BEGA 51 213.2 LED Ceiling Luminaire Downlight for Indoor Use Instruction Manual

June 12, 2024
BEGA

BEGA 51 213.2 LED Ceiling Luminaire Downlight for Indoor Use

Product Information

The product is a luminaire, which is a lighting fixture. It is designed to provide illumination in various settings. The installation and operation of the luminaire must comply with national safety regulations. The manufacturer recommends that only qualified electricians carry out the installation and commissioning to ensure safety. The luminaire is protected against overvoltage in accordance with DIN EN 61547, but additional overvoltage protection components are recommended for enhanced protection against transients. The product comes with different LED modules that have specific characteristics such as colour temperature, colour rendering index, luminous flux, and luminous efficiency.

Product Usage Instructions

  1. Safety: Ensure that the installation and  operation of the luminaire comply with national safety regulations. Only qualified electricians should carry out the installation andcommissioning. The manufacturer does not accept liability for
    damage caused by improper use or installation. Any modifications to the luminaire should be done by a qualified person responsible for those modifications.

  2. Overvoltage Protection: Although the luminaire is already protected against overvoltage, it is recommended to use separate overvoltage protection components for additional protection. These components can be found on the manufacturer’s website.

  3. Installation: Avoid touching the light output opening of the LED directly during installation or relamping. To ensure a secure connection, position the luminaire housing precisely in relation to the mounting plate. Align the vertical bar inside the housing with the mounting hole on the long bar of the mounting plate. Press the housing firmly against the plate and turn it clockwise until it stops.

  4. Open Luminaire: Unscrew the glass from the luminaire housing by turning it counter-clockwise. To prevent the luminaire from turning on the mounting plate, hold the housing in place with one hand.

  5. Replacement of LED Module: The designation of the LED module is noted on a label inside the luminaire. Replacement modules from BEGA have the same light colour and lightoutput as the original modules. Qualified persons can replace the module using standard tools. Disconnect the system and open the  luminaire following the installation instructions for the LED module. Replace any defective glass and close the luminaire.

Dimensions

Instructions for use

Application
Ceiling luminaire downlight · indoor luminaire with symmetrical wide beam light distribution.

Product description

  • Aluminium alloy housing,  finish Stainless steel
  • Crystal glass, partially satin matt, with screw neck
  • Light-diffusing silicone lens
  • Reflector made of pure anodised aluminium
  • 2 mounting holes ø 4.5 mm
  • Distance apart 153 mm
  • Connecting terminals 2.5@
  • Earth conductor connection
  • LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DC 176-276 V
  • During DC operation the LED power is reduced to 15 %
  • DALI-controllable
  • Number of DALI addresses: 1
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire

Safety class I

  • Impact strength IK06
  • Protection against mechanical
  • impacts < 1 joule
  • CE  – Conformity mark
  • Weight: 3.1 kg
  • This product contains light sources of energy efficiency class(es) E

Safety

  • The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Lighting technology

  • Half beam angle 49°

Lamp

  • Module connected wattage 30.3 W
  • Luminaire connected wattage 35.3 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 35 °C

51 213.2 K27

  • Module designation LED-0785/927
  • Colour temperature 2700 K
  • Colour rendering index CRI > 90
  • Module luminous flux 4275 lm
  • Luminaire luminous flux 2927 lm
  • Luminaire luminous efficiency 82,9 lm / W

51 213.2 K3

  • Module designation LED-0785/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 4450 lm
  • Luminaire luminous flux 3047 lm
  • Luminaire luminous efficiency 86,3 lm / W

Installation

  • LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Remove mounting plate from the luminaire housing.
  • Unplug the earth conductor connection (plug contact).

Please note:

  • If the luminaire is to be mounted onto a metallic, electroconductive surface, it is mandatory to make sure that the mounting surface is connected conductive to the earth conductor of the luminaire!
  • Lead the power connecting cable through the mounting plate.
  • Fix the mounting plate with enclosed or any other suitable fixing material onto the mounting surface.
  • Establish the earth conductor connection on the earthing screw (1) of the mounting plate. Establish the earth conductor connection to the luminaire housing (plug contact).
  • Ensure the correct assignment of the connecting cable. Establish the mains connection on the brown (L) and blue (N) wires. The two connecting terminals marked DA, DA are provided for digital control purposes.
  • If these terminals are not assigned, the luminaire will work with full light output.

IMPORTANT:

  • To ensure secure connection, the luminaire housing must be positioned precisely in relation to the mounting plate.
  • Make sure that the vertical bar inside the luminaire housing is positioned precisely in the area of the mounting hole on the long bar of the mounting plate.
  • Press the luminaire housing firmly against the mounting plate and turn it clockwise firmly against the stop.

Open luminaire:

  • Unscrew glass from luminaire housing by turning it counter-clockwise.
  • To prevent the luminaire from turning on the mounting plate, hold the luminaire housing in place with one hand.

Cleaning · Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt.

Replacement of the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
  • Defective glass must be replaced.
  • Close the luminaire.

Spares

  • Spare glass 11 003 451 10M RG
  • LED power supply unit DEV-0144/600i
  • LED module 2700 K LED-0785/927
  • LED module 3000 K LED-0785/930
  • Reflector 76 001 786 M

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals