SFA 50859103 SANI CONDENS PRO Condensate Lifting Unit Instruction Manual
- June 5, 2024
- SFA
Table of Contents
- SFA 50859103 SANI CONDENS PRO Condensate Lifting Unit
- OPERATING PRINCIPLE
- OVERVIEW
- LIST OF DOCUMENTS PROVIDED
- DIMENSIONS
- SANICONDENS® Pro AREA OF APPLICATION AND TECHNICAL DATA
- PERFORMANCE CURVES
- VERTICAL PUMPING/HORIZONTAL PUMPING
- INSTALLATION
- TROUBLESHOOTING
- GUARANTEE
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SFA 50859103 SANI CONDENS PRO Condensate Lifting Unit
CAUTION
SANICONDENS® Pro is a pump for lifting condensation water from an air
conditioning system, a condensation boiler or from refrigeration units.
Include a neutralization device if necessary (see the manufacturer’s
instructions for your boiler). The pump starts automatically and has a high
level of performance, safety and reliability provided that all the
installation and maintenance instructions described in this notice are
strictly followed.
Please take particular note of the information marked by:
- An indication that risk of electrical origin exists,
- Instructions for use only by qualified professionals.
OPERATING PRINCIPLE
SANICONDENS® Pro contains a pump. The tank of the SANICONDENS® Pro is fitted with a float that controls the operation of the motor. When the condensates enter the tank, the pump starts up.
OVERVIEW
LIST OF DOCUMENTS PROVIDED
DIMENSIONS
SANICONDENS® Pro AREA OF APPLICATION AND TECHNICAL DATA
**SANICONDENS ® ****Pro AREA OF APPLICATION AND TECHNICAL DATA**
Application **Air conditioning systems, boilers,**
refrigeration units
Type CD10
Max. vertical pumping 4,5 m
Maximum flow rate (litres / hour) 342
Flow rate at 4 m 156
Min. pH 2,5
Voltage 220-240 V
Frequency 50 Hz
Power rating 60 W
Current consumption 0,52 A
Electrical class I
Protection index IP20
Sound level < 45 dBA
Average utilisation temperature 35°
Maximum allowable temperature 80°
S3 15% (90s ON, 510s OFF)
Net weight 2000 g
Tank volume 2 litre
Supply cable 2 m
Discharge hose 6 m
Alarm cable (3 core) 2 m
Wall fastening Yes
CAUTION:
All applications other than those described in this notice are prohibited.
PERFORMANCE CURVES
VERTICAL PUMPING/HORIZONTAL PUMPING
INSTALLATION
SANICONDENS® Pro has wall fixings.
The unit should be easy to access for testing and maintenance. The unit must
be installed level. Adjust the installation using a spirit level before fixing
the unit. Make sure that the equipment is protected from damp while installing
it.
CONNECTION AT THE COVER INLET
The unit has 2 inlets 28 mm in diameter (1 on each side – see fig. 7a). To connect the water to be drained off, connect the water inlet to one of the inlets. If necessary, use the rubber adaptator X 19, 32, 40 mm.
CONNECTING TO THE DISCHARGE PIPE
The SANICONDENS® Pro discharge pipe must be connec-ted to the flexible hose A (supplied: length 6 m). This hose should be used to form the vertical section of the discharge pipe.
- Place the flexible hose onto the non-return valve of the SANICONDENS® Pro (see diagram 7b).
- Position the flexible hose in the most vertical position possible to avoid it kinking.
- It is advisable to make a smooth bend to avoid the hose kinking.
- The hose has a diameter of less than 8 mm and can be connected to a PVC hose of larger diameter by a plastic reducing connection on the horizontal section of the discharge hose, or connected to your drain by a plastic reducing connection Y. In the UK fittings such as Speedfit from John Guest are available -part numbers PEM202215W used with PEM06150W to connect to 22mm pipework.
The SANICONDENS® Pro is fitted with a non-return valve to prevent re- activation.
ELECTRICAL CONNECTION
The electrical installation should be carried out by a qualified person. The unit should be connected to a fully earthed electrical supply. All wiring must conform to BS7671, 1992 requirements for electrical installations. The SANICONDENS® Pro requires a 220/240V single phase AC 50 Hz supply (UK specification). Do not connect SANICONDENS® Pro to a conventional plug and socket. It must be wired into a fused, unswitched, fixed wiring connector fitted with a 5 amp fuse. SANICONDENS® Pro has an Earth wire. The wires in the mains lead are colored in accordance with the following code: Brown – Live Blue – Neutral Green/Yellow – Earth
Warning:
Ensure the electricity is turned OFF at the main switchboard before wiring to
the connector. All work on cable, pressure chamber, and motor should only be
carried out by a qualified Saniflo servicing agent, as special tools are
required.
ALARM
SANICONDENS® Pro is fitted with a detection system that can trigger an alarm if the water level rises too high (audible or visual alarm, 1.5V to 230V), see diagram 7d:
- Brown wire: shared wire
- Black wire: normally off
- Blue wire: normally on
To fit the alarm, connect the blue and brown wires of the alarm to the respective terminals on the SANICONDENS® Pro.
OPTIONAL:
If you connect the brown and black wires to the control relays on your boiler,
it will be switched off if the water level rises too high in the unit.
ATTENTION:
The maximum current admissible for our detection system is 0.5A. To protect
the electrical components in the SANICONDENS® Pro, once the alarm has been
triggered, any water continuing to fill the tank comes out through the
overflow outlets in the cover.
BEFORE TURNING THE DEVICE ON, MAKE SURE YOU REMOVE THE PROTECTIVE LOCK PIN FROM THE REAR OF THE DEVICE
EXAMPLE OF AN INSTALLATION OF A SANICONDENS® Pro: see fig. 7f
STANDARDS
SANICONDENS® Pro conforms to the European directive 2006/95/CEE on
electrical safety.
DISASSEMBLY
If a breakdown occurs, any service on the unit should be carried out by a
qualified engineer. In particular the replacement of the power cable.
TROUBLESHOOTING
INSTRUCTIONS RESERVED SOLELY FOR QUALIFIED PROFESSIONALS
Disconnect the electrical supply before carrying out any work.
10 TROUBLESHOOTING
| INSTRUCTIONS RESERVED SOLELY FOR QUALIFIED PROFESSIONALS
| Disconnect the electrical supply before carrying out any work.
FAULT DETECTED| PROBABLE CAUSES| ACTION NEEDED
• The pump does not start|
• The pump is not connected to the power supply
• The lock pin has not been removed.
• The unit is not level.
• Power cut
• Float blocked
• Condensates inlet pipe blocked
| • Plug in the unit.
• Remove the lock pin.
• Please check the unit with a spirit level.
• Check the mains voltage.
• Clean the SANICONDENS® Pro tank.
• Clean the SANICONDENS® Pro inlet pipe.
• The pump does not lift|
• Non-return valve blocked
• Discharge pipe blocked
| • Clean the valve.
• Clean the discharge pipe.
| |
WARNING
This device is not designed for persons (including children) with limited
physical, sensory or mental abilities, or those with minimal experience and
knowledge, unless they are monitored and are given the necessary instructions
for using the device, with the help of a person responsible for their safety.
Monitor children and make sure they do not play with the device.
GUARANTEE
SANICONDENS® Pro SFA is guaranteed for 2 years for parts and labor, subject to correct installation and use of the unit.