Lutron RMJS-16R-DV-B PowPak Relay Module Installation Guide

June 12, 2024
Lutron

Lutron RMJS-16R-DV-B PowPak Relay Module

Lutron RMJS-16R-DV-B PowPak Relay Module-product

For set-up, programming, and troubleshooting with a ViveTM system, please refer to the installation instructions included with the ViveTM hub or at www.lutron.com

Note for Replacement: RMxS and URMxS – the “S” model can replace the non-” S” model

Important Notes:

Please read before installing.

  • For installation by a qualified electrician in accordance with all local and national electrical codes. • Note: Use copper conductors only.
  • Check to see that the device type and rating are suitable for the application.
  • DO NOT install if the product has any visible damage.
  • If moisture or condensation is evident, allow the product to dry completely before installation.
  • Operate between 32 °F (0 °C) and 131 °F (55 °C).
  • 0% to 90% humidity, non-condensing.
  • For indoor use only.

WARNING: Shock Hazard. May result in serious injury or death. Turn off the power at the circuit breaker before installing the unit.

All Wireless Transmitters must be installed within 30 ft (9 m) of the PowPak® Relay Module.

FCC / IC Information

This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:

(1) This device may not cause interference, and
(2) this device must accept any interference, including interference that may cause undesired operation.

Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s authority to operate this equipment.

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and the receiver.
  • Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.

Required Components

For each system ensure you have:

  • At least one PowPak® Relay Module.
    (Occupancy-Status CCO Option Shown)Lutron RMJS-16R-DV-B PowPak Relay Module-
fig-1 \(2\)PowPak® Relay Module

  • At least one Wireless Transmitter.Lutron RMJS-16R-DV-B PowPak Relay Module-fig-1 \(3\) Radio Powr SavrTM Occupancy Sensor (10 maximum) Pico® Remote Control (10 maximum) Radio Powr SavrTM Daylight Sensor (1 maximum)

Start Here
  • Install PowPakR Relay Module
    When installing a PowPakR Relay Module, use the supplied conduit nut and wire the module as shown.Lutron RMJS-16R-DV-B PowPak Relay Module-fig-1
\(6\)

    • Suggested Installation Location: Install in center of room. This ensures proper RF coverage of area. If installing unit inside a junction box please see Application Note #423.
    • For more information: www.lutron.com/powpakrelay

CCO operation affected only by associated occupancy or vacancy sensors.

  • Room Occupied: NO = Close NC = Open
  • Room Unoccupied: NO = Open NC = Close

Note: When wiring a CCO model to 3rd-party systems, use 20 AWG to 16 AWG (0.5 mm2 to 1.5 mm2) solid or stranded wire

  • Associate Wireless Transmitters to PowPakR 20 A Relay Module
    Before beginning this step, make sure that there are no other PowPak® modules being set up within the same building. It is possible that Wireless Transmitters from other systems can be incorrectly associated to this system.

    • Hold the Relay Toggle button on the PowPak® Relay Module for 6 seconds to enter association mode. Note: The load will flash once after each step to confirm successful completion.
    • Hold the indicated button on a Wireless Transmitter for 6 seconds to associate the device. Repeat for any additional Wireless Transmitters. Lutron RMJS-16R-DV-B PowPak Relay Module-08If no g button, hold “Lights Off” button.
    • Hold the Relay Toggle button on the PowPak® Relay Module for 6 seconds to save association(s).
  • Permanently Install Wireless Transmitters
    Note: Please consult individual component installation guides for information.Lutron RMJS-16R-DV-B PowPak Relay Module-fig-1
\(9\)

  • Daylight Sensor setup
    Calibration

    • Turn lights in room on using the Relay Toggle button on the PowPak® Relay Module or an associated Pico®.
    • Press & hold “Cal.” on the associated Daylight Sensor for 6 seconds.
    • Exit room for 5 minutes to allow calibration to be completed.
      Note: When calibration has completed, all lights will flash and the system will begin daylighting.Lutron RMJS-16R-DV-B PowPak Relay Module-fig-1
\(10\)
  • Tuning (Optional)
    If it is desired to have multiple zones of lights turn on at different daylight levels (using multiple Relay Modules with one Daylight Sensor) follow the Tuning procedure described in the Daylight Sensor (LRF2-DCRB) installation instructions. Use the Relay Toggle button in place of the Dimmer/Switch tap button referenced in the document.

Limited Warranty

(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)

Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.

This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. This warranty does not cover the cost of installtion, removal or reinstallation, or damage resulting from misuse, abuse, or damage from improper wiring or installation. This warranty does not cover incidental or consequential damages.

LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.

This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above limitations may not apply to you.

Lutron, Energi TriPak, Pico, PowPak and Softswitch are registered trademarks and Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc. ©2012-2015 Lutron Electronics Co., Inc.

