ICM532 Surge Protective Device Installation Guide

June 13, 2024
ICM

ICM532 Surge Protective Device

ICM532-Surge-Protective-Device-product

Product Information

  • Product Name: ICM532 Surge Protective Device
  • Application: Surge protection for 3-Phase Delta 600 VAC or Wye 347/600 VAC
  • Installation Guide: Click here
  • Maintenance: Regular maintenance required
  • Mode of Operation: Type 1 and 2 SPD

Specifications:

  • Service Voltage (3-Phase): 600 VAC Delta or 347/600 VAC Wye

  • Short Circuit Current Rating (SCCR): 200 kA

  • Nominal Discharge Current (In): 20 kA

  • Surge Protection Technology: TFMOV

  • Protection Mode: L-L, L-N (for Wye configuration only)

  • VPR (Vpk): L-L: 2500, L-N: 1500

  • Maximum Continuous Operation Voltage (MCOV): L-L: 920 VAC, L-N: 460 VAC (for Wye configuration only)

  • Input Power Frequency: 50/60Hz

  • Diagnostics: Green LED indicates surge protection present

  • Enclosure Rating: NEMA/Type 4X water-tight plastic enclosure
    for outdoor and indoor installation

  • Installation Point: Electrical panel/disconnect

  • Dimensions: 4.3″ X 4.1″ X 2.3″

  • Operating Temperature: Less than 85% non-condensing

  • Operating Humidity: Less than 2000 meters

  • Agency Certification and Approvals: ANSI/UL1449 4th Edition Listed Device – cULus Listed

Optional Features:

  • Cornered ground on any of the phases

Product Usage Instructions

  1. Turn off the main breaker and/or main power to the service disconnect.
  2. Determine if you have a Wye or Delta configuration.
  3. Verify your mains voltage and match that with ICM532 ratings.
  4. Remove the cover on the service disconnect or the electrical panel.
  5. Mount the ICM532 through the 3/4 conduit connection of the electrical panel.
  6. Remove the retaining ring and washer on the ICM532.
  7. Feed the wires into the electrical panel or service disconnect.
  8. Re-secure the retaining ring and washer.
  9. Route the white wire to the neutral lug and secure.
  10. Reinstall the cover on the service disconnect or the electrical panel.
  11. Restore power; Green LED should be on indicating full protection.

Note:
For ease of checking the SPD protection status, the LED display should face outwards after the installation has been completed.

Note:
ICM532 is a Type 1 and 2 SPD, designed to be compatible with 3-phase Delta and 3-phase Wye voltage configuration. Please check your supply voltage configuration and voltage levels before installing the ICM532 per the wiring diagram.

INSTALLATION, OPERATION & APPLICATION GUIDE
For more information on our complete range of American-made products – plus wiring diagrams, troubleshooting tips, and more, visit us at www.icmcontrols.com.

IMPORTANT SAFETY INFORMATION

ELECTRICAL SHOCK HAZARD!
Before installing this unit, turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position.

  • WARNING — No Serviceable Parts (Attention: Aucune pièce remplaçable ou reparable).
  • WARNING — Shock hazard — Do not open (ATTENTION – RISQUE DE CHOC – NE PAS OUVRIR).

Please follow all State, Local, and National electrical codes when installing this product. Installation should only be done by a licensed electrician for Type 1 devices or a licensed HVAC technician for Type 2 devices.

INSTALLATION INSTRUCTIONS

The conductors used to connect the SPD shall not be any longer than necessary and shall avoid unnecessary bends.

  1. Turn off the main breaker and/or main power to the service disconnect.

  2. Determine if you have a Wye or Delta configuration.

  3. Verify your mains voltage and match that with ICM532 ratings.

  4. Remove the cover on the service disconnect or the electrical panel.

  5. Mount the ICM532 through the 3/4” conduit connection of the electrical panel.

  6. Remove the retaining ring and washer on the ICM532.

  7. Feed the wires into the electrical panel or service disconnect.

  8. Re-secure the retaining ring and washer.

  9. Route the white wire to the neutral lug and secure.
    Wiring Type 1 installation

    • Route the three black wires to the appropriate L1, L2, and L3 connections before the breaker panel as seen in the wiring diagram for Type 1 installation and according to your local, state, and national electrical codes.

    • There will be a white wire which is only used in the Wye configuration and which needs to be capped off in the Delta configuration.
      Wiring Type 2 installation

    • Route and connect the three black wires (L1, L2, and L3) to the individual breakers on the circuit breaker panel as seen in the wiring diagram for Type 2 installation and according to your local, state, and national electrical codes.

