BEGA 12278.1K3 Wall Luminaire For Indoor Use Instruction Manual

June 13, 2024
BEGA

BEGA 12278.1K3 Wall Luminaire For Indoor Use Instruction Manual
BEGA 12278.1K3 Wall Luminaire For Indoor Use

Wall luminaire for indoor use

Product Dimension

Instructions for use

Application
Shielded wall luminaire · indoor luminaire for many lighting tasks in interior applications. The light emits upwards and downwards.

Product description

  • Aluminium alloy housing, finish Colour white
  • Crystal glass, inside white
  • 2 elongated fixing holes
  • Width 4.5mm · 276mm spacing 2 cable entries for through-wiring for mains
  • cable up to ø 10.5 mm max. 3 × 1.5@
  • Connection terminal 2.5@
  • Earth conductor connection
  • LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DC 170-280 V
  • Safety class I
  •  Safety mark
  • Conformity mark
  • Weight: 1.7 kg

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Lamp

Module connected wattage: 12.3 W
Luminaire connected wattage: 15.4 W
Rated temperature: ta=25 °C
Ambient temperature: ta max=35 °C

12 278.1K3

Module designation: LED-0599/930
Colour temperature: 3000 K
Colour rendering index: CRI >90
Module luminous flux: 1810 lm
Luminaire luminous flux: 1023 lm
Luminaire luminous efficiency: 66,4 lm/W

12 278.1K4

Module designation: LED-0599/940
Colour temperature: 4000 K
Colour rendering index: CRI >90
Module luminous flux: 1885 lm
Luminaire luminous flux: 1065 lm
Luminaire luminous efficiency: 69,2 lm/W

Installation

Undo set screws and lift off luminaire housing. LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or relamping.
Loosen earth connection (plug connection) and LED-connection between luminaire housing and mounting plate.
Lead the mains supply cable through the cable entry of the mounting plate.
Note position of application “arrow down”.
Fix mounting plate with enclosed or any other suitable fixing material onto the mounting surface.
It is imperative to use the enclosed gaskets. Make earth connection.
Pull silicone sleeves over the wires and make electrical connection to the terminals.
Make earth connection (plug connection) and LED-connection between luminaire housing and mounting plate again.
Install luminaire onto the mounting plate and tighten set screws evenly.
Note position of application “arrow down”.

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Defective glass must be replaced.

Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced. Close the luminaire.

Spares

LED power supply unit: DEV-0189/350
LED module 3000 K: LED-0599/930
LED module 4000 K: LED-0599/940

BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden · info@bega.com · www.bega.com