LEVITON LOGO Series 6000 3-Phase Meter
Cat. No. 61N00
Installation ManualLEVITON 6000 Series 3 Phase MeterDI-000-61N00-20A

WARNINGS AND CAUTIONS

WARNINGS:

  • TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!
  • TO AVOID SHOCK, BURN, OR ARC FLASH: DO NOT CLAMP OR PULL OUT NON-INSULATED CONDUCTORS CARRYING DANGEROUS VOLTAGE!
  • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS WARNINGS AND CAUTIONS CAN CAUSE BODILY INJURY, ELECTRIC SHOCK, BURNS, DEATH OR DAMAGE TO PROPERTY.
  • Only electricians or other qualified personnel should install or remove the product
  • To be installed and/or used in accordance with appropriate electrical codes and regulations.
  • DO NOT attempt to repair the product.

CAUTIONS:

  • Only use Leviton approved accessories.
  • Contact Leviton for any questions regarding the disposal of the product.
  •  When the ambient temperature exceeds +50°C, the minimum temperature rating of the copper cable to be connected to terminal must be +85°C .
  • Always connect the current transformers using the recommended connection RJ12 cables and observing the maximum prescribed currents.
  • Auxillary power supply input terminal maximum voltage is 400 VAC.
  • The product is designed only for the application specified in the operating instructions.
  • The network frequency indicated on the device is observed: 50 or 60 Hz.
  • The device must be positioned within an installation which complies with the standards currently in force.
  • Failure to follow these precautions could cause damage to the device.
  • SAVE THESE INSTRUCTIONS.

PRODUCT DESCRIPTION

2.1 General Description
The VERIFEYE 61N00 (61P00) Power Analyzer is equipped with Ethernet Modbus TCP/IP output and built in web server, and is enclosed in NEMA 4X PC enclosure prewired with fused voltage.
2.2 Physical Dimensions
Below shows the dimentions of the Power Analyzer with enclosure.

LEVITON 6000 Series 3 Phase Meter - Dimension

CONDUIT HOLE

The VERIFEYE 61N00 is shipped without conduit holes. They will need to be cut on the left side, right side, and/or the top of the enclosure. See the below drawings for recommended conduit hole locations.

  1. Open the enclosure door, unscrew the two right ride screws, and lift the metal plate.
  2. Cut the conduit holes only in the locations where conduit fittings will be installed. Conduit hole templates can be found within the black bag that comes in the box.
  3. To maintain the enclosure’s environmental rating, the installer must use conduit hubs/fittings with the same environmental rating as the enclosure. (Fittings not supplied by Leviton)
  4. Maintain spacing of at least ½ in. between conduit hubs/fittings and uninsulated live conductors.
  5. Use “Grounding” conduit fittings with built-in set screws. Run insulated copper conductors, 16AWG or thicker, from fittings to spar ground terminal blocks.
  6. Route incoming voltage conductors at least ¼ in. away from current sensor and signal conductors. Route current sensor conductors at least ¼ in. away from communication conductors.
  7. Use cable ties to secure conductors to each other and to maintain spacing.

LEVITON 6000 Series 3 Phase Meter - Locations

INSTALLATION

4.1 Install Mounting Feet to Back of Enclosure
The 61N00 is shipped with mounting feet and installation hardware.

LEVITON 6000 Series 3 Phase Meter - Hardware

  1. Turn the enclosure so the back side is visible. Then place the mounting feet over the octagon pieces (you can place the mounting feet horizontally, diagonally, or vertically) and fasten them with the ¼ in. -20 x 0.25 in. SS, countersunk Phillips drive screws (torque limit is 30 in. lbs.).LEVITON 6000 Series 3 Phase Meter - Diagonal
  2. Position enclosire vertically (i.e. on a wall) or horizontally (i.e. on a table top).
  3. Mount unit using #10-32 3/4 in. panhead screws and screw directly in the center of the cross on mounting feet.LEVITON 6000 Series 3 Phase Meter - Mounting Location

4.2 Wiring
NOTE: Before wiring the system, make sure that the fuses are NOT installed. The fuses are to be installed AFTER all wiring is complete.
Use class 1 conductors and the input voltage must be 110VAC to 277VAC L-N. Make sure that the metal cover is still open inside the enclosure.

  1. Behind the metal plate the prewired and the components that need to be wired can be seen.
  2. Wire the voltage according to the designated fuse holder (L1, L2, L3, and N).
    Specifications| |
    ---|---|---
    1| 2x OUTPUT
    30 VDC – 20 mA max. – SELV| x= 7 mm
    0.14 mm² – 1.5 mm²| 0.25 N.m max.
    2| 3x INPUT
    12 VDC – 27 mA max. – SELV| x= 7 mm
    0.14 mm² – 1.5 mm²| 0.25 N.m max.
    3| RS485
    MODBUS SELV| x= 7 mm
    0.14 mm² – 1.5 mm²| 0.25 N.m max.
    4| SUPPLY
    110-400 VAC 50-60Hz
    120-300 VDC| x= 7 mm
    0.2 mm² – 2.5 mm²| 0.6 N.m max.
    5| V1-V2-V3-VN
    50-300 VAC (L/N)
    87-520 VAC (L/L’)| x= 7 mm
    0.2 mm² – 2.5 mm²| 0.6 N.m max.
    6| ETHERNET PROFIBUS| –| –
    7|
    | x= 8 mm
    0.2 mm² – 4 mm²| 0.6 N.m max.

SELV: Safety Extra Low VoltageLEVITON 6000 Series 3 Phase Meter -
WiringLEVITON 6000 Series 3 Phase Meter - Wiring
Locations

  1. Maintain spacing of at least ½ in. between conduit hubs/fittings and uninsulated live conductors. Use cable ties to secure conductors to each other and to maintain spacing.

  2. Plug in the RJ12 cables to the VERIFEYE 61N00 and feed the cable out of a conduit hole
    NOTE: Connect the communication protocol being used at this point. For more detailed instructions on how to set up the communication protocols please refer to the VERIFEYE 61P00 instruction manual.

  3. Connect the current transformers to the load and connect them into the appropriate L1/L2/L3 input on the meter using an RJ12 cable.LEVITON 6000 Series 3 Phase Meter - Cable Locations

  4. Put fuses provided in the black bag into the fuse holders.

  5. Close the metal plate and screw it back down. The VERIFEYE 61N00 should now be powered and functioning.

LEVITON 6000 Series 3 Phase Meter - INSTALLATION

Description of the terminals

LEVITON 6000 Series 3 Phase Meter - Description

Means to prevent loosening of the conductors must be fitted on the nearest of the connections.
4.2.2 Connection to the electrical network and to the loads
The Series 6000 can be used on single-phase, two-phase or three-phase circuits.
6.2.1 Configurable loads based on the network type
The table below summarizes the load that it is possible to configure depending on the type of networat the installation.

Network type Configurable load
1P+N single- phase 1P+N – 1CT
2P two-phase 2P – 1CT
2P+N two-phase 2P+N – 2CT
3P three-phase 3P – 3CT / 3P – 2CT / 3P – 1CT
3P+N three-phase 3P+N – 3CT / 3P+N – 1CT

6.2.2 Description of the main network and load combinations
Legend:

LEVITON 6000 Series 3 Phase Meter - Legend

CONFIGURATION

5.1 Configure using Wizard
The VERIFEYE 61N00 can be configured using the display configuration setup “Wizard”. When using Wizard, the VERIFEYE 61N00 provides step by step setup on-screen. Follow the on-screen instructions.
5.2 Configure using EasyConfig
EasyConfig is free software available to download on the Leviton website. If you would like to configure the VERIFEYE 61P00 by EasyConfig please refer to the VERIFEYE 61P00 instruction manual: https://www.leviton.com/en/products/61p00-000
https://www.leviton.com/en/docs/Easy_Config_System_LEVITON_v2.1.1.0.zip
5.3 Webview
Webview offers real-time monitoring of electrical installations and tracking of energy consumption level, embedded in the VERIFEYE 61N00 Ethernet version. It is intended for use by those who wish to have a complete tool to quickly analyze their electrical installation and to guarantee energy-related performance.
Once the configuration is done in EasyConfig, the configuration will be recognized in Webview.

  • Open the internet browser and type in the IP address of the VERIFEYE 61N00.
    The 61N00 default IP address: 192.168.0.4.

LEVITON 6000 Series 3 Phase Meter - Webview

NOTES:

  • For more information on Webview refer to the Webview Instruction Manual.
  • Any changes or modifications not expressly approved by Leviton Manufacturing Co., could void the user’s authority to operate the equipment.

STANDARD STATEMENTS AND WARRANTY

FCC Statement:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Any changes or modifications not expressly approved by Leviton Manufacturing Co., could void the user’s authority to operate the equipment.
IC Statement:
This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic
Development Canada’s license-exempt RSS(s). Operation is subject to the following two conditions:

  1. This device may not cause interference.
  2. This device must accept any interference, including interference that may cause undesired operation of the device.

FCC SUPPLIER’S DECLARATION OF CONFORMITY:
Model Series 6000 meter. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Leviton Manufacturing Co., Inc.
201 North Service Road, Melville, NY 11747
Visit Leviton’s website at www.leviton.com
© 2023 Leviton Manufacturing Co., Inc. All rights reserved.
Specifications and price subject to change at any time without notice.
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada ULC to the attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call: 1-800-824-3005 (USA Only) or 1-800-405-5320 (Canada Only) www.leviton.com

Documents / Resources

| LEVITON 6000 Series 3 Phase Meter [pdf] Instruction Manual
6000 Series 3 Phase Meter, 6000, 61N00, Series 3 Phase Meter, 3 Phase Meter, Phase Meter, Meter
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals