AIRZONE Aidoo Pro Wi-Fi Mitsubishi Electric AC Controller User Guide
- June 15, 2024
- AIRZONE
Table of Contents
Quick guide
Aidoo Pro
**AZAI6WSPMD3
**
Environmental policy
- Never dispose of this equipment with household waste. Electrical and electronic products contain substances that can be harmful to the environment if not properly handled. The crossed-out waste bin symbol indicates separate collection of electrical devices, which must be separated from other urban waste. For correct environmental management, at the end of its useful life the equipment should be taken to the collection centers provided for this purpose.
- The parts that make it up can be recycled. Therefore, please respect the regulations in force regarding environmental protection.
- If you replace the equipment, the original equipment must be returned to your dealer or deposited at a specialized collection center.
- Violations are subject to the penalties and measures stipulated in environmental protection law.
Aidoo Pro Control Wi-Fi by Airzone
Device for remote management and integration of units via Cloud services. Control via the “Airzone Cloud” app (available for iOS and Android). Wireless network connection via Wi-Fi. Power supplied by external source. Functionalities:
- Control of the different AC unit parameters.
- Communication via Wi-Fi Dual (2.4/5 GHz).
- Possibility of integration via Local API and Cloud API.
- Detection of errors during communication.
- Time scheduling of temperature and operation mode.
- Multi-user and multi-session.
- Port for integration via Modbus protocol or thermostat connection.
- Automatic mode change.
- Temperature limits for hot and cold.
- On/Off input.
For more information about our products, visit airzonecontrol.com
DEVICE ELEMENTS
Both the shape of the terminal on the Aidoo Pro device and the shape of the cable may vary depending on the compatible manufacturer.
RS-485 port
RS485 port for establishing Modbus
communication with the device. The device will work as a Modbus secondary.
https://doc.airzone.es/producto/Gama_AZ6/Airzone/Comunes/Manuales/MI_AZ6_MODBUS_A4_MUL.pdf
Connection to the indoor unit
This terminal allows the device to communicate with the indoor air to water unit or the thermostat via the connection cable, allowing management of the following parameters:
- On/Off
- Operation mode
- Set-point temperature
As well as reading of room temperature reading and errors in the unit.
Note : Both the shape of the terminal on the Aidoo Pro device and the
shape of the cable may vary depending on the compatible manufacturer.
Factory reset
This button allows you to restore the device to factory settings by pressing
it continuously for more than 10 seconds.
Digital input
Voltage free input. It can be used as a window contact, occupancy or similar
to turn the AC unit on/off if the input changes value.
By default it will be disabled and configured as “normally open.”
Note : It is recommended that the wiring of the digital inputs be routed
through a separate conduit.
Reset of the device
Allows you to reset the device without removing any previously set
configuration parameters.
Power supply input
12 Vdc input that enables providing power to the Aidoo Pro device.
The 230 Vac – 12 Vdc power supply is supplied with the device.
Relay output (12 V) – Auxiliary heat
The relay activation logic depends on whether the air to water unit is
configured to work with supply water temperature or room temperature. No
additional configuration is required in the Aidoo.
Aerothermal LWT mode
Circuit status| Relay
Circuit 1 y Circuit 2 OFF| OFF
Circuit 1 and/or Circuit 2 ON| ON
Circuit 1 and/or Circuit 2 on demand| ON
DHW ON| OFF
DHW OFF| OFF
Aerothermal TH mode
Circuit status| Relay
Circuit 1 y Circuit 2 OFF| OFF
Circuit 1 and/or Circuit 2 ON| OFF
Circuit 1 and/or Circuit 2 on
demand| ON
DHW ON| OFF
DHW OFF| OFF
Aidoo Pro air to water units can work with up to 2 zones and DHW depending on the characteristics of each air to water unit. If there is more than one zone, they must all have the same working settings.
Diagnostic LEDs
Meaning
| Connecting to a Wi-Fi network| Blinking| Green
---|---|---|---
Connected to a Wi-Fi network| Steady
Connected to the server| Steady| Blue
Not configured| Off| –
| Cloud Communications| Blinking| Red
| Microprocessor activity| Blinking| Green
| Power supply| Steady| Red
| Transmission of data to the indoor unit| Blinking| Red
| Reception of data from the indoor unit| Blinking| Green
Configuration of Aidoo Pro Accessories
AIDOO PRO FANCOIL – AIDOO PRO AEROTERMIA EQUIPMENTS
Perform the connection and configuration of the elements according to their
technical specifications:
- AZAI6WSPFAN – Aidoo Pro Fancoil
- AZAI6WSPXXX – Aidoo Pro for aerothermal equipment
Continue with the following steps to complete the solution.
Connection
Connect the INT port of the Aidoo Pro Fancoil to the RS485 port of the Aidoo Pro.
Configuration
Open the Airzone Cloud application. In the sidebar menu, tap on Airtools to
access advanced settings. Tap on the Bluetooth icon to search for devices and
select the one you want to configure.
Tap on Integrations and select the output port with Aidoo Pro Aerothermal.
Operation
Mode | Zone | Water production |
---|---|---|
Cool/Heat | On | On |
Cool/Heat | Confort | Off |
Off | Off |
Advanced settings
To perform advanced configuration of the device, download the Airzone Cloud app.
https://airzonecontrol.com/qrc/aidooAppPro
To access the advanced settings follow the steps described in the Airzone Cloud support section.