CCO Information

  • Some PowPak® Relay Modules include a dry contact closure output that provides occupancy status to 3rd-party equipment such as building management systems, HVAC, and VAV controllers.
  • CCO provides both normally open (NO) and normally closed (NC) maintained-type outputs.
  • CCO rated to switch resistive loads at voltages up to 24 V only. To properly control inductive load types such as relays, solenoids, or motors, refer to Application Note #434.Lutron RMJS-16R-DV-B PowPak Relay Module-fig-1 \(11\)

Unaffected Mode

Unaffected Mode allows a system with an Occupancy Sensor associated to multiple Relay Modules to be set up such that only selected loads turn on automatically. Other loads will require a manual turn-on with a PicoR Remote Control. All loads will turn off automatically when the room is vacated.

  • On a Relay Module, press and hold both the Relay Toggle and Advanced Operations (“ADV”) buttons for 6 seconds until the LED begins flashing quickly.
  • On the associated Occupancy Sensor, press and hold the “Test” button* for 6 seconds until the lens flashes.
  • Unaffected mode will be exited automatically. This Relay Module will now be unaffected by occupancy commands. Repeat procedure for any additional devices.

If no “Test” button, hold “Lights On” button.

Note: The CCO cannot be made unaffected.

Reset Factory Defaults

Note: In some instances it may be necessary to reset the PowPak® Relay Module back to factory default settings.

  • Triple-tap the “CNTRL” button on the Relay Module and hold until the LED begins to flash slowly.
  • Within 3 seconds of flashing, release and triple-tap the button again and the LED will flash rapidly indicating that the unit has been reset to factory defaults.

Note: Any associations or programming previously set up with the unit will be lost and will need to be re-programmed.

Troubleshooting

Load does not respond to Wireless Transmitter(s)

  • Ensure breaker to the PowPak® Relay Module is on.
  • Ensure the load has been properly wired to the PowPak® Relay Module.
  • Ensure Wireless Transmitter is properly associated to PowPak® Relay Module.
  • Ensure Wireless Transmitter’s battery is installed correctly.

Wireless Transmitter(s) cannot be associated to PowPak® Relay Module

  • The maximum number of Wireless Transmitters have been associated to the PowPak® Relay Module. To remove a previously set up Wireless Transmitter, tap the button used for association on the Wireless Transmitter three times, on the third tap hold for three seconds and then tap three more times.

www.lutron.com

Need Help? www.lutron.com or call the Lutron Technical Support Center, at 1.800.523.9466

FREQUENTLY ASKED QUESTIONS

What is the Lutron RMJS-16R-DV-B PowPak Relay Module?

The Lutron RMJS-16R-DV-B PowPak Relay Module is a wireless device designed to control loads, such as lighting or fans, in commercial and residential settings.

What is the purpose of the PowPak Relay Module?

The PowPak Relay Module is used to switch or control electrical loads, enabling remote control and automation through a Lutron control system.

Is the RMJS-16R-DV-B a wireless or wired device?

The Lutron RMJS-16R-DV-B is a wireless device that communicates using Lutron's proprietary wireless communication protocol.

What type of loads can the RMJS-16R-DV-B control?

The PowPak Relay Module can control a variety of loads, including lighting fixtures, fans, motors, and other electrical devices.

Can the RMJS-16R-DV-B be integrated into a larger Lutron lighting control system?

Yes, the RMJS-16R-DV-B is designed to be integrated into Lutron lighting control systems for centralized control and automation.

How does the RMJS-16R-DV-B connect to other devices in the Lutron system?

The PowPak Relay Module communicates wirelessly with other devices in the Lutron system through Lutron's Clear Connect RF technology.

What is the input voltage range for the RMJS-16R-DV-B?

The RMJS-16R-DV-B is designed to operate with an input voltage of 120-277 V~.

Does the RMJS-16R-DV-B support dimming functionality?

No, the RMJS-16R-DV-B is a relay module designed for on/off control of loads. It doesn't support dimming capabilities.

Can the RMJS-16R-DV-B be used for both indoor and outdoor applications?

The RMJS-16R-DV-B is typically intended for indoor applications and is not designed for direct exposure to outdoor elements.

How many relay outputs does the RMJS-16R-DV-B have?

The Lutron RMJS-16R-DV-B has one relay output for controlling a single load.

Is the RMJS-16R-DV-B compatible with Lutron's wireless Pico remote controls?

Yes, the PowPak Relay Module is compatible with Lutron Pico remote controls, allowing wireless remote operation.

Can the RMJS-16R-DV-B be programmed for scheduled events or automation scenes?

Yes, the PowPak Relay Module can be integrated into Lutron automation systems to create scheduled events and automation scenes.

What type of load rating does the RMJS-16R-DV-B support?

The RMJS-16R-DV-B typically has a load rating of up to 16A for most loads.

Does the RMJS-16R-DV-B require a neutral wire connection?

Yes, the PowPak Relay Module typically requires a neutral wire connection for proper operation.

DOWNLOAD THE PDF LINK:Lutron RMJS-16R-DV-B PowPak Relay Module Installation Guide

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals