MEAN WELL LOP-600 Series 600W Low Profile Open Frame Power Supply Owner’s Manual

June 16, 2024
MEAN WELL

600W 5″×3″ Low Profile Open Frame Power Supply
LOP-600 series

LOP-600 Series 600W Low Profile Open Frame Power Supply

MEAN WELL LOP-600 Series 600W Low Profile Open Frame Power
Supply

https://www.meanwell.com/Upload/PDF/PCB_EN.pdf

MEAN WELL LOP-600 Series 600W Low Profile Open Frame Power Supply -
icon

Features

  • MEAN WELL Patent Number: ZL 202223277512. 1
  • 5″x3”” compact size with low profile (12V: 35mm .15~-54V: 33.5mm)
  • 80~264Vac input with PFC, No load power consumption<0.5W
  • Global certificates in multi-fields (ITE 62368-1. Medical 60601-1. Househald 60335-1, Industria! 61558-1/-2-16)
  • 150° peak load @ 3s
  • 400W convection, 600W with FAN 23CFM forced-cooled
  • Suitable for Class I or Class II installations
  • Over voltage category III (OVC III)
  • -40 ~ +80°C wide range operation temperature
  • High efficiency up to 95%
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Extremely low leakage current
  • Operating altitude up to 5000 meters
  • Built-in 12V/0.5A for external FAN
  • 3 years warranty

Applications

  • Industrial automation machinery
  • Industrial control system
  • Mechanical and electrical equipment
  • Electronic instruments, equipments or apparatus
  • Power sourcing equipment of PoE
  • Medical devices

Hi GTIN CODE

MW Search: https://www.meanwell.com’serviceGTIN.aspx

Description

LOP-600 is a 600W highly reliable green PCB type low profile power supply with a high power density (30.3W/in’) on the 5” by 3” footprint. It accepts 80~264VAC input and offers various output voltages between 12V and 54V. The working efficiency is up to 95% and the extremely low no load power consumption is down below 0.5W.
LOP-600 is able to be used for both Class I (with FG) and Class I[(no FG) system design. LOP-600 is equipped with complete protection functions; It is complied with the international safety regulations such as IEC/BS EN/EN/UL62368-1,IEC/BS EN/EN60335-1,IEC/BS EN/EN61558-1/-2-16, IEC/BS EN/EN60601-1.LOP-600 serves as a high price-to-performance power supply solution for various industrial applications.The extremely low leakage current is less than 5004A.In addition, it conforms to the international medical regulations (2*MOPP) and EMC BS EN/EN55011, perfectly fitting all kinds of BF rated “patient contact” medical system equipment.

