BEGA 77815 In-Ground Luminaire Instruction Manual

June 12, 2024
BEGA

BEGA 77815 In-Ground Luminaire Instruction Manual

BEGA

Bodeneinbauleuchte

Instructions for use

Application

Recessed location luminaire for installation in cut-outs in floors.
Drive-over luminaire for vehicles with pneumatic tyres.

Please note:

Luminaire must not be used for installation in road lanes, where the fixture is exposed to a horizontal strain due to braking, acceleration and change of direction.
For walk-through public areas, we recommend skid-blocking glass  see accessories.


Product description

Luminaire made of stainless steel Steel grade no. 1.4301
Safety glass, white Silicone gasket
Required recessed opening ø 300 mm
Minimum material thickness 40 mm
Fixing is achieved by using four wedge-shaped clamping elements
1,8 m water-resistant connecting cable 07RN8-F 3 G 1@ with implemented water stopper and 1.2 m PVC cable conduit LED power supply unit 220-240 V x 0/50-60 Hz DC 170-280 V
BEGA Thermal Switch®
Temporary thermal shutdown to protect temperature-sensitive components Safety class I
Protection class IP 68 10 m
Dust-tight and water pressure tight
Maximum submersion depth 10 m
Not suitable for permanent operation under water
Pressure load 2,000 kg (~20 kN)
Impact strength IK10 Protection against mechanical impacts < 20 joule
Maximum surface temperature 20 °C (measured according to EN 60598 of ta 15 °C) r – Safety mark c – Conformity markWeight: 5.0 kg
This product contains light sources of energy efficiency classes C, D

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.

To achieve an additional protection against

e. g. transients, etc. we recommend separate overvoltage protection components.

You can find them on our website at

www.bega.com.


Safety

The installation and operation of this luminaire are subject to national safety regulations.

Installation and commissioning may only be

carried out by a qualified electrician.

We recommend fuse protection via a residual current circuit breaker to be provided by the customer.

The manufacturer accepts no liability for damage caused by improper use or installation.

If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Lamp

Module connected wattage                          7.3 W
Luminaire connected wattage                     9.2 W
Rated temperature                                         ta = 25 °C
Ambient temperature                                    ta max = 45 °C
When installed in heat-insulating
material                                                          ta max = 40 °C
77 815 K27
Module designation                                     LED-0381/927
Colour temperature                                   2700 K

Colour rendering index                            CRI > 90
Module luminous flux                              1245 lm
Luminaire luminous flux                          593 lm Luminaire luminous efficiency         64,5 lm / W 77 815 K3
Module designation                                   LED-0381/930
Colour temperature                                   3000 K
Colour rendering index                            CRI > 90
Module luminous flux                               1260 lm
Luminaire luminous flux                            600 lm Luminaire luminous efficiency         65,2 lm / W77 815 K4
Module designation                                    LED-0381/940
Colour temperature                                   4000 K
Colour rendering index                            CRI > 90
Module luminous flux                             1335 lm
Luminaire luminous flux                         635 lm Luminaire luminous efficiency            69 lm / W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.

Open the floodlight: Undo counter sunk

screws.

Lift stainless steel trim ring and glass with gasket.

Fixing of the luminaire is achieved by using four

wedge-shaped clamping elements.

For this purpose a recessed opening of ø 300_mm with a minimum depth of 120_mm is necessary.

The upper edge of the recessed opening must be firm on a thickness of 40 mm in order to accept the clamping forces of the luminaire.

The electrical connection at the luminaire connecting cable must be carried out on site in a

n according protection class and safety class. We recommend to use a distribution box

70 730 or 71 053.

Place luminaire into the recessed opening and fix it by tightening the 4_screws (torx drive T25) evenly.

Make sure that luminaire housing is properly

fixed in the recessed opening.

Place glass with gasket with stepped side

upturned into the floodlight housing.

Make sure that gasket is positioned correctly. Place cover ring onto the glass step and tighten screws crosswise.

Torque = 5 Nm.

Cleaning · Maintenance

After installation, the luminaire should first be cleaned. Building dust, residues from contact adhesives, paint splashes and rust film must be completely removed. Never use high pressure cleaners and cleaning implements made

of normal steel, steel brushes or steel wool because they cause extraneous rust to form. When using stainless steel cleaners, please read the directions carefully.

Cleaning agents containing hydrochloric acid and chlorides should never be used.

We recommend cleaning the luminaires regularly.


Please note:

Do not remove the desiccant bag from the luminaire housing.

It is needed to remove residual moisture.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire.

The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.

Disconnect the electrical installation.

The LED module of this luminaire may only be exchanged by the manufacturer or by one of his assigned service technicians or a comparable qualified person.

Clean dirt and deposits from key openings of screw head.

Do not use a high pressure cleaner. Open the luminaire and clean.

Use only solvent-free cleaners.

The luminaire housing must be completely clean and absolutely dry.

Replace LED module.

Please follow the installation instructions for the LED module.

Check all screws and threads thoroughly and grease them.

Check the gasket and replace, if necessary. A broken glass must be replaced.

Insert glass with gasket with stepped side turned upward into the luminaire housing. Make sure that the glass is correctly positioned in the gasket bed.

Place trim ring onto glass step and tighten screws crosswise.

Torque = 5 Nm.

Accessories

140258R Skid-blocking glass

BEGA skid-blocking glass with the highest rating R 13 according to DIN 51130 can be used without restriction for all public areas. Abrasion resistance according to

EN ISO 10545-7 Class 3

Distribution box for installation in soil

70 730 Distribution box with 7 cable entries Connection terminals 5 x 4@

71 053 Distribution box with 10 cable entries Connection terminals 6 x 16@

A separate instructions for use can be provided

upon request.

Spares __

Spare glass                                                14 000 258
Spare glass skid-blocking                       14 000 258 R
LED power supply unit                           DEV-0141/250
LED module 2700 K                               LED-0381/927
LED module 3000 K                               LED-0381/930
LED module 4000 K                               LED-0381/940
Gasket glass                                               83 001 680

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals