FEATURES
√ NEMA Type 4X watertight plastic enclosure for outdoor and indoor
installation
√ Green LED indicates surge protection present
√ Easily connects to an electrical panel or disconnects for indoor and outdoor
applications
√ UL Listed Type 1 or Type 2 SPD
√ Dimensions: 4.30” x 4.10” x 2.30”
OVERVIEW
HE ICM530 is a series of Type 1 and Type 2 three-phase surge protective
devices for three-phase Delta, three-phase Wye, or Delta High-leg
configurations. When a surge occurs, the ICM three-phase surge protective
device will absorb the surge up to the specified limitations of the device.
ICM incorporates superior thermally protected metal oxide varistor technology
into the three-phase surge suppressors, which allows for safe disabling of the
surge elements when a surge exceeds the thermal limits of the device. There is
a single status light on the controls which identifies operational status when
illuminated.
The ICM 3-phase surge protective device can be installed as a Type 1 or Type 2
device for both indoor and outdoor applications.
ICM530 (DELTA OR WYE CONFIGURATION)
-
Service voltage (3-phase): 240 VAC Delta or 120/208 VAC Wye
-
Short Circuit Current Rating (SCCR): 200 kA
-
Nominal discharge current (In): 20kA
-
Protection mode:
• 3 for Delta configuration
• 6 for Wye configuration (neutral tied to ground) -
Maximum Continuous Operation Voltage (MCOV):
• L-L: 300 VAC
• L-N: (for Wye configuration only): 150 VAC -
VPR:
• Delta L-L: 1200 VAC
• Wye L-L: 1200 VAC
• Wye L-N: 700 VAC -
SPD type: Type 1 (can also be used in Type 2 applications)
-
Surge protection technology: TFMOV
-
Input power frequency: 50/60 Hz
ICM531 (DELTA OR WYE CONFIGURATION)
-
Service voltage (3-phase): 480 VAC Delta or 277/480 VAC Wye
-
Short Circuit Current Rating (SCCR): 200 kA
-
Nominal discharge current (In): 20kA
-
Protection mode:
• 3 for Delta configuration
• 6 for Wye configuration (neutral tied to ground) -
Maximum Continuous Operation Voltage (MCOV):
• L-L: 700 VAC
• L-N: (for Wye configuration only): 350 VAC -
VPR:
• Delta L-L: 2500 VAC
• Wye L-L: 2500 VAC
• Wye L-N: 1200 VAC -
SPD type: Type 1 (can also be used in Type 2 applications)
-
Surge protection technology: TFMOV
-
Input power frequency: 50/60 Hz
ICM532 (DELTA OR WYE CONFIGURATION)
-
Service voltage (3-phase): 600 VAC Delta or 347/600 VAC Wye
-
Short Circuit Current Rating (SCCR): 200 kA
-
Nominal discharge current (In): 20kA
-
Protection mode:
• 3 for Delta configuration
• 6 for Wye configuration (neutral tied to ground) -
Maximum Continuous Operation Voltage (MCOV):
• L-L: 920 VAC
• L-N: (for Wye configuration only): 460 VAC -
VPR:
• Delta L-L: 2500 VAC
• Wye L-L: 2500 VAC
• Wye L-N: 1500 VAC -
SPD type: Type 1 (can also be used in Type 2 applications)
-
Surge protection technology: TFMOV
-
Input power frequency: 50/60 Hz
ICM533 (DELTA HIGH-LEG CONFIGURATION)
-
Service voltage (3-phase): 120/240 VAC Delta High-Leg
-
Short Circuit Current Rating (SCCR): 200 kA
-
Nominal discharge current: (In): 20kA
-
Protection mode: 3 for Delta configuration
-
Maximum Continuous Operation Voltage (MCOV):
• L-L: 300 VAC
• L-N: 150 VAC
• H-L: 450 VAC
• L-N: 300 VAC -
VPR:
• L-L: 1200 VAC
• H-L: 1500 VAC
• L-N: 700 VAC
• H-N: 900 VAC -
SPD type: Type 1 (can also be used in Type 2 applications)
-
Surge protection technology: TFMOV
-
Input power frequency: 50/60 Hz