SFA SANICONDENS Mini Pump for Boiler Condensation Condensate Instruction Manual

June 5, 2024
SFA

SFA SANICONDENS Mini Pump for Boiler Condensation Condensate

SFA-SANICONDENS-Mini-Pump-for-Boiler-Condensation-Condensate-
PRODUCT

CAUTION

SANICONDENS® Mini is a pump for lifting condensation water from an air conditioning system, a condensation boiler or from refrigeration units. Include a neutralisation device if necessary (see the manufacturerʼs instructions for your boiler). The pump starts automatically and has a high level of performance, safety and reliability provided that all the installation and maintenance instructions described in thisnotice are strictly followed. Please take particular note of the information marked by : Indication that a risk of electrical origin exists, Instructions for use only by qualified professionals. Please contact our Customer Services for any additional information.

OPERATING PRINCIPLE

SANICONDENS® Mini contains a pump. The tank of the SANICONDENS® Mini is fitted with a float which controls the operation of the motor. When the condensates enter the tank, the pump starts up.

LIST OF DOCUMENTS PROVIDED

DIMENSIONS

SFA-SANICONDENS-Mini-Pump-for-Boiler-Condensation-Condensate-
FIG-3

SANICONDENS® MINI AREA OF APPLICATION AND TECHNICAL DATA

  • Application Air conditioning systems, boilers, refrigeration units
  • Type SK17
  • Max. vertical pumping 2 m
  • Maximum flow rate (litres / hour) 144
  • Min. pH 2,5
  • Voltage 220-240 V
  • Frequency 50 Hz
  • Power rating 35 W
  • Current consumption 0,4 A
  • Electrical class I
  • Protection index IP20
  • Sound level < 45 dBA
  • Average utilisation temperature 35°
  • Maximum allowable temperature 80° S3 15% (90s ON, 510s OFF)
  • Net weight 1,3 kg
  • Dimensions 231x120x143 mm
  • Supply cable 2 m

CAUTION :
All applications other than those described in this notice are prohibited

PERFORMANCE CURVES

VERTICAL PUMPING/HORIZONTAL PUMPING:

INSTALLATION

SANICONDENS® Mini has wall fixings. The unit should be easy to access for testing and maintenance. The unit must be installed level. Adjust the installation using a spirit level before fixing the unit (see fig ). Make sure that the equipment is protected from damp while installing it.

SFA-SANICONDENS-Mini-Pump-for-Boiler-Condensation-Condensate-
FIG-6

CONNECTION AT THE COVER INLET
The unit has 4 inlets 28 mm in diameter (2 on each side – see fig. ). To connect the water to be drained off, connect the water inlet to one of the inlets and close off any unused inlets with the plugs . If necessary, use the rubber adaptator 19, 32, 40 mm (see fig. and ).

CONNECTING TO THE DISCHARGE PIPE
The SANICONDENS® Mini discharge pipe must be connected to the flexible hose ( , Ø 8/11, not supplied). This hose should be used to form the vertical section of the discharge pipe.

  • Place the flexible hose onto the non-return valve of the SANICONDENS® Mini.
  • Position the flexible hose in the most vertical position possible to avoid it kinking.
  • It is advisable to make a smooth bend to avoid the hose kinking.
  • The hose has a diameter of less than 8 mm and can be connected to a PVC hose of larger diameter by a plastic reducing connection on the horizontal section of thedischarge hose, or connected to your drain by a plastic reducing connection ( not supplied). In UK fittings such as Speedfit from John Guest are available -part numbers PEM202215W used with PEM06150W to connect to 22mm pipework

ELECTRICAL CONNECTION
The electrical installation should be carried by a qualified person.The unit should be connected to a fully earthed electrical supply. All wiring must conform to BS7671, 1992 requirements for electrical installations. The SANICONDENS® Mini requires a 220/240V single phase AC 50 Hz supply (UK specification) Do not connect SANICONDENS® Mini to a conventional plug and socket. It must be wired into a fused, unswitched, fixedwiring connector fitted with a 5 amp fuse. SANICONDENS®Mini has an Earth wire. The wires in the mains lead are colored in accordance with the following code:Brown – Live Blue – Neutral Green/Yellow – Earth Warning: Ensure the electricity is turned OFF at the main switchboard before wiring to the connector.All work on cable, pressure chamber and motor should only be carried out by a qualified Saniflo servicing agent, as special tools are required. EXAMPLE OF AN INSTALLATION OF A SANICONDENS®
Mini

STANDARDS
SANICONDENS® Mini conforms to the European directive 89/336/CEE on electrical safety

DISASSEMBLY
If a breakdown occurs, any service on the unit should be carried out by a qualified engineer. In particular the replacement of the power cable. Disconnect the electrical supply before carrying out work on the unit

TROUBLESHOOTING

INSTRUCTIONS RESERVED SOLELY FOR QUALIFIED PROFESSIONALS Disconnect the electrical supply before carrying out any work.

FAULT DETECTED PROBABLE CAUSES ACTION NEEDED
The pump does not start ****

•  The pump is not connected to the power supply

•  Power cut

•  Float blocked


•  Condensates inlet pipe blocked

| •  Plug in the unit .



•  Check the mains voltage.


•  Clean the SANICONDENS ® **Mini tank.**


•  Clean the SANICONDENS ® **Mini inlet pipe.**

The pump does not lift| •  Non-return valve blocked

•  Discharge pipe blocked

| •  Clean the valve.

•  Clean the discharge pipe.

GUARANTEE

SANICONDENS® Mini SFA is guaranteed for 2 years for parts and labour, subject to correct installation and use of the unit

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SFA User Manuals

Related Manuals