MEAN WELL DR-RDN20 20A Power Supply Redundancy Module Instructions
- June 12, 2024
- MEAN WELL
Table of Contents
MEAN WELL DR-RDN20 20A Power Supply Redundancy Module
Product Information
-
Product Name: 20A Power Supply Redundancy Module
-
Model: DR-RDN20
-
Specifications:
-
Reverse Voltage (max.): 30V
-
Output Current (max.): 20A
-
Voltage Drop: 0.6V
-
LED Indicators: Two green LEDs indicating each input is OK or fail
-
Input Voltage Range: 21 ~ 28V
-
Number of Inputs: Two
-
Input Current (max.): 20A per input
-
Function Input Voltage Alarm
-
Relay Contact Rating (max.): 30VDC, 1A
-
Working Temperature: -40°C ~ +70°C
-
Working Humidity: 20 ~ 90% RH non-condensing
-
Storage Temperature, Humidity: -40°C ~ +85°C, 10 ~ 95% RH
-
Vibration: 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each
along X, Y, and Z axes; Mounting: Compliance to IEC60068-2-6 -
Safety Standards: UL508, AS/NZS 62368.1, EAC TP TC 00 approved
-
Safety & Withstand Voltage EMC: Terminal-Chassis: 0.5KVAC, Relay Contacts-Terminal: 0.5KVAC
-
Isolation Resistance: Terminal-Chassis: >100M Ohms / 500VDC / 25/ 70% RH
-
EMC Emission: Compliance to EN55032 (CISPR32) Class B,EN61000-3-2,-3, EAC TP TC 020
-
EMC Immunity: Compliance to EN61000-4-2,3,4,5,6,8,11, heavy industry level, EAC TP TC 020
-
MTBF: 2315.6K hrs min. Telcordia SR-332 (Bellcore); 996.9K hrs min. MIL-HDBK-217F (25)
-
Dimensions: 55.5125.2100mm (WHD)
-
Packing: 0.5Kg; 20pcs/11Kg/1.49CUFT
-
Product Usage Instructions
The 20A Power Supply Redundancy Module can be used in various
configurations to enhance the reliability of the power supply system. Here are
some typical application notes:
Redundancy Using 1 more PSU as the redundant unit
In this configuration, you can connect an additional power supply unit (PSU)
as a redundant unit to the DR-RDN20 module. The DR-RDN20 module will monitor
the inputs from both PSUs and ensure
continuous power supply in case one PSU fails.
Redundancy: Using more PSUs as redundant units to increase reliability In
this configuration, you can connect multiple PSUs as redundant units to the
DR-RDN20 module. This setup increases the
reliability of the power supply system by providing backup power from multiple
sources.
Single Use: Connecting only one PSU to one DR-RDN20 to reduce stress and increase reliability In this configuration, you can connect a single PSU to one DR-RDN20 module. This setup reduces the stress on the diodes and improves the overall reliability of the power supply system. Please refer to the product manual for detailed instructions on connecting and configuring the 20A Power Supply Redundancy Module in your specific application.
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspr
Features
- Suitable for redundant operation of 24V system
- Installed on DIN Rail TS35 / 7.5 or 15
- Relay contact signal output and LED indicator for input failure alarm
- Cooling by free air convection
- 3 years warranty
SPECIFICATION
MODEL | DR-RDN20 |
---|
OUTPUT
| REVERSE VOLTAGE (max.)| 30V
OUTPUT CURRENT (max.)| 20A
VOLTAGE DROP| 0.6V
LED INDICATORS| Two green LEDs indicating each input is “OK or fail”
INPUT
| INPUT VOLTAGE RANGE| 21 ~ 28V
NUMBER OF INPUTS| Two
INPUT CURRENT (max.)| 20A per input
FUNCTION| INPUT VOLTAGE ALARM| When input is > 20V(±5%) or <
30V(±5%) relay contacts
RELAY CONTACT RATING (max.)| 30VDC, 1A
ENVIRONMENT
| WORKING TEMP.| -40 ~ +70℃
WORKING HUMIDITY| 20 ~ 90% RH non condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X,
Y, Z axes ; Mouning: Compliance to IEC60068-2-6
SAFETY & EMC
(Note 2)
| SAFETY STANDARDS| UL508, AS/NZS 62368.1, EAC TP TC 004 approved
WITHSTAND VOLTAGE| Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal
:0.5KVAC
ISOLATION RESISTANCE| Terminal-Chassis :>100M Ohms / 500VDC / 25℃/ 70%
RH
EMC EMISSION| Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3,
EAC TP TC 020
EMC IMMUNITY| Compliance to EN61000-4-2,3,4,5,6,8,11, heavy industry
level, EAC TP TC 020
OTHERS
| MTBF| 2315.6K hrs min. Telcordia SR-332 (Bellcore) ; 996.9K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 55.5125.2100mm (WHD)
PACKING| 0.5Kg; 20pcs/11Kg/1.49CUFT
NOTE|
-
All parameters NOT specially mentioned are measured at 24VDC input, rated load, and 25 °C of ambient temperature.
-
The power supply is considered a component that will be installed into the final equipment. All the MC tests are been executed by mounting the unit on a 360mm 360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets MC directives. For guidance on how to
To perform these MC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com) -
The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitude higher than 2000m(6500ft Product Liability Disclaimer: For detailed information. Please refer to www.meanwell.com/serviceDisclaimer.aspx
Typical Application Notes
- Redundancy Using 1 more PSil as the redundant unit
- Redundancy: Using more PSUs as the redundant units to increase the reliability
- Single Use: Connecting only one PSU to one DR-RDN20 to reduce the stress of the diodes and hence increase the reliability
Mechanical Specification
Block Diagram
Derating Curve
File Name: DR-RDN20-SPEC 2022-02-28
Read User Manual Online (PDF format)