    • There will be a white wire which is only used in the Wye configuration and which needs to be capped off in the Delta configuration.

  10. Reinstall the cover on the service disconnect or the electrical panel.

  11. Restore power; Green LED should be on indicating full protection.

MAINTENANCE

Periodically check the LED status on the SPD. If the Greenlight is OFF, the protection is no longer available and the SPD needs to be replaced immediately. 12 AWG stranded copper wire or larger required. The product contains no serviceable parts. This device features internal protection that will disconnect the surge protective component at the end of its useful life but will maintain power to the load – now unprotected.

MODE OF OPERATION

The ICM532 is a UL Listed Type 1&2 Surge Protective Device for three-phase Delta 600 VAC or Wye 347/600 VAC three-phase voltage configurations. When a surge occurs, the ICM532 will absorb the surge up to the limits expressed in the specifications section of this guide. The ICM532 incorporates thermal protection on the surge elements (TMOVs) which allows for safe disabling of the surge elements when a surge exceeds the thermal limits of the device. The ICM532 has a status light on the control which identifies operational status when illuminated. The ICM532 can be installed as a Type 1 or Type 2 device for both indoor and outdoor applications. Suitable for use on a circuit capable of delivering not more than 200kA RMS symmetrical amperes, 600V maximum (Convient à des circuits produisant au plus 200kA RMS A eff.”, 600V maximum).

SPECIFICATIONS

Description Ratings
Service Voltage (3-Phase) 600 VAC Delta OR 347/600 VAC Wye
Short Circuit Current Rating (SCCR) 200 kA
Nominal Discharge Current (In) 20 kA
SPD Type Type 1 (Can also be used in Type 2 applications)
Surge Protection Technology TFMOV
Protection Mode 3 for Delta configuration

6 for Wye configuration (neutral tied to ground)


VPR (Vpk)

| VOLTS (V) MODE       VPR (Vpk)

600                 L-L             2500

600/347          L-L             2500

L-N            1500

Maximum Continuous Operation Voltage (MCOV)| L-L: 920 VAC L-N: (for Wye configuration only): 460 VAC
Input Power Frequency| 50/60Hz
Diagnostics| Green LED indicates surge protection present
Enclosure Rating| NEMA/Type 4X water-tight plastic enclosure for outdoor and indoor installation
Installation Point| Electrical panel/disconnect
Dimensions| 4.3” X 4.1” X 2.3”
Operating Temperature| -40°F to 185°F (-40°C to 85°C)
Operating Humidity| Less than 85%, non-condensing
Operating Altitude| Less than 2000 meters
Agency Certification and Approvals| ANSI/UL1449 4th Edition Listed Device – cULus Listed

WIRING DIAGRAMS

DELTA CONFIGURATION

Type 1 Wiring – Fuse Disconnect

ICM532-Surge-Protective-Device-fig- \(1\)

Type 2 Wiring – Circuit Breaker

ICM532-Surge-Protective-Device-fig- \(2\)

  • Note 1:
    For ease of checking the SPD protection status, the LED display should face outwards after the installation has been completed.

  • Note 2:
    ICM532 is a Type 1 and 2 SPD, designed to be compatible with 3-phase Delta and 3-phase Wye voltage configuration. Please check your supply voltage configuration and voltage levels before installing the ICM532 per wiring diagram.

  • Note 3:

    • When installing the Surge Protecting Device (SPD), avoid sharp bends in the conduit and long line sets.
    • Keep the mounting conduit straight and short in length.

Legend:

  • BLK Black
  • WHT White
  • A, B, C Incoming phase Ground
WYE CONFIGURATION

Type 1 Wiring – Fuse Disconnect

ICM532-Surge-Protective-Device-fig- \(3\)

Type 2 Wiring – Circuit Breaker

ICM532-Surge-Protective-Device-fig- \(4\)

  • Note 1:
    For ease of checking the SPD protection status, the LED display should face outwards after the installation has been completed.

  • Note 2:
    ICM532 is a Type 1 and 2 SPD, designed to be compatible with 3-phase Delta and 3-phase Wye voltage configuration. Please check your supply voltage configuration and voltage levels before installing the ICM532 per wiring diagram.

  • Note 3:

    • When installing the Surge Protecting Device (SPD), avoid sharp bends in the conduit and long line sets.
    • Keep the mounting conduit straight and short in length.

Legend:

  • BLK Black
  • WHT White
  • A, B, C Incoming phase Ground

LIMITED LIFETIME PROTECTION WARRANTY

  • Review the enclosed warranty information for full details & registration information