MEAN WELL RS-25 Series Single Output Switching Power Supply Owner’s Manual

June 1, 2024
MEAN WELL

25W Single Output Switching Power Supply
RS-25 seriesMEAN WELL RS-25 Series Single Output Switching Power
Supply GTIN CODE MW Search
https://www.meanwell.com/serviceGTIN.aspx

Features :

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • LED indicator for power on
  • 100% full load burn-in test
  • All using 105t long life electrolytic capacitors
  • Withstand 300VAC surge input for 5 second
  • High operating temperature up to 70t
  • Withstand 5G vibration test
  • No load power consumption<0.5W
  • High efficiency, long life and high reliability
  • 3 years warranty

https://www.meanwell.com/Upload/PDF/Enclosed_Type_EN.pdf

SPECIFICATION

MODEL RS•25-3.3 RS•25•5 RS•25•12 RS•25•15 RS•25-24 RS-25-48
OUTPUT DC VOLTAGE 3.3V 5V 12V 15V 24V
RATED CURRENT 6A 5A 2.1A 1.7A 1.1A 0.57A
CURRENT RANGE 0 – 6A 0 – 5A 0 – 2.1A 0 – 1.7A 0 – 1.1A 0 – 0.57A
RATED POWER 19.8W 25W 25.2W 25.5W 26.4W 27.36W
RIPPLE & NOISE (max.) Natal 80mVp-p BOmVp-p 120mVp-p 120mVp-p 120mVp-p

200mVp-p
VOLTAGE ADJ. RANGE| 2.85 – 3.6V| 4.75 – 5.5V| 10.8 – 13.2V| 13.5 – 16.5V| 22 – 27.6V| 42 – 54V
VOLTAGE TOLERANCE Note.3| ±3.0%| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION Note.4| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION Note.3| ±2.0%| ± 1.0%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 1800ms, 23ms/230VAC 4000ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)| 80ms/230VAC 14ms/115VAC at full load
INPUT| VOLTAGE RANGE| 88 – 264VAC 125 – 373VDC (Withstand 300VAC surge for 5sec. Without damage)
FREQUENCY RANGE| 47 – 63Hz
EFFICIENCY(Typ.)| 74.%| 179.%| 182.%| 184.%| I86%| I85%
AC CURRENT (Typ.)| 0.7A/115VAC 0.4A/230VAC
INRUSH CURRENT (Typ.)| COLD START 45A/230VAC
LEAKAGE CURRENT| <2mA/ 240VAC
PROTECTION| OVERLOAD| 110 -180% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER VOLTAGE| 3.8 – 4.45V| I 5.75 – 6.75V| 1 13.8 – 16.2V| 1 17.25 – 20.25V| I 27.6 – 32.4V I| 55.2 – 64.8V
Protection type : Shut off o/p voltage, damping by zener diode
ENVIRONMENT| WORKING TEMP.| -20 – +70t (Refer to ‘Derating Curve’)
WORKING HUMIDITY| 20 – 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 – +85t , 10 – 95% RH
TEMP. COEFFICIENT| ±0.03%1°C (0 – 50°C)
VIBRATION| 10 – 500Hz. 5G 10min./1cycle. period for 60min. each along X. Y, Z axes
SAFETY &
EMC (Note 6)| SAFETY STANDARDS| UL62368-1, TUV BS EN1EN62368-1 , AS/NZS 62368.1, EAC TP TC 004, CCC 064943.1, BSMI CNS14336-1, BIS IS13252(Part1):201011EC 60950-1: 2005 approved
WITHSTAND VOLTAGE| UP-0/P:3KVAC UP-FG:2KVAC 0/P-FG:0.5KVAC
ISOLATION RESISTANCE| 11P-0/P, UP-FG, O!P-FG:100M Ohms! 500VDC / 25°C/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2.-3,G69254 class 6.GB17625.1, EAC TP TC 020, CNS13438 Class B
EMC IMMUNITY| Compliance to 6S EN/EN61000-4-2,3,4,5,6,8,11, BS EN1EN55035, light industry level, EAC TP TC 020
OTHERS| MTBF| 3992.0K hrs min. Telcordia SR-332 (Bellcore) ; 663.3K firs min. MIL-HDBK-217F (25t )
DIMENSION| 7851’28mm (LW•H)
PACKING| 0.2Kg; 60pcs/13Kg10.46CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25-C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1 rt F & 47 If F parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high Me at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. The power sum is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re- confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.’
(as available on https://Awnv.meanwell.com//Upbad/PDF/EMIfitatement_en.pdf )
7. The ambient temperature derating of 3.5-C/1000m with fanless models and of 5.C/1000m with fan models for operating altitude higher than 2000m(6500ft). Product Liability Disdains. : For detailed information, please refer to https://wvmmeanwell.com/serviceDisciaimeraspx

Mechanical Specification

MEAN WELL RS-25 Series Single Output Switching Power Supply -
Specification

Block Diagram

MEAN WELL RS-25 Series Single Output Switching Power Supply -
Diagram

Derating Curve

MEAN WELL RS-25 Series Single Output Switching Power Supply -
Curve

Output Derating VS Input Voltage

Documents / Resources

| MEAN WELL RS-25 Series Single Output Switching Power Supply [pdf] Owner's Manual
RS-25 Series Single Output Switching Power Supply, RS-25 Series, Single Output Switching Power Supply, Output Switching Power Supply, Switching Power Supply, Power Supply, Supply
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals