Aquis EV433934 Scout Digital Flow Meter Installation Guide
- June 6, 2024
- Aquis
Table of Contents
SCOUT Flowmeter
Overview of components
Definitions of terms:
- Programming and display unit
- Display
- “MENU” button
- The “RESET” button
- “MODIFY” button
- Connector power supply
- Alarm
- Connector flowmeter sensor
- Sensor unit with G 3/8” F nut and G 3/8” M thread
- Cable 1.5 m
- Filter head bracket
- Wall bracket
- Cable guide
General Information
The SCOUT flowmeter was specially developed for monitoring water filter cartridges. It is used to measure the amount of filtered water and to display the remaining filter capacity until replacement. Therefore, the filter- specific nominal capacity must be entered into the device. If the capacity is exhausted or if the maximum operating time of 12 months is exceeded, the filter cartridge must be replaced. The programming and display unit provides the following information:
- nominal capacity and remaining filtration capacity of the cartridge
- total filtrate volume since Flowmeter installation
- filtrate volume and operation time of the last five installed filter cartridges
- gal to liter
Technical Data
Sensor Unit | Standard Version |
---|---|
Connection | inches |
Operating pressure (min/max) | bar / psi |
Flow rate | l/h |
Pressure loss | bar |
Precision (horizontal installation) | % |
Water temperature (min/max) | °C / °F |
Ambient temperature (min/max) | °C / °F |
Dimensions (BxHxT) | mm |
Installation position | Horizontalrecommended |
Programming and Display Unit | |
--- | --- |
Graphic display | |
Counter | l |
Dimensions (WxHxD) | mm |
Cable incl. jack plug | |
Power supply |
Instructions
3.1 General
-
Read the Installation and Operation Guide carefully before each installation and start of operation.
Follow all steps exactly as indicated in the instructions. -
Ensure that the flow direction corresponds to the arrows on the sensor unit.
-
It is recommended to mount the sensor horizontally for the highest accuracy.
-
Don’t expose the Flowmeter to any mechanical stress.
-
Ensure that all seals and connections are made using suitable components (are included).
-
The Label with FCC ID and Logo is placed in the battery compartment.
-
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
-
Changes or modifications made to this equipment not expressly approved by Aquis GmbH may void the FCC authorization to operate this equipment.
-
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
-
Reorient or relocate the receiving antenna.
-
Increase the separation between the equipment and receiver.
-
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-
Consult the dealer or an experienced radio/TV technician for help.
3.2 Measurement tips
- Avoid rapidly pulsating water flow
- Avoid water-air mixture
- Avoid inductive interference
- Be aware that the unit is calibrated to measure water flow and hence measurements may vary with other fluids
3.3 Staff
The installation and maintenance of the SCOUT Flowmeter may only be carried
out by trained and authorized personnel.
3.4 Safety Information
- Follow all instructions and guidelines.
- Use only standard battery cells of the type AA (2 pieces).
- Ensure that the battery cover is properly sealed to avoid debris and moisture penetration.
- The battery should be removed in the following cases:
- Water or other liquids ingress into the appliance.
- If the display does not function.
- If the housing or the display unit is damaged.
- If the buttons do not function.
All repairs should only be carried out by an Authorised Service Agent.
3.5 Disclaimer
Information contained in this document is believed to be accurate at the
time of publication but does not constitute a contractual offer. The right is
reserved to alter specifications without prior notice. Illustrations and
tabulated data are for guidance only. Aquis does not assume liability for any
damages, including subsequent damages, that may result from incorrect
installation or usage of the products. Aquis does not assume liability for
damage caused by using parts from other manufacturers.
Installation
4.1 First-time installation of the filter system with the sensor unit
For initial installation of filter system with SCOUT Flowmeter, first, install
the filter head (see Operation Guide “filter systems” chapter 6).
4.2 Installation of the sensor unit to an existing filter system
If a filter system is already in place, follow the following steps:
- Remove connection hose from the filter head liquid outlet using an appropriate tool.
- Connect the sensor unit with the nut directly to the filter head (use the provided flat gasket).
- Connect the hose to the outlet of the sensor unit (use the flat gasket).
NOTE Disconnect the filter head from the water supply before the start of
installation. Ensure correct alignment of the sensor unit with the direction
of flow (arrow on the housing). Use only appropriate tools for the
installation (spanner 19 mm). The sensor unit should be mounted horizontally.