AIRZONE CLOUD
Information
Alias. Allows you to assign an alias to identify each device.
Name. Name of the device.
MAC. MAC address of the device.
Version. Displays the webserver version of the device.
Wi-Fi. Network linked to the device.
IP address. Displays the IP address of the device.
Integration. Integrations available through the webserver. Allows you to make
the following configurations depending on the integration selected:
Local:
- Local API. Enables the option of integration with third parties via Local API.
- MDNS. Enables the MDNS service for device discovery within a local network.
Integration port:
- Modbus RS485. Edition of the Modbus ID and selection of communication speed.
Indoor unit*. Displays the following information for the indoor unit: manufacturer, thermostat units (configurable in °C or °F), zone temperature and return temperature.
- Not available in Bluetooth configuration.
Airtools settings in Aidoo PRO Aerothermal
Auto Mode (dual setpoint)**. Allows you to configure changing from automatic
mode based on the setpoints defined for the cooling and heating mode. The
configurable parameters are:
- Setpoint differential. Establishes the minimum differential between cooling mode and,heating mode setpoints (by default 1 ºC / 2 ºF).
- Mode switching protection (min). Allows you to define the minimum operating time before allowing a change of mode, by default 30 min.
Available only in air to water units that have Auto mode and that are
configured to work with room temperature (TH).
Limits**. By default it is disabled. Once it is enabled, it allows you to set
the maximum temperature for heating mode and the minimum temperature for
cooling mode.
Available only if the air to water unit is configured to work with room
temperature (TH).
Note: When temperature limits are enabled it will not be possible to use Auto
mode.
Digital input*. Allows you to activate or deactivate this function and change:
-
Settings. Allows you to set the input as normally open or normally closed.
a. Activation by state: the state is persistent, if the input is activated the machine will be forced off until it changes state.
b. Activation by edge: the status is punctual, only the on/off is sent when the opening or closing condition is met for the first time. -
Time to turn off (minutes). Displays a drop-down for selecting the time (in minutes) that you want to elapse before turning off the equipment after receiving the signal. If disabled, the equipment will automatically turn off after receiving the signal.
-
Time to turn on (minutes). Allows you to select the time (in minutes) that must elapse with the signal deactivated before the equipment turns on again. This setting only turns on the equipment if it has previously been turned off. If it is disabled, the equipment must be switched on again manually.
-
In air to water units with 2 water circuits, the digital input only affects to circuit 1.
Operation of the device
FUNCTIONALITIES
Operation modes
The manufacturer’s units can operate in both room temperature mode (TH) and in
water supply temperature mode (LWT).
Room temperature mode is not currently functional in Airzone systems, and the
unit must always be previously configured to function only in water supply
mode (LWT).
The Aidoo device will be able to regulate the temperature in two circuits in
water supply mode.
DHW control
The manufacturer’s units allow you to manage domestic hot water (DHW)
production status control.
The “Powerful” function can be activated in DHW production status control,
which forces the DHW to reach a temperature that has been preset in the
configuration of the unit. If DHW is turned off, it will not be possible to
activate this parameter.
Status modes
The unit status can be selected from the Airzone device, enabling on/off
control of the unit, after having performed the necessary configuration and
wiring. The unit status can be controlled in both water supply mode and in
domestic hot water production mode (DHW).
The selectable status mode values are Cooling mode, Heating mode and Auto
mode. If the unit is operating in Auto mode, its operation will depend on the
outdoor temperature and the thermostat room temperature.
Set-point temperature
The unit temperature will depend on the operation mode:
- The unit must be previously configured to function in LWT mode, so the water supply temperature at which the unit is to operate must be selected.
- The DHW temperature can be selected within the ranges set by the unit’s own main thermostat.
The temperature limits can be obtained via protocol for LWT mode and for DHW production status control, and they depend on the unit model.WW
PRIOR MANUFACTURER CONFIGURATION
The unit must be configured from the installer menu in order to function correctly:
-
Set the indoor unit address to address 1:
1. Go to menu “17. HMI ADDRESS SET”.
2. Set the parameters to the following values:
17.1 HMI SET = MASTER
17.2 HMI ADDRESS FOR BMS = 1 -
Set the unit to water supply mode (LWT):
1. Go to menu “5. TEMP. TYPE SETTING”.
2. Set the parameters to the following values:
5.1 WATER FLOW TEMP = YES
5.2 ROOM TEMP = NON
5.3 DOUBLE ZONE = (NON for 1 circuit, YES for 2 circuits)
3. Go to menu “6. ROOM THERMOSTAT”.
4. Set the parameters to the following values:
6.1 ROOM THERMOSTAT = NON
Note : Changes must be saved before exiting the menu.
Compatibilities Tool
HOW TO KNOW IF MY AC UNIT IS COMPATIBLE WITH AIRZONE
Visit airzonecontrol.com, then go to the “Control
solutions” menu and select Aidoo Pro:
Once selected, click on “Consult compatibility”:
Select the brand and then the model of your indoor unit:
The compatibility list with the selected unit will appear. If your manufacturer or indoor AC unit does not appear in the list, do not hesitate to contact us.
airzonecontrol.com
Marie Curie, 21
29590 Málaga
Spain
v. 107
References
Read User Manual Online (PDF format)