LUTRON Q-POE-8 PoE Switch Instruction Manual
- June 6, 2024
- Lutron
Table of Contents
LUTRON Q-POE-8 PoE Switch Instruction
Important Notes
- For installation by a qualified electrician in accordance with all local electrical codes.
- Install the PoE switch where the terminal block / wires are not accessible to users in the space.
- The power wiring must be 0.2 mm2 to 1.0 mm2 (24 AWG to 18 AWG) and rated for at least 75 ˚C.
- This equipment is intended for indoor use only; in a 32 °F to 104 °F (0 °C to 40 °C) setting with a relative humidity less than 90%, non‑condensing.
Included Components
For each system, ensure that you have:
PoE Switch
(8) M3 x 4 mm Assembly Screws
(2) Mounting Brackets
(4) 8-32 x 0.25 in Mounting Screws
(1) 6-pin Connector Customer Assistance
For questions concerning the installation or operation of this product, call Lutron Customer Assistance. Please provide exact model number when calling.
- U.S.A. and Canada
- 1.844.LUTRON1
- Mexico 8am – 8pm ET
- +1.888.235.2910
Installation
-
WARNING — Shock Hazard. May result in serious injury or death. Turn off power at the circuit breaker before installing the unit.
-
Attach the two mounting brackets to the PoE switch using the (8) M3 x 4 mm machine screws provided. Orient the left bracket as shown using the holes in the bracket marked with an “L” and orient the right bracket as shown using the holes in the bracket marked with an “R”. Torque all screws to 5 in‑lbs (0.56 N•m).
-
Left Bracket
-
Mount the assembled PoE switch in the Lutron panel using (4) 8‑32 x 0.25 in machine screws provided. Torque to 17 in‑lbs (1.92 N•m).
- Mounting Locations for PD8‑65T‑DV, PD6‑42T‑DV and ALPD Control Panel
-
Power Wirin
-
Assemble the power cable using the red and black wires that are provided along with the 6‑pin power connector to plug into the
Q‑ POE‑8. The QSPS‑DH‑1‑75‑H is equipped with screw terminals for the wiring connections. -
Power the unit from a 24 V- power supply, Lutron model QSPS‑DH‑1‑75‑H.
-
-
Connect the communication wiring from the ethernet ports on the front panel of the switch to the PoE device.
Notes
- Use Cat5e minimum cable for all connections between hubs and a Athena Clear Connect Gateway‑Type X.
- The wiring between hubs and gateways is considered PELV / NEC® Class 2; do not run in the same conduit as line (mains) voltage wiring.
- Processors cannot be daisy‑chained. Each must be connected to the internal Ethernet switch. The second Ethernet connection is used for service or diagnostics only.
- All system Ethernet wiring must comply with IEEE 802.3 standards.
- Wiring distance for any single “wire segment” is 328 ft (100 m) max; this applies for any Ethernet connections between hubs or to a Athena Clear Connect Gateway‑Type X. Use Lutron’s Q‑POE‑PNL or unmanaged Ethernet switches for longer distances.
- For more information about connecting an Athena system to a corporate or building‑wide network, please refer to the Athena IT Guide (P/N 040453) at www.lutron.com/AthenaITguide
- Para obtener más información sobre cómo conectar un sistema Athena a una red corporativa o de un edificio, consulte la Guía de informática de Athena (N/P 040453) en www.lutron.com/AthenaITguide
| LED| Color (pattern)| Indication
---|---|---|---
PoE switch
| Power 1| Green (solid)| Power present
Power Fault| Amber| P1 or P2 power fault
Link / Act| Green (solid or flashing)| Normal operation
PoE Power| Green| PoE power injected
Limited Warranty
For limited warranty information, please visit http://www.lutron.com /en-US/Service-Support/Pages/Service/ Warranty/Warranty.aspx
Lutron, Clear Connect, and Athena are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries.
©2021 Lutron Electronics Co., Inc.