Model Encoding

MEAN WELL LOP-600 Series 600W Low Profile Open Frame Power Supply -
parts

SPECIFICATION

MODEL| LOP-600-12| LOP-600.15| LOP-600.18| LOP-600.24| LOP-600.27| LOP-600.36| LOP-600.48| LOP-600.54
---|---|---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 15V| 18V| 24V| 27V| 36V| 48V| 54V
CURRENT| Peak(3sec.)| 75A| 60A| 50A| 37.5A| 33.3A| 25A| 18.8A| 16.7A
23CFM| 50A| 40A| 33.3A| 25A| 22.3A| 16.7A| 12.5A| 11.2A
Convection| 30A| 24A| 20A| 16.7A| 14.8A| 11.1A| 8.3A| 7.4A
RATED POWER| Peak(3sec.)| 900W| 900W| 900W| 900W| 899.1W| 900W| 902.4W| 901.8W
23CFM| 600W| 600W| 599.4W| 600W| 602.1W| 601.2W| 600W| 604.8W
Convection| 360W| 360W| 360W| 400.8W| 399.6W| 399.6W| 398.4W| 399.6W
RIPPLE& NOISE (max.) Note.2| 120mVp-p| 150mVp-p| 180mVp-p| 200mVp-p| 200mVp-p| 250mVp-p| 250mVp-p| 250mVp-p
VOLTAGEADIRANGE(MAIN OUTPUT)| 11.4∼12.6V| 14.3∼15.8V| 17.1∼18.9V| 22.8∼25.2V| 25.6 ∼ 28.4V| 34.2 ∼37.8V| 45.6 ∼50.4V| 52 ∼58V
VOLTAGE TOLERANCE Note.3| ±3.0%| ±3.0%| ±3.0%| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 1000ms, 50ms/230VAC 1500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)| 12ms@400W load , 8ms@600W load
INPUT| VOLTAGE RANGE Note.4| 80 – 264VAC 113 – 370VDC
FREQUENCY RANGE| 47 – 63Hz
POWER FACTOR| PF>0.95/230VAC PF>0.98/115VAC at full load
EFFICIENCY (Typ.)| 93%| 94.%| 94%| 94%| 95%| 95%| 95%| 95%
AC CURRENT (Typ.)| 6.4A/115VAC 3.2A/230VAC
INRUSH CURRENT (Typ.)| COLD START 40A/115VAC 80A/230VAC
LEAKAGE CURRENT| Earth leakage current < 500mμA(rms) @ 264VAC , touch current < 70mA(rms) @ 264VAC
PROTECTION| OVERLOAD| 105∼150% rated output power, Protection type : Hiccup after 3 sec, recovers automatically after fault condition is removed
OVER VOLTAGE| 13.2 ∼ 15.6V| 16.5∼19.5V| 19.8 ∼ 23.4V| 26.4 ∼ 31.2V| 29.7 ∼ 35.1V| 39.6 ∼ 46.8V| 52.8∼ 62.4V| 59.4 ∼67.5V
Protection type : Shut down o/p voltage, re power on to recover
OVER TEMPERATURE| Protection type : Shut down o/p voltage, recovers automatically after temperature goes down ( Vin=115Vac ) Shut down o/p voltage, re-power on to recover ( Vin=230Vac on Fan Lock )
FUNCTION| EXTERNAL FAN SUPPLY| [email protected] driving a fan / [email protected] without fan: (23CFM) tolerance -15% ∼+15% at main output 20% rated current
REMOTE SENSE| The remote sensing compensatesvoltage drop on the load wiring up to 0.5V
POWER GOOD/ POWER FAIL (optional)| 500ms>PG>10ms ; The TTL signal goes high with 10ms to 500ms delay after power set up; The TTL signal goes low at least 1 ms before Vo below 90% of rated value; TTL(0 ∼ 1V), TTH(2 ∼ 5V)
ENVIRONMENT| WORKING TEMP.| -40 ∼ +80’C (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ∼ 90% RH non-condensing
STORAGE TEMP., HUMIDRY| -40 ∼ +85°C, 10 ∼ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03WC (0 ∼ 50°C)
VIBRATION| 10 ∼ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY &
EMC (Note 5)| SAFETY STANDARDS| CB IEC62368-1, IEC60335-1, IEC,61558-11-2-16, IEC60601-1;
TUV BS EN/EN62368-1, BS EN/EN60335-1, BS EN/EN61558-11-2-16, BS EN/EN60601-1(3.2 Version); UL UL62368-1, ANSI /AAMI ES60601-1(3.2 Version) ;
CCC GB4943.1 ; RCM AS/NZS 61558-11-2-16; EAC TPTC 004 approved.
---|---|---
OVER VOLTAGE CATEGORY| IEC/EN 61558-1/-2-16(0VO Ill altitude up to 2000M )
IEC/EN/UL 62368-1 (OVC II, altitude up to 5000M )
IEC/EN 60335-1 (OVC II, altitude up to 5000M )
IEC/EN 60601-1 (OVC II, altitude up to 4000M )
PROTECTIVE EXTRA- LOW VOLTAGE| IEC/EN61558-2-16 (SELV ) IEC/EN/UL 62368-1 (SELV / ES1 )
WITHSTAND VOLTAGE| UP-0/P:4KVAC UP-FG:2KVAC 0/P-FG:1.5KVAC
ISOLATION RESISTANCE| I/P-0/P, UP-FG, O/P-FG:100M Ohms / 500VDC / 25t/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level /Note
Conducted & Radiated| BS EN/EN55032(CISPR32)| Class I : Class B , Class II: Class A
BS EN/EN55014(CISPR32)| Class I : Class B
Harmonic Current| BS EN/EN61000.3-2| ClassA
Vokage Flicker| BS EN/EN61000-3-3| ——
EMC IMMUNITY| BS EN/EN55035,BS EN/EN61030-6-2
Parameter| Standard| Test Level Mote
ES D| BS EN/EN61000-4-2| Level 4, 15KV air ; Level 4, 8KV contact
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, 10V/m ( 80M Fiz-2.7GFIz ) Table 9, 9-28V/m( 385MHz-5.786Hz )
EFT/Burest| BS EN/EN61000-4-4| Level 3, 2KV
Surge| BS EN/EN61000-4-5| Level4, 4KV/Line-FG ; 2KV/Line-Line
Conducted| BS EN/EN61000-4-6| Level 3,10V
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A1m
Voltage Dips and interruptions| BS EN/EN61000-4.11| > 95% dip 0. 5 periods, 100% dip 1 periods, 30% dip 25 periods >95% interruptions 250 periods
OTHERS| MTBF| 1963.2K hrs min. Telcordia SR-332 (Bellcore) ; 310.9K hrs min. MIL-HDBK-217F (25°C )
DIMENSION| 12V: 12776.235mm (LW1-1) , 15-54V: 12776.233 5m m (LWH)
PACKING| 0.48Kg; 24pcs/13.7Kg/1.10CUFT
NOTE| 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.10 & 47,0 parallel capacitor.
3.Tolerance : includes set up tolerance, line regulation and load regulation.
4.Derating may be needed under low input voltages. Please check the derating curve for more details.
5.The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1 mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
※ Product Liability Disclaimer : For detailed information, please refer to https://www.meanwell.com/serviceDisdaimer.aspx

Block Diagram

MEAN WELL LOP-600 Series 600W Low Profile Open Frame Power Supply -
parts1

Derating Curve

MEAN WELL LOP-600 Series 600W Low Profile Open Frame Power Supply -
parts2

Output Derating VS Input Voltage

Mechanical Specification

MEAN WELL LOP-600 Series 600W Low Profile Open Frame Power Supply -
parts4 Note:
Class I System: Mounting holes marked with have to be  connected to safety earth.
Class II System: Unnecessary to connect with safety earth.
HS1,HS2 can not be shorted

Installation Manual

Please refer to: http://www.meanwell.com/webnet/search/InstallationSearch.html

File Name:LOP-600-SPEC 2023-11-22

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals