LEVITON LB225-ST Branch Circuit Breaker Installation Guide
- June 1, 2024
- Leviton
Table of Contents
INSTALLATION INSTRUCTIONS
LB225-ST Branch Circuit Breaker
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING.
WARNING
- TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER SUPPLYING THIS EQUIPMENT, AND CONFIRM POWER IS OFF, before installing, removing or servicing this equipment.
- This equipment MUST BE installed and serviced by an electrician.
- Replace all doors and covers before connecting power to this equipment.
- To be installed and/or used in accordance with electrical codes and regulations.
- To be used in permanently installed and listed enclosures only.
- Install only on a single phase 120/240 VAC grounded system in a residential application.
- DO NOT reverse-feed or back-wire. DO NOT perform a megger or a high voltage test with the breaker in place. Remove the breaker prior to high-pot testing of the circuit.
Patents covering this product, if any, can be found on Leviton.com/patents.
FCC STATEMENT
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
IC STATEMENT
This device complies with Industry Canada licence-exempt RSS standard(s).
Operation is subject to the following two conditions: (1) this device may not
cause interference, and (2) this device must accept any interference,
including interference that may cause undesired operation of the device.
Patents covering this product, if any, can be found on
Leviton.com/patents.
For Technical Assistance Call:
1-800-824-3005 (USA Only) or
1-800-405-5320 (Canada Only)
www.leviton.com
Scan this code with your cell phone camera to see the Getting Started Guide.
https://goto.leviton.com/on_off
Branch Circuit Breaker
Visit my.leviton.com/pro to sign up for the My Leviton Pro Support Program.
INSTALLATION
WARNING: TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER SUPPLYING THIS
EQUIPMENT, AND CONFIRM POWER IS OFF, before installing, removing or servicing
this equipment.
-
Turn OFF all power to the panelboard by moving the handle of the main breaker to OFF position (see fig. 1). NOTE: If installing the breaker in a sub-panel turn power OFF from the breaker located in the main panel.
-
Remove panel cover (if necessary).
-
Strip and connect the load power and load neutral conductors to appropriate
terminal lugs (see fig. 1 and the Terminations table). NOTE: THE LOAD NEUTRAL MUST BE CONNECTED TO THE LOAD NEUTRAL TERMINAL, NOT THE MAIN NEUTRAL TERMINAL. -
Place handle of the branch circuit breaker to the OFF position (see fig. 2).
-
Place branch circuit breaker into the panel as shown (see fig. 4).
-
WARNING: Check all wiring and ensure all circuit breakers are installed in the proper position before energizing.
-
Replace all doors and covers before turning ON power to this equipment.
-
If installing 2nd Gen Smart Circuit Breakers, install the supplied “Remotely-operated circuit breakers” label in a location on the panel that is visible without removing the cover or deadfront.
IF INSTALLING A SMART CIRCUIT BREAKER, REFER TO THE “GETTING STARTED GUIDE” TO ENABLE ITS SMART FEATURES USING THE MY LEVITON APP.
HANDLE OPERATION AND LED DIAGNOSTICS
Each circuit breaker’s rocker handle window displays its operational status
using an intuitive color scheme.
In the event that the circuit breaker trips move the handle to the OFF
position and then to the ON position. If the circuit breaker will not reset or
trips again turn OFF or unplug all loads downstream of the circuit breaker and
try again. If the circuit breaker still will not reset contact an electrician
to make repairs.
Handle Window | “ON/OFF” LED | Device Status |
---|---|---|
Green | OFF | ON |
Green | ON (solid) | Remote OFF |
Red | OFF | Overload or short-circuit trip |
White | OFF | Manual OFF |
SAVE THESE INSTRUCTIONS
TERMINATIONS
Termination
Point| Wire
Material| Wire Gauge & Configuration| Strip
Length| Torque
---|---|---|---|---
A (Load Phase, brass)
B (Load Neutral, silver)| Copper| (1) #4 AWG – #8 AWG, Stranded| 0.4 in.| 45
in.-lbs
(1)#10 AWG, Solid or Stranded| 35 in.-lbs
(2)#14 AWG – #10 AWG, Solid
(1)#12 AWG – #14 AWG, Solid or Stranded| 25 in.-lbs.
(2)#14 AWG or (2) #12 AWG, Stranded
Aluminum| (1) #4 AWG – #6 AWG, Stranded| 45 in.-lbs
(1)#8 AWG, Stranded| 35 in.-lbs
(2)#12 AWG – #10 AWG, Solid
(1)#10 AWG – #12 AWG, Solid| 25 in.-lbs.
(2)#12 AWG or (2) #10 AWG, Solid
C (Ground, Neutral & Equipment Ground
Bar)| Copper /
Aluminum| (1) #6 AWG – #4 AWG, Stranded| 0.5 in.| 35 in.-lbs
(1) #8 AWG, Stranded| 25 in.-lbs
(1)#14 AWG – #10 AWG, Solid or Stranded| 20 in.-lbs
Copper| (2)#14 AWG – #10 AWG, Solid or Stranded| 25 in.-lbs
(1) #14 AWG and (1) #12 AWG, Solid| 25 in.-lbs
(1) #14 AWG and (1) #10 AWG, Solid or Stranded| 25 in.-lbs
(1)#12 AWG and (1) #10 AWG, Solid| 25 in.-lbs
Aluminum| (2)#12 AWG – #10 AWG, Solid| 20 in.-lbs
(1) #12 AWG and (1) #10 AWG, Solid| 20 in.-lbs
LIMITED PRODUCT WARRANTY
For Leviton’s limited product warranty, go to www.leviton.com. For a printed copy of the warranty you may call 1-800-323-8920.
PK-A3205-10-02-5G