COOLON TNR Tunnel Ray Industrial LED User Manual
- June 12, 2024
- COOLON
Table of Contents
COOLON TNR Tunnel Ray Industrial LED User Manual
Technical Specifications
Voltage Range
100 – 240VAC 50/60Hz
Temperature Range
-20 to +50°C
IP Rating
IP66
IK Rating
IK09
Dimension Instruction
Mounting Plat
INSTALLATION INSTRUCTIONS
Step : 1
Choose luminaire position and orientation.
When choosing the location of Tunnel Ray luminaire, please ensure that
sufficient clearance is allowed for the airflow through the heatsink. Avoid
blocking the air vents.
Horizontal Mounting
Vertical Mounting
In a vertical mount, mount the TNR in the following orientation to maximize
the airflow through the heatsink.
Step : 2
Once the Tunnel Ray is securely mounted, open the junction box.
Ensure to only open an accessible area of the junction box that is sealed with
Phillips Head screws.
Step : 3
Feed the cable through the cable gland. Connect wires to terminals
according to the wiring diagram below and secure the cable with the cable
restrainer.
Wire In
Step : 4
Close the junction box. Ensure the rubber gasket is intact and sits snuggly
in the dedicated channel. Secure junction box cover back onto the Tunnel Ray
luminaire using the Phillips Head screws.
Ensure the rubber gasket is intact and sits snuggly in the dedicated channel.
External Earthing
When mounted on a non-conductive or non-earthed facilities, the body of the
luminaire needs to be externally grounded.
One of the 4, M6 nutserts can be used as appropriate. It is recommended that a
spring/locking washer and 4mm2 cable with a suitable terminal is used (not
supplied with the fitting).
Product must be installed by a suitably qualified person. All documentation is subject to change without notice. Refer to our website for the latest information.
support@coolon.com.au
aus. 1300 287 533
intl. +613 8681 3633
www.coolon.com.au
www.coolon.com.au