MEAN WELL MDR-60-24 60W Single Output Industrial DIN Rail Power Supply Owner’s Manual
- June 1, 2024
- MEAN WELL
Table of Contents
MEAN WELL MDR-60-24 60W Single Output Industrial DIN Rail Power Supply
Product Information
Specifications:
- Product Name: 60W Single Output Industrial DIN Rail Power Supply
- Series: MDR-60
- GTIN CODE: [Insert GTIN CODE]
- Features:- Universal AC input/Full range
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- Class I, Div 2 Hazardous Locations T4
- LED indicator for power on
- DC OK relay contact
- No load power consumption
 
Product Usage Instructions
Installation :
- Ensure the power supply is compatible with your system’s requirements.
- Mount the power supply on a DIN rail TS-35/7.5 or 15 securely.
- Connect the universal AC input to the power source.
- Verify proper cooling by allowing free air convection around the power supply.
Operation:
- Check the LED indicator for power status.
- Ensure proper connections for DC output.
- Monitor for any overload or short circuit issues.
Maintenance :
- Regularly check for dust accumulation and clean if necessary.
- Inspect for any signs of wear or damage and replace components as needed.
FAQ
- 
Q: What should I do if the DC OK relay contact is not functioning? 
 A: Check the connections and ensure they are properly secured. If the issue persists, contact customer support for assistance.
- 
Q: Can the power supply be used in hazardous locations other than Class I, Div 2 areas? 
 A: No, it is recommended to only use the power supply in Class I, Div 2 Hazardous Locations T4 as specified.
60W Single Output Industrial DIN Rail Power Supply
MDR-60 series
Features
- Universal AC input/Full range
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- Class I, Div 2 Hazardous Locations T4
- LED indicator for power on
- DC OK relay contact
- No load power consumption<0.75W
- 100% full load burn-in test
- 3 years warranty
GTIN CODE MW Search: https://www.meanwell.com/serviceGTIN.aspx

| MODEL | MDR-60-5 | MDR-60-12 | MDR-60-24 | MDR-60-48 | 
|---|---|---|---|---|
| OUTPUT | DC VOLTAGE | 5V | 12V | 24V | 
| RATED CURRENT | 10A | 5A | 2.5A | 1.25A | 
| CURRENT RANGE | 0 ~ 10A | 0 ~ 5A | 0 ~ 2.5A | 0 ~ 1.25A | 
| RATED POWER | 50W | 60W | 60W | 60W | 
| RIPPLE & NOISE (max.) **Note.2** | 80mVp-p | 120mVp-p | 150mVp-p | 200mVp-p | 
| VOLTAGE ADJ. RANGE | 5 ~ 6V | 12 ~ 15V | 24 ~ 30V | 48 ~ 56V | 
| VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | 
| LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | 
| LOAD REGULATION | ±1.5% | ±1.0% | ±1.0% | ±1.0% | 
| SETUP, RISE TIME Note.5 | 500ms, 30ms/230VAC 500ms, | 
30ms/115VAC at full load
HOLD UP TIME (Typ.)|  50ms/230VAC            20ms/115VAC at full load
INPUT|  VOLTAGE RANGE|  85 ~ 264VAC           120 ~ 370VDC
FREQUENCY RANGE|  47 ~ 63Hz
EFFICIENCY (Typ.)|  78%| 85%| 87%| 87%
AC CURRENT (Typ.)|  1.8A/115VAC            1A/230VAC
INRUSH CURRENT (Typ.)|  COLD START 30A/115VAC           60A/230VAC
LEAKAGE CURRENT|  <1mA / 240VAC  
PROTECTION
|  OVERLOAD|  105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after
fault condition is removed
OVER VOLTAGE|  6.25 ~ 7.25V| 15.6 ~ 18V| 31.2 ~ 36V| 57.6 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
FUNCTION|  DC OK SIGNAL|  Relay contact rating(max.): 30V/1A
resistive
ENVIRONMENT|  WORKING TEMP.|  -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY|  20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY|  -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT|  ±0.03%/℃ (0 ~ 50℃)
VIBRATION|  Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min.
each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
SAFETY & EMC **(Note 4)|  SAFETY STANDARDS|  Ul508, UL62368-1, TUV
BS EN/EN62368-1,Class I, Div. 2 Group A, B, C, D Hazardous Locations T4, EAC
TP TC 004, BSMI CNS14336-1, AS/NZS 60950.1 , IS13252(Part1)/IEC60950-1(except
48V) approved
WITHSTAND VOLTAGE|  I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE|  I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION|  Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3
Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B
EMC IMMUNITY**|  Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS
EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3, heavy industry level, EAC TP
TC 020  
OTHERS
|  MTBF|  2355.2K hrs min.       Telcordia SR-332 (Bellcore) ; 489.9K hrs
min.        MIL-HDBK-217F (25℃)
DIMENSION|  4090100mm (WHD)
PACKING|  0.33Kg; 42pcs/14.8Kg/0.82CUFT
NOTE|
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
- (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
- Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set-up time.
- The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).
Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Mechanical Specification

Block Diagram

| Contact Close | PSU turns on / DC OK. | 
|---|---|
| Contact Open | PSU turns off / DC Fail. | 
| Contact Ratings (max.) | 30V/1A resistive load. | 
- 
Derating Curve 
- 
Output Derating VS Input Voltage 
  
- 
Downloaded from Arrow.com. 
- 
File Name: MDR-60-SPEC 2024-02-19 
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>