Don`t expose the Flowmeter to any mechanical strain; particularly take care of
any leveraging effect from kinked or bent hoses. If necessary, brace the
connections. Use only suitable gaskets and connecting materials. Before
starting of operation flush the system and check for leaks.
4.3 Programming and Display Unit
4.3.1 Mounting using a screw (is recommended for secure and permanent
fixation)
1. Flat head screw with max. 4 mm shaft diameter is recommended.
4.3.2 Mounting with a glue dot
- Attach the supplied glue dot to the back of the wall mounting.
- Completely remove the protective film from the glue dot.
- Glue the wall mounting in the desired position.
NOTE: Avoid unintentionally pulling out the connector. Handling: press the sensor cable into the cable guide (Fig. 13).
Programming
5.1 General operation
Step | Button | Display | |
---|---|---|---|
1 | Press the „MENU“ button once – Display „filter status“ | ||
2 | Press the „MENU“ button once – Display „flow“ | ||
3 | Press the „MENU“ button once – Display „total count“ | ||
4 | Press the „MENU“ button once – Display „set filter capacity“ | ||
5 | Press the „MENU“ button once – Display „counter reading“ |
– 0 appears in the display = current filter was used at a counter reading
of 287 L|
6| | Press the „MENU“ button once – Display „alarm“|
7| | Press the „MENU“ button once – Display „settings“|
After 30 seconds of inactivity, the display automatically returns to,, filter
status”.
5.2 Setting the filter capacity in a liter
Please follow the capacity instruction for the appropriate CLARIS filter
cartridge (see CLARIS filter Guide).
Step | Button | Display | |
---|---|---|---|
1 | Press and hold the „MENU“ button for approx. 5 sec. | ||
– Active digit flashes | |||
2 | Press the „MODIFY“ button | ||
– Setting the active digit | |||
3 | Press the „MENU“ button – to confirm the desired digit and switch to the | ||
next digit – Active digit flashes (repeat the process to the last digit) |
5.3 Resetting the filter capacity (after replacement of filter cartridge)
Step | Button | Display | |
---|---|---|---|
1 | Menu item „filter status“ Programmed filter capacity exhausted or maximum |
operation time of
12 months exceeded|
2| | Press and hold the „RESET“ button for approx. 5 sec. – „reset 5s“ appears
on the display, the countdown counts down|
3| | The filter capacity is reset, and the last programmed value appears|
After reset, a timer is started that shows a filter change after 360 days.
5.4 Count reading (when inserting the filter)
It is possible to call up the total count reading during the exchange of the
last five filters installed individually.
Step | Button | Display | |
---|---|---|---|
1 | Press and hold the „MENU“ button for approx. 5 sec. – The digit „-1“ | ||
appears = Total count reading at the penultimate exchange of a filter | |||
2 | Press the „MENU“ button once – The digit „-2“ appears, press until „-4“ | ||
possible |
5.5 Alarm
Step | Button | Display | |
---|---|---|---|
1 | Press and hold the „MENU“ button for approx. 5 sec. | ||
– „Beep on“ or „Beep off“ flashes | |||
2 | Press the „MODIFY“ button once | ||
– Change in „Beep on“ or „Beep off“ | |||
3 | Press the „MENU“ button once | ||
– The programmed value appears |
5.6 a Setting unit (Liter or gallon)
Step | Button | Display | |
---|---|---|---|
1 | Press and hold the „MENU“ button for approx. 5 sec. | ||
– „L“ or „Gal“ flashes | |||
2 | Press the „MODIFY“ button once | ||
– Change in „L“ or „GAL“ | |||
3 | Press the „MENU“ button once | ||
– The programmed value appears |
5.6 b Setting pulses per liter
Calibration factor to be able to use other sensors.
Step | Button | Display | |
---|---|---|---|
1 | Press and hold the „MENU“ button for approx. 5 sec. | ||
– „L“ or „Gal“ flashes | |||
2 | Press and hold the „MODIFY“ button for approx. 10 sec. again – „Pulses | ||
per liter“ appears – Active digit flashes | |||
3 | Press the „MODIFY“ button – Setting the active digit | ||
4 | Press the „MENU“ button – to confirm the desired digit and move to the | ||
next digit – Active digit flashes (process belongs to the last digit) |
6. Service / Maintenance
Check the SCOUT flowmeter for leaks daily.
In the event of a fault, please contact your service contractor.