Ford FDT9200SE Diesel Generator Owner’s Manual

June 5, 2024
Ford

Ford Logo FDT9200SE Diesel Generator
Owner’s ManualFord FDT9200SE Diesel Generator

SAFETY INFORMATION
In order to ensure the safe use of the generator please follow the next safety instructions:

  1. Check the outside of the generator in order to detect any apparent trouble.
  2. Check the screws and nuts, they could loosen because of the equipment vibration.
  3. The temperature range to use this equipment is between + 5 °C and 40 °C.
  4. The use of good quality oil and diesel is a must
  5. All elements must be cleaned regularly.
  6. Storage should be in a dry place. Frost damage permanently your group. Drain your machine completely before storing it in a dry and warm place.
  7. The air filter must be checked and cleaned regularly.
  8. Make sure all filters are cleaned regularly.
  9. Exhaust fumes contain carbon monoxide. This gas is odorless and colorless and is very dangerous. NEVER USE THE EQUIPMENT IN A CLOSED OR POORLY VENTILATED AREA.
  10. The exhaust temperature is high during equipment use and remains hot even after turning off the generator. Be careful not to touch the hot exhaust and wait for the machine to cool before moving it.
  11. The repairs to the generator should be done by qualified and authorized personnel for this purpose.
  12. Do not smoke or allow flames or sparks during the operation of the generator or during filling the fuel tank. Do not store the generator near flammable material to avoid the danger of explosion.
  13. Store the generator in a well-ventilated area.
  14. Never place the generator in an inclined or vertical position to prevent fuel leakage and damage to equipment.

ATTENTION
The warranty is automatically voided if the process described to start and stop the group is not followed.
Not following the process described can damage the equipment.
ALWAYS control the level of oil and fuel as well as its maintenance before each use.

Technical Data

Model FDT9200SE (FD7200S)
Frequency Hz 50
Rated Power kva 6 / 7.5 kva
Max. Power kva 6.3 / 7.9 kva
Voltage v 230 / 400
Current A 25.2 / 11.4
Plugs 16A& 32A
Display LED6
Fuel tank capacity L 13
Running time @75% load H 7
Sound level @ 7m dBA 72
DC output V/A 12 / 8.3
Battery V/Ah 12 / 30
ENGINE D500E
Engine type Diesel
Power hp 12
Start Electric
Displacement cc 498
Oil Capacity L 1.75
ALTERNATOR AL6-T
Power Ku 6
Power Factor 1/0.8
Voltage Regulation Brush / AVR
DIMENSIONS & WEIGHT
Net Weight Kg 162
Gross Weight Kg 170
Machine size mm 920x520x720
Dimensions Package mm 960x560x760
FCL 20740’HO 48/144

COMPONENTS

General view

Ford FDT9200SE Diesel Generator - Fig

  1. Fuel filter
  2. Battery 12V 36Ah
  3. Oil filter
  4. Transport wheels
  5. Injection pump
  6. Starter lever
  7. Oil refill/Oil dipstick
  8. Oil drain
Side view

Ford FDT9200SE Diesel Generator - Fig 1

  1. Diesel tank
  2. Control panel
  3. Engine access
  4. Carrying handle
  5. Air filter
Control panel LED

Ford FDT9200SE Diesel Generator - Fig 2

1. LED6 display
2. Start key
3. Emergency stop
4. Transfer switch
5. Breaker
6. AUTO socket
7. ATS socket| 8. Pre-heater button
9. Earth terminal
10. 400V 16A socket
11. 230V 3M socket
12. 230V 16A socket
13. Overload protector
---|---

First startup

Preparation before starting up

Put oil on the motor (Fig.1) using 1 5W40 oil, 1.6Lt maximum, check the level with the dipstick without screwing it in, the level must remain at the maximum line (without exceeding the upper mark).Ford FDT9200SE Diesel
Generator - Fig 3 Fill the fuel tank with diesel (Fig 2) , with 17 liters (depending on the version).
Connect the positive (red wire) to the battery, insert it back into its housing, and pay attention not to touch the positive to the body or it could blow the fuse. Tape the positive terminal if necessary.Ford FDT9200SE Diesel
Generator - Fig 4 Be sure to remove the lateral battery caps. (Fig 3) Ford FDT9200SE Diesel Generator - Fig
5

Starting the Generator

Turn the speed lever to the “RUN” position. (Fig 4) Ford FDT9200SE Diesel
Generator - Fig 6 It is possible that the first time you need to purge air from the circuit by removing the rubber tube indicated (Fig.5) , letting flow the diesel. When no air, put them back in place, and do not touch the pressure tubes. Repeat if necessary.Ford
FDT9200SE Diesel Generator - Fig 7 Insert the key into the bowler and proceed to startup. Turn right to the “ON” position to give contact. Turn the key to the START position to start the engine (Fig 6). Once the generator is running, make it work for 3 minutes and make sure the differential is at the “OFF” position (down). Then you can connect the load and put the differential at the “ON” position.
RESPECT THE GENERATOR’S RATED POWER. IF THERE’S AN OVERLOAD THE BREAKER WILL JUMP BETWEEN 3 AND 10 SECONDS.
WHEN THE GENERATOR IS RUNNING THE DIGITAL DISPLAY LED 5 WILL SHOW YOU THE VOLTAGE, FREQUENCY, THE HOURS OF USE, AND THE APPLIED POWER.

Stopping the generator

Turn the differential to the “OFF” position (down, Fig 7 ) and disconnect the equipment connected to the control panel.
(If you miss this step, you may damage the voltage regulator AVR). Ford
FDT9200SE Diesel Generator - Fig 9 To stop the engine, turn the key ) to the “OFF” position.Ford FDT9200SE Diesel
Generator - Fig 10

Engine maintenance

First oil change after 20 hours

Ford FDT9200SE Diesel Generator - Fig 11| Ford FDT9200SE Diesel Generator - Fig 12
---|---

Place a recipient underneath to catch the oil.
Loosen the drain screw. Drain the engine oil.
Fit and tighten the drain screw again.
Replace the gasket screw at each change to avoid losses.
Fill the engine with new oil 15W40 (1.6Lt).
NEXT OIL CHANGES EVERY 100 HOURS OF OPERATION.

Oil filter

Ford FDT9200SE Diesel Generator - Fig 13

Remove and clean the oil filter on every oil change by changing the gasket to prevent leakage.
If there are impurities in the filter, it can block the oil sensor stopping the start of the generator.
REPLACE THE OIL FILTER EVERY 200 HOURS.

Air filter

Ford FDT9200SE Diesel Generator - Fig 14

Clean the air filter with compressed air at each oil change and replace it every 200 hours.
WARNING: DO NOT START THE ENGINE WITHOUT AN AIR FILTER.

Diesel filter

Ford FDT9200SE Diesel Generator - Fig 15| Ford FDT9200SE Diesel Generator - Fig 16
---|---

Replace every 100 hours (Fig 14).
The filter is located inside the fuel tank or in the fuel pipe (depending on the model).
It is above the battery to replace it and place a container, as there is no stopcock to prevent the escape of dieseL.
If the fuel used is dirtier than normal, replace it earlier than indicated.

General maintenance

Never incline the generator during transportation without emptying the oil pan.
Failure to observe this instruction may cause severe damage to the engine.
We recommend cleaning the equipment after use and before storage.
Visually check the external components.
Check the screws and nuts due to equipment vibration could loosen.

Prolonged storage

To keep the equipment in perfect condition we recommend the following steps:
– Drain the fuel tank.
– Drain the engine oil.
– Pull the starter until you feel some resistance (allowing the valves to close in order to prevent moisture and corrosion of the cylinder and the valve regulation)
-After prolonged storage, the starting process is identical to the first startup.
ATTENTION
The warranty is automatically voided if the process described to start and stop the group is not followed.
Not following the process described can damage the equipment.
ALWAYS control the level of oil and fuel as well as its maintenance before each use.

Troubleshooting

Causes Remedies
No start of the engine Insufficient fuel
Air in the fuel circuit Purge air in the fuel circuit
No spray-on injector or a little quantity Repair and adjust the injector
Speed control rod not at “RUN” position Set control rod to “RUN” position
Check the lube oil lever The level between the upper mark “H” and lower mark

“L”
Dirty on the nozzle| Clean the nozzle
No electricity in the battery| Charge or change the battery
No output of the generator| Not turn on the switch| Turn to the “CLOSE” position
Worse contact with the socket| Adjust the socket
Not reach the rated speed of the engine| According to the stipulation
Voltage too low| Not reach the rated speed of the engine| Set speed control rod to operation position.
Check AVR| Adjust the resistance clockwise
Automatic stop after a certain time of operation| (1)lack of the fuel
(2)lack of lube oil
(3)voltage too low/too high
(4)frequency too low/too high
(5)over-current| Repair according to relative alarming of the control panel

www.fordpower.cc

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals