BANNER R45C Analog to IO-Link Device Converter User Manual

June 5, 2024
BANNER

R45C Analog to IO-Link Device Converter
User Manual

R45C Analog to IO-Link Device Converter

This guide is designed to help you set up and install the R45C Analog to IO- Link Device Converter. For complete information on programming, performance, troubleshooting,  dimensions, and accessories, please refer to the Instruction Manual at www.bannerengineering.com. Search for p/n 222980 to view the Instruction Manual. The use of this document assumes familiarity with pertinent industry standards and practices.

  • Compact analog to IO-Link device converter that outputs an analog value, voltage, or current, as presented by the IO-Link Master
  • The converter also connects to an analog source, voltage, or current, and outputs the value to the IO-Link master
  • Rugged over-molded design meets IP65, IP67, and IP68
  • Connects directly to a sensor or anywhere in-line for ease of use

Overview

Analog In
When an analog input value is received by this converter, the numerical representational value is sent to an IO-Link Master via Process Data In (PDI).
PDI Analog Ranges:

  • Voltage = 0 mV to 10,000 mV
  • Current = 4,000 µA to 20,000 µA

Analog Out
This converter also allows the user to output an analog value by sending the numerical analog value from the IO-Link Master via Process Data
Out (PDO).
PDO Analog Ranges:

  • Voltage = 0 mV to 11,000 mV
  • Current = 0 µA to 24,000 µA

PDO Outside Valid Range (POVR)
If the PDO value sent to this converter is outside of the PDO Analog Range value, then the actual analog output value will be set to one of the
three selectable POVR levels after a 2-second delay:

  • Low (default): 0 V or 3.5 mA
  • High: 10.5 V or 20.5 mA
  • Hold: Level retains previous value indefinitely

Note: If a connected IO-Link sensor is changed back to SIO mode, then the previous value will be held.

Status Indicators

The R45C Analog to IO-Link Device Converter has two ambers LED indicators on both sides for IO-link and analog communications to allow for installation needs and still provide adequate indication visibility. There is also a green LED indicator on both sides of the converter, which signals the device’s power status.

IO-Link Amber LED

Indication| Status
Off| IO-Link communications are not present
Flashing Amber (900 ms On, 100 ms Off)| IO-Link communications are active
Analog In Amber LED

Indication| Status
Off| The Analog current value is less than setpoint SP1
OR analog value is greater than setpoint SP2
Solid Amber| The Analog current value is between setpoint SP1 AND setpoint SP2
Default Current Values:
• SP1 = 0.004 A
• SP2 = 0.02 A| Default Voltage Values:
• SP1 = 0 V
• SP2 = 10 V
Analog Out Amber LED

Indication| Status
Off| Turns off if the written PDO analog value is outside the allowable output range
Solid Amber| Turns on if written PDO analog value is inside the allowable output range
Allowable Current Range: 0 mA to 24 mA Allowable Voltage Range: 0 V to 11 V

Mechanical Installation

Install the R45C to allow access for functional checks, maintenance, and service or replacement. Do not install the R45C in such a way to allow for intentional defeat. All mounting hardware is supplied by the user. Fasteners must be of sufficient strength to guard against breakage. The use of permanent fasteners or locking hardware is recommended to prevent the loosening or displacement of the device. The mounting hole (4.5 mm) in the R45C accepts M4 (#8) hardware. See the figure below to help in determining the minimum screw length.

Screw Length (with screw head fitting in counterbore) = 12.9 mm + “X” mm + 3 mm
CAUTION: Do not overtighten the R45C’s mounting screw during installation. Overtightening can affect the performance of the R45C.

Specifications

Supply Voltage
18 V DC to 30 V DC at 50 mA maximum
Power Pass-Through Current
4 A maximum
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Leakage Current Immunity 400 µA
Resolution 14 bits
Accuracy 0.5%
Indicators Green: Power
Amber: IO-Link communications
Amber: Analog input value present
Amber: Analog output value in the range
Connections
Integral male/female 4-pin M12 quick disconnect
Construction
Coupling Material: Nickel-plated brass
Connector Body: PVC translucent black
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)
Certifications
Banner Engineering Europe
Park Lane, Culliganlaan 2F bus 3, 1831 Diegem, BELGIUM
Turck Banner LTD Blenheim House, Blenheim Court, Wickford, Essex SS11 8YT, Great Britain

Environmental Rating
IP65, IP67, IP68
NEMA/UL Type 1
Operating Conditions
Temperature: –40 °C to +70 °C (–40 °F to +158 °F)
90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature: –40 °C to +80 °C (–40 °F to +176 °F)
Required Overcurrent Protection
WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations. Overcurrent protection is required to be provided by the end product application per the supplied table.
Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.

Supply Wiring (AWG) Required Overcurrent Protection (Amps)
20 5
22 3
24 2
26 1
28 0.8
30 0.5

Banner Engineering Corp. Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture that, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for the misuse, abuse, or improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING, OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO THE BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL, OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by anner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com.
For patent information, see www.bannerengineering.com/patents.
FCC Part 15
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.
Industry Canada
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.

  More sensors more solutions
© Banner Engineering Corp. All rights reserved

Documents / Resources

| BANNER R45C Analog to IO-Link Device Converter [pdf] User Manual
R45C Analog IO-Link Device Converter, R45C, Analog IO-Link Device Converter, IO-Link Device Converter, Converter
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals