BEGA 50252.4 Ceiling Downlight Instruction Manual

June 13, 2024
BEGA

BEGA logo 50 252.4
Technical amendments reserved
Recessed ceiling downlight for indoor use

50252.4 Ceiling Downlight

BEGA 50252.4 Ceiling Downlight Instructions for use

Application

Recessed ceiling luminaire · indoor luminaire with aluminium housing for shielded light deflected downwards.
Luminaire for connection to external LED power supply unit.

Product description

Recessed LED ceiling luminaire »STUDIO LINE«
made of die-cast aluminium – without power supply unit
Aluminium housing shield, Finish Colour velvet black inside hue matt brass
Light-diffusing silicone lens
Reflector of anodised pure aluminium
Fixing is achieved by using 2 adjustable wedge-shaped claws
1 connecting cable with strain relief and plug connector system for BEGA power supply unit, on/off or DALI
Safety class III
**** – Conformity mark
Weight: 0.4 kg
This product contains light sources of energy efficiency class(es) E

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Lamp

Module connected wattage 12.3 W
Luminaire connected wattage 14.3 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 40 °C

50 252.4 K3

Module designation LED-0423/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 1640 lm
Luminaire luminous flux * 744 lm
Luminaire luminous efficiency * 52 lm / W
  • preliminary data
    Lighting technology
    Half beam angle 48°

Installation

  Luminaire housing must not be installed in heat-insulating material.
A separate power supply unit is required to operate the luminaire – see accessories.
The recessed opening will be covered by the frame of the luminaire.
Fixing of the luminaire is achieved by using 2 adjustable wedge-shaped claws.
LEDs are high-quality electronic components!
Please avoid touching them directly during installation or relamping.

Installation into false ceilings

A recessed opening of ø 68 mm is necessary to accept the luminaire.
Free space depth min. 100 mm (see sketch).
Luminaire and external LED-power supply unit must not be installed in heatinsulating material.
The lateral distance between recessed luminaire and standard combustible building parts must be at least 50 mm.
The claws catch the panel from the reverse side. If minimum thickness of the panel is less than 3 mm it must be reinforced from the reverse side. Maximum thickness of the panel must be no more than 20 mm.
For connection to external LED-power supply unit – accessory 13 144 or 13 169 – the luminaire is equipped with a 2-pin connector.
Note operating instructions of the LED-power supply units.
Push external LED power supply unit and luminaire into the ceiling cut-out.
Hand-tight screws of claw fasteners evenly.
Center reflector onto the enclosed housing shield.
Mount housing shield with reflector onto luminaire frame (magnetic) (see sketch).BEGA 50252.4 Ceiling Downlight - Figure 1

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt.

Replacement of the LED module

The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system.
Pull housing shield with mounted reflector from luminaire frame.
Please follow the installation instructions for the LED module.
Mount housing shield with reflector onto luminaire frame (magnetic).

Accessories

Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain relief and plug connector system.
13 144 Power supply unit on/off
13 169 Power supply unit DALI
The power supply units are only suitable for the operation of one LED luminaire.
For the accessories a separate instructions for use can be provided upon request.

Spares

Shield black · matt brass 42 000 202 .3M 9
LED module 3000 K LED-0423/930
Reflector 76 001 317

BEGA Gantenbrink-Leuchten KG · Postfach 31 60
· 58689 Menden
· info@bega.com
· www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals