C 8 Port Analog In to IO Link Hub Instruction Manual
- May 15, 2024
- BANNER
Table of Contents
R95C 8-Port Analog In to IO-Link
Hub Instruction Manual
Features
- Compact analog to IO-Link device converter that connects to an analog source and outputs the value to the IO-Link master
- Ability to represent one of the eight analog inputs as a PFM output
- Rugged over-molded design meets IP65, IP67, and IP68
- Connects directly to a sensor or anywhere in-line for ease of use
- R95C IO-Link hubs are a quick, easy, and economical way to integrate non-IOLink devices into an IO-Link system
Models
Overview
When an analog input value is received by the R95C-8UI-KQ hub, the numerical representational value is sent to an IO-Link Master via Process Data In (PDI).
PDI Analog Ranges
Voltage = 0 mV to 10,000 mV
Current = 4,000 µA to 20,000 µA
PFM Out
Enables a PFM representation of an analog input as an output
PFM Input Source Channel
Selects the analog input value from Port 1..8 as the PFM out-put source
Pulse Frequency Configuration
Sets the near and far frequency values
Configuration
For more information, see P/N 232874 R95C-8UI-KQ IO-Link Data Reference Guide
and P/N 232873 R95C-8UI-KQ IODD Files.
IO-Link®
IO-Link® is a point-to-point communication link between a master device and a
sensor and/or light. It can be used to automatically parameterize sensors or
lights and to transmit process data. For the latest IO-ink protocol and
specifications, please visit www.io-link.com.
For the latest IODD files, please refer to the Banner Engineering Corp website at: www.bannerengineering.com.
Mechanical Installation
Install the R95C to allow access for functional checks, maintenance, and
service or replacement. Do not install the R95C in such a way to allow for
intentional defeat.
Fasteners must be of sufficient strength to guard against breakage. The use of
permanent fasteners or locking hardware is recommended to prevent the
loosening or displacement of the device. The mounting hole (4.5 mm) in the
R95C accepts M4 (#8) hardware.
See the figure below to help in determining the minimum screw length.
CAUTION: Do not overtighten the R95C’s mounting screw during installation. Overtightening can affect the performance of the R95C.
Wiring
Port 1-Port 8 — Female | Pin | Signal Description |
---|---|---|
1 | 18 V DC to 30 V DC | |
2 | Analog In | |
3 | Ground | |
4 | Not Used | |
Male | Pin | Signal Description |
--- | --- | --- |
1 | 18 V DC to 30 V DC | |
2 | Banner-specific/PFM out | |
3 | Ground | |
4 | IO-Link |
Status Indicators
The R95C 8-Port Analog In to IO-Link Hub has matching amber LED indicators on both sides for each analog in port to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is specific to the IO-Link communication.
Power Indicator Green LED
Indication| Status
Off| Power off
Solid Green| Power on
Power Indicator Green LED
Indication| Status
Off| Power off
Solid Green| Power on
Analog In Amber LED
Indication| Status
Off| Analog current value is less than setpoint SP1 OR analog value is greater
than setpoint SP2
Solid Amber| Analog current value is between setpoint SP1 AND setpoint SP2
Default Current Values:
• SP1 = 0.004 A
• SP2 = 0.02 A| Default Voltage Values:
• SP1 = 0 V
• SP2 = 10 V
Specifications
Supply Voltage
18 V DC to 30 V DC at 400 mA maximum
Power Pass-Through Current
500 mA per port maximum
Analog Input Impedance
Current version: Approximately 250 ohms
Voltage version: Approximately 14.3K ohms
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Leakage Current Immunity
400 µA
Indicators
Green: Power
Amber: IO-Link communications
Amber: Analog In status
Connections
(8) Integral 4-pin M12 female quick-disconnect connector
(1) Integral 4-pin M12 male quick-disconnect connector
Construction
Coupling Material: Nickel-plated brass
Connector Body: PVC translucent black
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55
Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)
Certifications
****| Banner Engineering BV
Park Lane, Culliganlaan 2F bus 3
1831 Diegem, BELGIUM
---|---
| Turck Banner LTD Blenheim House
Blenheim Court
Wickford, Essex $S11 8YT
GREAT BRITAIN
Product Identification
Environmental Rating
IP65, IP67, IP68
NEMA/UL Type 1
Operating Conditions
Temperature: –40 °C to +70 °C (–40 °F to +158 °F)
90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature: –40 °C to +80 °C (–40 °F to +176 °F)
Required Overcurrent Protection
WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations.
Overcurrent protection is required to be provided by end product application
per the supplied table.
Overcurrent protection may be provided with external fusing or via Current
Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to
www.bannerengineering.com.
Supply Wiring (AWG)| Required Overcurrent Protection (A)| Supply Wiring (AWG)|
Required Overcurrent Protection (A)
---|---|---|---
20| 5.0| 26| 1.0
22| 3.0| 28| 0.8
24| 1.0| 30| 0.5
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Industry Canada ICES-003(B)
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the
following two conditions: 1) This device may not cause harmful interference;
and 2) This device must accept any interference received, including
interference that may cause undesired operation.
Dimensions
All measurements are listed in millimeters [inches], unless noted otherwise.
Accessories
Cordsets
4-Pin Threaded M12 Cordsets—Double Ended
Model| Length| Style| Dimensions| Pinout
MQDEC-401SS| 0.31 m (1 ft)| Male Straight/Female
Straight| | Female Male
1 = Brown
2 = White
3 = Blue
4 = Black
MQDEC-403SS| 0.91 m (2.99 ft)
MQDEC-406SS| 1.83 m (6 ft)
MQDEC-412SS| 3.66 m (12 ft)
MQDEC-420SS| 6.10 m (20 ft)
MQDEC-430SS| 9.14 m (30.2 ft)
MQDEC-450SS| 15.2 m (49.9 ft)
Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in
material and workmanship for one year following the date of shipment.
Banner Engineering Corp. will repair or replace, free of charge, any product
of its manufacture which, at the time it is returned to the factory, is found
to have been defective during the warranty period. This warranty does not
cover damage or liability for misuse, abuse, or the improper application or
installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER
EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING
UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of
Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING
CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS,
EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL
DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE
THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT
LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the
design of the product without assuming any obligations or liabilities relating
to any product previously manufactured by Banner Engineering Corp. Any misuse,
abuse, or improper application or installation of this product or use of the
product for personal protection applications when the product is identified as
not intended for such purposes will void the product warranty. Any
modifications to this product without prior express approval by Banner
Engineering Corp will void the product warranties. All specifications
published in this document are subject to change; Banner reserves the right to
modify product specifications or update documentation at any time.
Specifications and product information in English supersede that which is
provided in any other language. For the most recent version of any
documentation, refer to:
www.bannerengineering.com.
For patent information, see www.bannerengineering.com/patents.
November 2, 2023
© Banner Engineering Corp. All rights reserved.