COOLON DLK3 Industrial LED Luminaire Instruction Manual
- June 12, 2024
- COOLON
Table of Contents
DLK3 INDUSTRIAL LED MANUAL
EDITION 1.2
DLK3 Luminaire
a. Main LEDs (dual alternating CCT)
b. RGBW Indicator
c. EM LEDs
d. EM Test Button
Technical Specifications
VOLTAGE IN | POWER | IP RATING | IK RATING |
---|---|---|---|
200 – 240VAC 50/60Hz, 190 – 250VDC | 68W Max | IP66 | IK09 |
OPERATING TEMPERATURE | STORAGE TEMPERATURE | STORAGE SHELF LIFE* | |
0°C ≤ Tamb ≤ 50°C | 0°C ≤ Tamb ≤ 45°C | Up to 12months @ 20±5°C, Up to 6months @ |
0 to 15°C or 25 to 45°C
- Shelf life is defined as time when the Battery Isolation Switch is placed in OFF position after the product had completed a charge cycle. A factory charge cycle is completed prior to the unit being dispatched. Units stored for periods exceeding the shelf life need to undertake a charge cycle within the prescribed time to ensure battery health, see Storage Shelf Life section of the installation manual.
INSTALLATION INSTRUCTIONS
Step 1
Feed cable into the DLK3 and mount onto the spigot.
Step 2
Secure using U-bolts with washers and nuts.
Step 3
Remove the junction box lid (6x TX25 Torx captive screws) proceed to connect
wires as required.
See DLK3 operating modes for wiring/operation options.
Proceed to connect wires as required.
You can secure the cable using the plastic clamp.
Conductor Requirements
CONDUCTOR SIZE
1 – 2.5mm²
CABLE OD MIN/MAX
7mm/13mm
24mm wrench required for tightening the cable gland
**** Housing is earthed internally.
Step 4
Put the Battery Isolation Switch in the ‘ON’ position if the unit is expected
to be commissioned or put In-Service within the next 24-hours. This 24-hour
window may be extended up to 14 days if a Battery Charge Cycle (see respective
section) was completed within three months prior to the installation.
Switching the Battery Isolation Switch to the ‘ON’ position will initiate the
EMBH “TEST” mode, where the unit performs a self-check and enables the Battery
Module to supply power to LEDS for a duration of up to 2 minutes. This
indicates that the battery is functional and in working order.
The Battery Isolation Switch must be left in the ‘OFF’ position if the above
conditions cannot not be met. Failing to do so may lead to battery depletion
below a recoverable level. This type of failure is not covered under warranty.
** Switching the Battery Isolation Switch to the ‘ON’ position without
having mains connected will result in the unit operating in EM mode for a
duration of up to 2 minutes.
Step 5**
Reattach the junction box lid (6x TX25 Torx captive screws).
Ensure the cover lanyard is not caught between the internal test button and
cover.
OPERATION
Operating Modes
|
|
---|---|---
NON-MAINTAINED
Emergency use only
3 Wires Constant Active Only| MAINTAINED
Always ON*
3 Wires Constant Active Only| SWITCHED
Conventional luminaire use with emergency backup
4 Wires Constant Active and Switched Active
OPERATION STATE| ACTIVE| CONTROL| LUMINAIRE STATE| DESCRIPTION
---|---|---|---|---
Non-Maintained| ON| N/A| OFF| Main LEDs is OFF. RGBW Indicator will indicate
mains presence with Green.
Non-Maintained| OFF| N/A| ON-EM| Main LEDs is OFF. EM LEDs is ON (power
supplied from battery).
RGBW Indicator will be OFF.
Maintained| ON| ON (Link)| ON| Main LEDs is ON. RGBW Indicator will indicate
mains presence with Green.
Maintained| OFF| OFF (Link)| ON-EM| Main LEDs is OFF. EM LEDs is ON (power
supplied from battery).
RGBW Indicator will be OFF.
Switched| ON| ON| ON| Main LEDs is ON. RGBW Indicator will indicate mains
presence with Green.
Switched| ON| OFF| OFF| Main LEDs is OFF. RGBW Indicator will indicate mains
presence with
Green. Any induced voltage on the Control wire should be no greater
than 10V when the Control is OFF.
Switched| OFF| ON or OFF| ON-EM| Main LEDs is OFF. EM LEDs is ON (power
supplied from battery).
RGBW Indicator will be OFF*.
Switched*| ON| Digital ON| ON| Main LEDs is ON. RGBW Indicator will indicate
mains presence with Green.
Switched| ON| Digital OFF| OFF| Main LEDs is OFF. RGBW Indicator will
indicate mains presence with Green.
Switched| OFF| Digital ON or OFF| ON-EM| Main LEDs is OFF. EM LEDs is ON
(power supplied from battery).
RGBW Indicator will be OFF.
Unless switched digitally.
Via BitCortex application, gateway required. The Control terminal must be
linked to the Active terminal via bridge link.
RGBW Indicator defaults to show Mains power presence (Green) unless
triggered.
Commissioning / Put In-Service
The commissioning of the DLK3 involves the following:
- Verify that the DLK3 is installed and wired appropriately as per the Installation Instructions.
- Ensure the Battery Isolation Switch is in the ‘ON’ position in accordance with Step 4 of the Installation Instructions.
- Supply mains power continuously for at least 16 hours.
- Conduct the Commissioning EM Operation test by disconnecting the mains power. The unit is deemed to have passed the test if light is produced for a minimum of 120 minutes.
The unit is considered to be In-Service once it is provided a minimum of 16
hours of uninterrupted mains supply following the Commissioning EM Operation
test.
Testing (In-Service)
There are 2 ways to test the DLK3 for EM Operation as outlined below.
NOTE: The unit needs to complete the Commissioning EM Operation test
prior to undergoing In-Service EM testing.
-
Test Button
a. Press the Test Button to interrupt mains supply to the DLK3.
b. The DLK3 is deemed to have passed the test if the RGBW Indicator stops illuminating green and Emergency Light is produced.
c. Release the Test Button to allow mains supply to energize the DLK3 and revert its operating state appropriate for the wiring configuration. -
In-Service EM Test
NOTE: The DLK3 should have a minimum of 16 hours of uninterrupted mains supply prior to the In-Service EM Test.
a. Disconnect power to the DLK3, the RGBW Indicator will stop illuminating green and the unit will provide Emergency Light.
b. The DLK3 is deemed to have passed the test if it produces light for 90 minutes.
c. Reconnect power to the DLK3. It will revert to its operating state appropriate for the wiring configuration.
Power Interruption
The DLK3 is designed to provide reliable Emergency Light in the event of a
power outage. Users can expect a minimum of 90 minutes of Emergency Light
during In-Service operation when power is supplied for a minimum of 16 hours
prior to the event. If an area needs to be accessed prior to the DLK3
completing the 16-hour charge period, the Coolon App can be used to identify
the DLK3 unit in the area and determine its calculated Emergency Light runtime
– see “Predicted Duration” in the app. This allows the operator to determine
if the emergency light output duration will be sufficient for their task in the
event of a power interruption/outage. If the DLK3 is expected to be
deenergised for more than 7 days, the Battery Isolation Switch must be set to
the ‘OFF’ position. This will prevent the DLK3 battery from depleting below
the recoverable level due to the prolonged power interruption. Failing to do
so may result in irreparable damage to the battery, which is not covered under
warranty.
Storage / Removal from In-Service
The Battery Isolation Switch must be set to the ‘OFF’ position if the DLK3 is
to be removed from In-Service operation for storage, transportation or any
other reason. Please ensure the DLK3 has had a minimum of 16 hours
uninterrupted mains power supplied prior to this. Take note of the date the
DLK3 is taken out of service and observe the requirements set in the Storage
Shelf Life section.
Storage Shelf Life
The DLK3 has a storage shelf life of up to 12 months when stored at a
temperature of 20±5°C after dispatch from the factory. Storage temperatures
outside of 20±5°C but within the specified unit operating temperature limit
will decrease the product shelf life to 6 months. The DLK3 should be put
through a Battery Charge Cycle if it cannot be commissioned within the
prescribed shelf life. Following the Battery Charge Cycle, the DLK3 can be
stored for a further period appropriate to the storage temperature. Failure to
comply with the above requirements may result in irreparable damage to the
battery since such a state would permanently alter the battery chemistry. This
type of failure is excluded from the warranty.
Battery Charge Cycle
-
Connect A (Active), N (Neutral) and E (Earth) terminals of the unit to mains voltage. Control line remains unconnected.
-
Turn the battery isolation switch to the ON (connected) position.
-
Energize the unit and allow to charge for 16 hours. RGBW Indicator should be observed to be green.
Flashing green RGBW Indicator means battery disconnected or a battery fault. -
De-energize the unit and disconnect mains supply.
-
Turn the battery isolation switch to the OFF (disconnected) position.
-
Record the date of the Battery Charge Cycle.
-
Pack the unit for storage or proceed to the next operation / installation step.
Battery Replacement Procedure
The DLK3 emergency LED luminaire is designed to operate providing specified
emergency operating time using the in-built battery for the life of the
product. As a result, there is no field battery replacement capability.
Extended Functionality
As part of the Brilliant Connected Lights (BCL) series, the DLK3 supports many
extended functionalities to improve site visibility, situational awareness,
and general productivity. The key functions below can be configured and
controlled via the BitCortex webapp when a gateway is present:
-
Luminaire
- Identification (luminaire will flash)
- Meta data capture (assigned location, alias etc)
- Time from factory dispatch
- Alarms/alerts
- Historical data
-
Main LEDs
- Dynamic colour switching (Amber or White)
- Dim level
- ON/OFF
- Behaviour on sensor input*
-
EM LEDs
- Battery health
- Predicted duration
- Power outage history
- Emergency operation logging for AS2293 test and reporting
-
RGBW Indicator LEDs
- Colour
- Frequency
- Trigger
NOTE:** The DLK3 must be within 30 meters (line of sight) of either a gateway or from a BCL chain of luminaires which have connection to the gateway.
-
Additionally, the DLK3 together with other BCL enabled luminaires mesh together autonomously to form a IoT backbone* for:
- Asset Tracking & Monitoring
- Personnel tracking
- Machine condition monitoring
- Electronic interface
*Additional wireless IoT devices purchased separately.
RGBW Indicator defaults to show Mains power presence (Green) unless
triggered.
Troubleshooting
** The RGBW Indicator is flashing green
Flashing green RGBW Indicator means battery disconnected (Battery Isolation
Switch is in the OFF position) or a battery fault.
The unit does not turn off when the Switched Active / Control line is de-
energized
This may be one of two common reasons, either
a. The induced voltage at the Control terminal is sufficiently high to signal
the unit that the switch is still on. Check the voltage at the Control
terminal or the Switched Active line to ensure it is below 10V.
b. The Constant Active and Switched Active lines are wired into wrong
terminals. Having a Switched Active line connected to the Active terminal will
give the impression that the DLK3 is operating correctly, however, when the
Switched Active line is deenergized, the unit will interpret that action as a
power loss and will start to provide Emergency Light. An inspection of the
wiring would be able to identify if this is the case, alternatively, if the
unit does switch off up to 2 hours after the line is deenergized, this would
be a clear indicator of incorrect wiring. Under normal working “Switched”
conditions, when the Switched Active line is deenergized, the DLK3 will stop
producing light and the RGBW Indicator will be green (unless triggered)
indicating the presence of mains at its Active terminal.
A
web based platform to manage and control smart wireless devices.
Accessible anywhere through an internet connected browser.
IMPORTANT
Primary use: conveyor light for commercial and industrial applications. The
light source of this luminaire is not replaceable, when the light source
reaches its end of life the whole luminaire shall be replaced.
- Read through this manual before installation
- Handle the product with care
- The product must be grounded
- The product must be installed by a suitably qualified person
- Do not stare at operating lamp, may be harmful to the eyes
- Turn OFF the power before installation and maintenance
- Make sure the product is securely installed
- The housing might become hot after operation
- Keep optical face clean
As a matter of continual improvement, the requirements and recommendations in
our manuals evolve to reflect new industry requirements and the latest feedback
from the field.
The Coolon team is working hard to ensure optimal product operation and the
safety of all users, please check our website periodically to ensure you are
up to date with the latest information.
Product must be installed by a suitably qualified person. All documentation is
subject to change without notice.
www.coolon.com.au
support@coolon.com.au
aus. 1300 287 533
intl. +613 8681 3633
Documents / Resources
|
COOLON DLK3 Industrial LED
Luminaire
[pdf] Instruction Manual
DLK3 Industrial LED Luminaire, DLK3, Industrial LED Luminaire, LED Luminaire,
Luminaire
---|---