EIP DD400 Industrial Dehumidifier Owner’s Manual
- June 5, 2024
- EIP
Table of Contents
EIP DD400 Industrial Dehumidifier
UNPACKING
Carefully remove the DD400 dehumidifier unit from its transit box and visually
check for signs of transit damage. If there is evidence of damage DO NOT
attempt to operate the unit, call your supplier for advice. Do not discard the
packing, it will be useful when transporting the dehumidifier unit in the
future.
INTRODUCTION
Dehumidifiers remove moisture from the air that is circulating through the
unit. The resulting reduction of relative humidity helps prevent rust, rot,
mould, mildew and condensation within the room, or other enclosed spaces where
the dehumidifier is used. The DD400 is of the desiccant wheel type designed to
dry air by passing a large volume of air, the “process” air through a slowly
rotating Silica gel rotor. Silica gel is a hygroscopic material that absorbs
moisture direct from the air. As the air passes through the rotor the humidity
of the air is reduced, whilst the moisture content of the rotor is increased.
A smaller volume of air, the reactivation air, is heated by an internal heater
and passes through a portion of the rotor in the opposite direction. As this
heated air passes through the rotor it will “reactivate” it by removing the
moisture content from the silica gel material. The reactivation air will leave
the humidifier as warm, moist air and must be vented to outside of the
building.
Continuous circulation of the room air through the dehumidifier unit gradually
reduces the relative humidity in the room.
The DD400 dehumidifier is a robust, compact unit designed to control the
humidity in the enclosed space in which it is placed. The casing is fabricated
from Stainless Steel 304 and has been designed for the exacting conditions
which can prevail in offices, shops, houses, restaurants, public houses etc.
It combines lightness and compactness with high reliability and strength.
Carry handles are provide to contribute to its portability.
The unit is thermally protected and will switch off if the maximum operating
temperature of 40ºC is exceeded.
The dehumidifier has two separate filters. One in the “process” air inlet and
one in the “reactivation” air inlet, used to clean the air entering the
dehumidifier.
SPECIFICATIONS
MODEL : | DD400 |
---|---|
HEIGHT : | 420mm |
WIDTH : | 400mm |
DEPTH : | 540mm |
WEIGHT : | 27 Kg |
DRY AIRFLOW : | 370 M³/HR |
WET AIRFLOW : | 150 M³/HR |
POWER SUPPLY : | 230V, 1 ph, 50Hz |
POWER | 2.2 kW (max) |
FINISH : | Stainless steel 305 |
DEHUMIDIFICATION CAPACITY
(AT 28°C AND 60% RH)| 34 lt/day
NOISE| 67dB(A)
INSTALLATION
POSITIONING:
The DD400 is designed for indoor use. Position the dehumidifier unit in the center of the room to be conditioned if at all possible.
NOTE: Both the air inlets and outlets of the dehumidifier unit must have clear space around them and not be obstructed in anyway. For correct installation and operation the unit inlet and outlet must have a clearance of 0.5M from all adjacent surfaces and or structures
DUCT CONNECTION
The wet air outlet from the dehumidifier must be exhausted to outside of the room being dried by means of a suitable duct. All duct connections to the dehumidifier have been designed for connections to standard size ducts. The duct should be as short as possible to reduce the risk of condensation of the wet air. The duct should slope downwards away from the unit to stop any condensed water from flowing back into the unit.
The dry air outlet is also provided with a means of attaching a duct. This can be used to direct the air towards more severe damp patches.
WIRING:
WARNING: THIS APPLIANCE MUST BE EARTHED
The DD400 is provided with a standard plug and is designed to operate from a
13 Amp supply.
IMPORTANT The wires in the mains lead are coloured in accordance with the
following code:
GREEN & YELLOW…………EARTH
BLUE………………………….NEUTRAL
BROWN……………………….LIVE
If the supply cord is damaged it must be replaced by qualified Ebac Industrial
Products Ltd personnel or other similar qualified persons in order to avoid
hazard.
OPERATION
The electrical controls are located on the front of the unit. They are:
-
ON / OFF Switch
0 Dehumidifier OFF
1 Dehumidifier ON -
Humidity Switch
M Dehumidifier in continuous operation
A Dehumidifier operation by means of an external humidistat -
An ammeter is provided to display the current used by the unit.
-
An hour counter is provided to display the total time the unit has been in operation
-
A socket is provided for connection of a external humidistat
To start the dehumidifier, turn the On / Off switch to position
- Turn the humidity switch to position M. After a slight delay the fans will operate air can be felt blowing from the air outlets and the heater will come on. The unit will operate continuously at this setting.
Note. The DD400 is controlled by an electronic circuit board and uses dual PTC (positive temperature coefficient) heater technology to provide the heat necessary to “reactivate” the rotor. To ensure safe start up, the heaters are switched on in stages the first heater is switched on at start up and the remaining heater switched on after 10 seconds. At switch on, the ammeter will initially show a higher current for a few seconds, prior to settling to a steady value. This is normal. After 10 seconds the ammeter will again show an increased value as the second heater is switched on. This is normal.
If an external humidistat control is fitted, turn the humidity switch to
position A. Depending on the setting of the humidistat, the dehumidifier may
switch off as the relative humidity in the room decreases. As the humidity
increase the unit will automatically switch back on.
The Humidistat plug supplied should be wired using pins numbered 1 & 2. Pin 3
is not required. See diagram 5010307 at back of manual.
AIR MOVING SYSTEM:
The DD400 is a dual fan system with dedicated fans for the “Process” air and
“Regeneration” air flows. As the air passes over the rotor, it will be heated
as a result of the regeneration cycle. The air leaving the unit will be hotter
than the air entering
During normal operation some parts of the dehumidifier may become hot. This is
normal.
HIGH TEMPERATURE CUT OUT:
The DD400 dehumidifier has been designed to work in ambient conditions of
-20ºC to +40ºC. Should the temperature in the room become excessive an
overheat protector will operate, switching off the PTC heaters. The fans and
drive motor will continue to operate. This is a manual reset device. Prior to
resetting the protector, check that the dehumidifier is installed correctly
and the ambient temperature does not exceed 40°C. See repairs section for
details on resetting device.
DEHUMIDIFICATION CAPACITY
Approximate capacity in Kg/h at different inlet process air temperature and
relative humidity (%)
Dehumidification Capacity Kg/h
Process Air Temperature (°C)
SAFETY
-WARNING-
DO NOT ALLOW CHILDREN TO PLAY WITH OR AROUND THE UNIT. ENSURE THE UNIT IS
INACCESIBLE TO CHILDREN WHEN NOT ATTENDED.
DO NOT USE THIS UNIT IN AN ENVIRONMENT CONTAINING FLAMMABLE FUMES
DO NOT USE THIS UNIT IF THE CABINET OR POWER CORD IS DAMAGED
DO NOT INSERT OBJECTS INTO ANY OF THE GRILLES ON THE MACHINE
DO NOT COVER OR OBSTRUCT AIRFLOW FROM THE GRILLES
DO NOT OPERATE THE UNIT WITH THE COVERS REMOVED DO NOT ATTEMPT ANY REPAIRS
SHOULD THE UNIT FAIL TO
OPERATE DO NOT STAND ON THE UNIT DO NOT LIFT THE UNIT WHEN SWITCHED ON DO
CHECK THE PLUG ON THE EQUIPMENT MATCHES THE
SUPPLY DO USE THE UNIT FOR THE PURPOSE FOR WHICH IT WAS
DESIGNED DO ENSURE THE POWER CORD AND SUPPLY IS EARTHED
CORRECTLY DO USE A RESIDUAL CURRENT DEVICE “RCD” WHERE
POSSIBLE DO KEEP THE UNIT DRY. NEVER USE A HOSE OR PRESSURE
WASHER TO CLEAN THE UNIT.
ROUTINE SERVICE & REPAIR
WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED
BEFORE CARRYING OUT ROUTINE
SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A
SUITABLY QUALIFIED
PERSON..
SWITCH OFF THE DEHUMIDIFIER APPROXIMATELY 15 MINUTES PRIOR TO REMOVING ANY PANELS, ALLOWING
THE HEATER TO COOL DOWN
To ensure continued full efficiency of the dehumidifier, maintenance
procedures should be performed as follows:
-
We recommend that the filters are checked at least once a month. Intervals for cleaning or replacement of filters will depend on the installation
-
Never operate the dehumidifier without the filters, as the rotor can be damaged by dust.
To carryout the following, it is necessary to remove the top cover panel. This machine should be serviced by qualified Ebac Industrial Products Ltd personnel or other persons having technical competence in servicing electrical equipment following the instructions in this Service Manual. -
The rotor is maintenance free. However, should it be necessary to clean the rotor, compressed air should be used to carefully blow dirt from the rotor.
-
The PTC heaters are maintenance free. However should it be necessary to clean the heaters, compressed air should be used to carefully blow dirt from the heaters.
-
Check that the fans are firmly secured and that the fan rotates freely.
-
Check all wiring connections.
-
Check the belt tensioning at regular intervals. Adjust when needed by loosening the four bolts holding the drive wheel and rotating the drive motor until correct tension is achieved.
-
The overheat protector is located inside the unit, towards the front, near the rotor. To reset this device press the red button.
-
Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part.
IF ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC INDUSTRIAL PRODUCTS
LTD SERVICE CENTER PRIOR TO CONTINUED
OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE.
TROUBLESHOOTING
SYMPTOM | CAUSE | REMEDY |
---|---|---|
Filter clogged | Clean or replace filters | |
Little or no dehumidification capacity | No regeneration heat Reduced |
airflow
No rotation of Rotor| Check PTC / OHP Check fans / duct
Check belt tension / drive motor
| Air leakage| Check sealing
Dehumidifier does not start
| No power
Correct switch setting| Check fuse
Check Auto / Manual switch
| Loose electrical wiring| Check wiring diagram – fault find & repair
| Drive belt slipping| Check belt tension
Rotor does not rotate| Drive belt broken
Rotor jammed| Replace drive belt
Check center shaft, rim of rotor
| Drive motor faulty| Check supply /Replace motor
No Dry or Wet Air Airflow| Filter clogged
Fan faulty Ducts blocked| Clean or replace filters Check supply / fan
Check duct for obstruction
Low current displayed on ammeter| Low reactivation airflow
PTC faulty| Check air path for restriction
Check PTC / OHP
Noisy| Fan loose
Loose fastenings| Check fans secured firmly
Tighten all fastenings
SPARE PARTS LIST
DESCRIPTION | PART NUMBER |
---|---|
Process Air Fan Motor | 3040251 |
Capacitor for Process Air Fan Motor | 3030835 |
Process Inlet Filter | 2050029 |
Regeneration Air Fan Motor | 3040250 |
Capacitor for Regeneration Air Fan Motor | 3030834 |
Regeneration Inlet Filter | 2050030 |
Drive Motor | 3040289 |
Capacitor for Drive Motor | 3030907 |
Pulley | 3050569 |
Pulley Belt | 3050566 |
PTC Heater | 3031625 |
Overheat Protector | 3477026 |
Desiccant Wheel | 3020761 |
PCB Controller | 1619600 |
Mains Cable | 2029217 |
On / Off Switch | 3030557 |
Auto / Manual Switch | 3030522 |
Ammeter | 3180101 |
Hour Counter | 3030778 |
Humidistat Socket | 3033806 |
Humidistat Plug | 3033807 |
Spare parts available online
www.EIPLDIRECT.com
WARNINGS
This appliance can be used by children from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning use of
the application in a safe way and understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children without
supervision.
If the SUPPLY CORD is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified person in order to avoid hazard.
UK Head Office
Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County
Durham DL14 9AD
Tel: +44 (0) 1388 664400
Fax: +44 (0) 1388 662590
www.eipl.co.uk
sales@eipl.co.uk
American Sales Office
Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News
Virginia, 23606-2575 USA
Tel: +01 757 873 6800
Fax: +01 757 873 3632
www.ebacusa.com
sales@ebacusa.com
German Sales Office
Ebac Industrial Products Ltd. Gartenfelder Str. 29-37 Gebäude 35 D-13599,
Berlin Germany
Tel: +49 3043 557241
Fax: +49 3043 557240
www.eip.ltd.de
sales@eip-ltd.de
References
- EIP Group - Industrial Dehumidifiers
- EIP Group - Industrial Dehumidifiers
- EIPL - Industrial Dehumidifiers
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>