ROBUS R100LEDRETE 10w SMD Led Emergency Golf Retrofit Fitting Instruction Manual

June 6, 2024
ROBUS

ROBUS R100LEDRETE 10w SMD Led Emergency Golf Retrofit Fitting

PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES. Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or use of this product, consult a competent electrician

Note: Product technical information and specification may change over time without prior notification. For the latest technical information please visit our web site www.robus.com or robusdirect.com -10°C < Ta < +35°C, 220V – 240V ~ 50/60Hz, Class I, Battery Warranty: 2 Years Luminaire is non-dimmable Light output will typically be reduced by 25% when installed in a fitting with opaque diffuser (e.g. ROBUS 2D housing).

Installation

  1.  Ensure mains supply is switched off before commencing work

  2.  Installation instructions as per existing conventional fitting

  3.  Remove existing conventional tray

  4.  Ensure that there is sufficient room in the fitting housing for the R100LEDRETE

  5.  Connect wires from un-switched supply to terminals: Brown/red to PL, Blue/ Black to N and green/yellow to earth. For fitting always on , link terminal “SL” to terminal “PL”. When controlled by switch connect switched live wire to terminal SL and permanent live to PL.
    Note: if “SL” terminal not connected, fitting works as non-maintained.

  6.  Attach LED tray to fitting base using existing mounting posts and screws. Ensure that the tray is secure

Attention : In order to protect the battery life, please disconnect the battery if the power supply shut off over 3 days.
Switch on supply: The green led should come on indicating correct battery charge status, all LEDs will come on.When supply to the switched live PL is lost, battery will operate fitting in emergency mode.
Market Surveillance: LS Code of energy efficiency Class E. R100LEDRET-LS Disconnect driver input and output connections. Remove LED plate.

Testing

The emergency lighting must be inspected and tested regularly in accordance with local codes of practice: note: for safety reasons tests should be carried out during daylight hours. The minimum recommended test schedule is as follows: After installation, allow 24 hours to ensure full battery charge and then interrupt the supply; the maximum duration time is 3 hours check that LEDs are still lighting.

  1.  Daily check that charge indicator LED is working
  2.  Monthly, interrupt mains for a short period and check LED lights
  3.  Annual 12 month check, full duration test. Interrupt mains supply, LEDs will light and should last for a minimum 3 hours operation: batteries must be replaced when they can no longer support 3 hour operation.
  4.  Complete record sheet on installation and retain in maintenance file.
  5.  Update file with ongoing test records for inspection by fire officer or other duly authorized person

Information for the Product user:

  1.  Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste (WEEE marked with crossed out wheelie bin symbol).
  2.  Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre for waste electrical equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.
  3.  This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly. It is important that it is separated from normal household waste and recycled in the WEEE chain
  4.  The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household waste, but should be disposed of according to local WEEE regulations

Installation and Maintenance Record:

ROBUS-R100LEDRETE-10w-SMD-Led-Emergency-Golf-Retrofit-
Fitting-1

Documents / Resources

| ROBUS R100LEDRETE 10w SMD Led Emergency Golf Retrofit Fitting [pdf] Instruction Manual
R100LEDRETE, 10w SMD Led Emergency Golf Retrofit Fitting
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ROBUS User Manuals

Related Manuals