RANGER WS1CS 1 Inch Control Valve Instruction Manual
- June 12, 2024
- RANGER
Table of Contents
Water Specialist
1” Control Valve Series Model: WS1CS
1.25” Control Valve Series Model: WS1.25CS
Operation and Instruction Manual for OEM Only.
Please Note : This operation and instruction manual is for the training
of the OEM and for the OEM to use to train their customers. This document is
not to be used as the complete system manual.
FOR INFORMATION COMMON TO ALL 1” & 1.25” CONTROL VALVES REFER TO THE WS1 AND
WS1.25 DRAWINGS AND SERVICE MANUAL
Control Valve Function and Cycles of Operation
This glass filled Noryl1 (or equivalent) fully automatic control valve is
designed as the primary control center to direct and regulate all cycles of a
water softener or filter. When the WS1CS or WS1.25 control valve is
manufactured as a softener, the control valve can be ordered to perform
downflow or upflow regeneration. When the WS1CS or WS1.25CS control valve is
set up as a filter, the control valve can be set to perform downflow
regeneration or simply backwash. The control valve can be set to regenerate on
demand (consumption of a predetermined amount of water) and/or as a time clock
(passage of a particular number of days). The control valve can be set so that
a softener can meet the Water Quality Association (WQA) Standard S100 or
NSF/ANSI Standard 44
efficiency rating.
It is not recommended to change control valves from downflow to upflow brining
or vice versa in the field. The valve bodies for downflow and upflow are
unique to the regeneration type and and should not be interchanged. A mismatch
of valve body and regeneration piston will result in hard water bypass during
service.
The control valve is compatible with a variety of regenerants and resin
cleaners. The control valve is capable of routing the flow of water in the
necessary paths to regenerate or backwash water treatment systems. The
injector regulates the flow of brine or other regenerants. The control valve
regulates the flow rates for backwashing, rinsing, and the replenishing of
treated water into a regenerant tank, when applicable.
The control valve uses no traditional fasteners (e.g. screws); instead clips,
threaded caps and nuts and snap type latches are used. Caps and nuts only need
to be firmly hand tightened because radial seals are used. Tools required to
service the valve include one small blade screw driver, one large blade screw
driver, pliers and a pair of hands. A plastic wrench is available which
eliminates the need for screwdrivers and pliers. Disassembly for servicing
takes much less time than comparable products currently on the market.
Control valve installation is made easy because the distributor tube can be
cut ½” above to ½” below the top of tank thread. The distributor tube is held
in place by an o-ring seal and the control valve also has a bayonet lock
feature for upper distributor baskets.
The AC adapter power pack comes with a 15 foot power cord and is designed for
use with the control valve. The AC adapter power pack is for dry location use
only. The control valve remembers all settings for up to 8 hours if the power
goes out and the battery is not depleted. After 8 hours, the only item that
needs to be reset is the time of day; other values are permanently stored in
the nonvolatile memory. If a power loss lasts less than 8 hours and the time
flashes on and off, the time of day should be reset and the non rechargeable
battery should be replaced.
Table 1 shows the order of the cycles when the valve is set up as a softener.
The OEM has the option of having the regenerant refill after the rinse cycle
or have the regenerant prefill before regeneration. If the OEM chooses to have
the regenerant prefill before regeneration, the prefill starts two hours
before the regeneration time set. During the 2-hour period in which the brine
is being made, treated (softened) water is still available. For example:
regeneration time = 2:00 am, prefill option selected, downflow softener.
Fill occurs at 12:00 a.m., start of backwash cycle occurs at 2:00 a.m. Tables
2 and 3 show the length of the cycles when different program codes are
selected.
Table 1
Regeneration Cycles Softening
WS1CS & WS1.25CS
Downflow Regenerant Refill After Rinse
| WS1CS & WS1.25CS
Downflow Regenerant Prefill
| WS1CS & WS1.25CS
Upflow Regenerant Refill After Rinse
| WS1CS & WS1.25CS
Upflow Regenerant Prefill
---|---|---|---
1st Cycle:Backwash
2nd Cycle: Regenerate 3rd Cycle: Second
Backwash 4th Cycle: Rinse
5th Cycle: Fill/Dissolve 6th Cycle: Service| 1st Cycle: Fill
2nd Cycle: Service 3rd Cycle: Backwash
4th Cycle: Regenerate 5th Cycle: Second Backwash
6th Cycle: Rinse 7th Cycle: Service| 1st Cycle: Regenerate
2nd Cycle: Backwash 3rd Cycle: Rinse
4th Cycle: Fill/Dissolve 5th Cycle: Service| 1st Cycle: Fill
2nd Cycle: Service 3rd Cycle: Regenerate
4th Cycle: Backwash 5th Cycle: Rinse
6th Cycle: Service
*Second Backwash is optional
1 Noryl is a trademark of Sabic Innovative Plastics IP B.V. Company
Table 2
Downflow Softener Program Codes for WS1CS or WS1.25CS
Program Code| Main Piston| 1st Backwash| Brine/Slow Rinse| 2nd Backwash| Fast
Rinse
---|---|---|---|---|---
P1| Down Flow| 3| 40| 3| 3
P2| Down Flow| 3| 45| 3| 3
P3| Down Flow| 4| 45| 4| 3
P4| Down Flow| 4| 60| 4| 3
P5| Down Flow| 5| 60| 4| 4
P6| Down Flow| 5| 60| 5| 4
P7| Down Flow| 6| 45| 4| 3
P8| Down Flow| 6| 60| 5| 4
P9| Down Flow| 6| 60| 6| 5
P10| Down Flow| 7| 50| 5| 4
P11| Down Flow| 7| 60| 6| 6
P12| Down Flow| 7| 65| 7| 7
P13| Down Flow| 8| 45| 5| 4
P14| Down Flow| 8| 60| 6| 6
P15| Down Flow| 8| 60| 8| 8
P16| Down Flow| 8| 65| 8| 6
P17| Down Flow| 8| 65| 8| 7
P18| Down Flow| 8| 75| 8| 5
P19| Down Flow| 9| 50| 5| 5
P20| Down Flow| 9| 60| 5| 4
P21| Down Flow| 9| 65| 8| 5
P22| Down Flow| 10| 45| 4| 4
P23| Down Flow| 10| 60| 5| 4
P24| Down Flow| 10| 65| 8| 8
P25| Down Flow| 10| 65| 6| 5
P26| Down Flow| 10| 75| 7| 5
P27| Down Flow| 12| 45| 4| 4
P28| Down Flow| 12| 60| 6| 4
P29| Down Flow| 12| 60| 8| 8
P30| Down Flow| 12| 65| 6| 6
P31| Down Flow| 12| 65| 8| 8
P32| Down Flow| 12| 65| 12| 8
P33| Down Flow| 12| 75| 6| 6
P34| Down Flow| 14| 45| 5| 4
P35| Down Flow| 14| 60| 6| 5
P36| Down Flow| 14| 60| 8| 8
P37| Down Flow| 14| 65| 7| 6
P38| Down Flow| 14| 65| 8| 8
P39| Down Flow| 14| 65| 12| 8
P40| Down Flow| 14| 75| 8| 7
P41| Down Flow| 16| 60| 7| 5
P42| Down Flow| 16| 65| 8| 6
P43| Down Flow| 16| 65| 8| 8
P44| Down Flow| 16| 65| 12| 8
P45| Down Flow| 16| 75| 9| 7
P50| Down Flow| 6| 45| 3| 3
P51| Down Flow| 8| 60| 8| 4
P52| Down Flow| 8| 75| 10| 6
Table 4 shows the order of the cycles when the valve is set up as a filter. If
the control valve is set to regenerate for a filter, the OEM has the option of
having the regenerant refill after the rinse cycle or have the regenerant
prefill before regeneration. If the OEM chooses to have the regenerant prefill
before regeneration, the prefill starts two hours before the regeneration time
set. During the 2-hour period in which the regenerant is being made, treated
water is still available. For example: regeneration time = 2:00 am, prefill
option selected, downflow filter. Fill occurs at 12:00 a.m., start of backwash
cycle occurs at 2:00 a.m.
When the control valve is used as a nonregenerating filter, the OEM has the
option to specify one backwash or two backwashes. If two backwashes are
specified, two rinses occur. Tables 5 and 6 show the length of the cycles when
the valve is set up as a filter. When used as a nonregenerating filter, the
downflow piston must be installed, the regenerant piston removed, injector
plugs must be installed in both the DN and UP injector locations and the
refill elbow must be replaced with a refill port plug.
Table 3
Upflow Softener Program Codes for WS1CS or WS1.25CS
Program
Code
| Main
Piston
| 1 st Backwash| Brine/Slow Rinse| 2 nd
Backwash| Fast Rinse
---|---|---|---|---|---
P60| Upflow| N/A| 45| 6| 4
P61| Upflow| N/A| 45| 8| 6
P62| Upflow| N/A| 60| 10| 6
P63| Upflow| N/A| 60| 12| 8
P64| Upflow| N/A| 75| 10| 6
P65| Upflow| N/A| 75| 12| 8
Table 4
Regeneration Cycles Filtering for WS1CS or WS1.25CS
Downflow Regenerant Refill After Rinse| Downflow Regenerant Prefill| No
Regenerant
---|---|---
1st Cycle: Backwash
2nd Cycle: Regenerate 3rd Cycle: Second Backwash* 4th Cycle: Rinse
5th Cycle: Fill
6th Cycle: Service
| 1st Cycle: Fill
2nd Cycle: Service 3rd Cycle: Backwash
4th Cycle: Regenerate
5th Cycle: Second Backwash*
6th Cycle: Rinse 7th Cycle: Service
| 1st Cycle: Backwash
2nd Cycle: Rinse
3rd Cycle: Second Backwash*
4th Cycle: Second Rinse 5th Cycle: Service
*Second Backwash is optional in some Program Codes
Table 5
Regenerating Filter Program Codes for WS1CS or WS1.25CS
Program
Code
| Main Piston| 1 st Backwash| Brine/ Slow Rinse| 2
nd Backwash| Fast Rinse
---|---|---|---|---|---
P70| Downflow| 6| 20| 6| 6
P71| Downflow| 12| 10| N/A| 12
P72| Downflow| 4| 50| N/A| 4
P73| Downflow| 10| 50| N/A| 6
P74| Downflow| 12| 60| N/A| 10
P75| Downflow| 12| 75| N/A| 10
Table 6
Non-Regenerant Filter Program Codes for WS1CS or WS1.25CS
Program Code| Main Piston| 1st Backwash| 1st Fast Rinse| 2nd Backwash| 2nd
Fast Rinse
---|---|---|---|---|---
P80| Downflow| 8| 8| N/A| N/A
P81| Downflow| 12| 6| N/A| N/A
P82| Downflow| 14| 8| N/A| N/A
P83| Downflow| 14| 10| N/A| N/A
P84| Downflow| 16| 10| N/A| N/A
P85| Downflow| 18| 10| N/A| N/A
P86| Downflow| 20| 10| N/A| N/A
P90| Downflow| 8| 6| 10| 8
P91| Downflow| 12| 6| 12| 10
Note: For non-regenerant filters: 1) The regenerant piston is removed; 2)
injector plugs are installed in both the UP and DN holes under the injector
cap.
Table 7
DIR/Time Clock Options
DIR
| Time Clock| ****
Reserve Capacity
| ****
Softener
| Filter| Settings3
---|---|---|---|---|---
Regenerant| Backwash Only| Day Override| Gallon Capacity
Yes| | Automatically calculated| Yes| | | Off| Auto
Yes| | If desired enter a value less than estimated capacity| Yes| Yes| Yes|
Off| Any Number
Yes| Yes| Automatically calculated| Yes| | | AnyNumber| Auto
Yes| Yes| If desired enter a value less than estimated capacity| Yes| Yes|
Yes| AnyNumber| Any number
| Yes| None| Yes| Yes| Yes| AnyNumber| Off
The control valve with a water meter can be set for Demand Initiated
Regeneration (DIR) only, Time Clock operation only or DIR and Time Clock which
ever comes first, depending upon what settings are selected for Day Override
and Gallon2 Capacity.
See Table 7.
If a control valve does not contain a meter, the valve can only act as a time
clock, and day override should be set to any number and gallon capacity should
be set to off.
For DIR Softeners, there are two options for setting the Gallons Capacity. The
Gallons Capacity is automatically calculated if set to AUTO.
Reserve Capacity is automatically estimated based on water usage if AUTO is
used. The other option is to set the Gallons Capacity to a specific number. If
a specific number is set, reserve capacity is zero, unless the value is
manually set (i.e. the manufacturer intentionally sets the gallon capacity
number below the calculated capacity of the system).
The control valve can also be set to regenerate immediately or at the next
regeneration time by changing the Regeneration Time Option.
There are three choices for settings:
- “NORMAL” means regeneration will occur at the preset regeneration time.
- “on 0” means regeneration will occur when the gallons capacity reaches zero.
- “NORMAL + on 0” means the regeneration will occur at the preset regeneration time unless the gallons capacity reaches zero. If the gallons capacity reaches zero the regeneration will begin 10 minutes after no water usage.
The user can initiate manual regeneration. The user has the option to request the manual regeneration at the delayed regeneration time or to have the regeneration occur immediately:
- Pressing and release REGEN. “Regen Today” will flash on the display and the regeneration will occur at the delayed regeneration time. The user can cancel the request by pressing and releasing REGEN. This method of manually initiating regeneration is not allowed when the system is set to “on 0,” i.e. immediately regenerate when the gallon capacity reaches zero.
- Pressing and holding REGEN for approximately 3 seconds will immediately start the regeneration. The user cannot cancel this request, except by resetting the control by pressing NEXT and REGEN simultaneously for 3 seconds.
A unique feature of this control valve is the ability to display actual water
usage for the last 63 days. The values are initially stored as “—-”. This
means the value is unknown. As days pass values are stored as “0” for no flow
or the actual number of gallons. The counting of the gallons starts at the
regeneration time. If no regeneration time can be set (i.e. when the valve is
set for immediate regeneration) the counting of gallons starts at 12 a.m. Day
1 is yesterday, day 2 the day before yesterday, etc.
Another unique feature is that the valve automatically calculates a reserve
capacity when set up as a softener with “Gallons Capacity” set to “AUTO” and
the “Regeneration Time Option” set to “Normal” or “Normal + on 0”. The actual
reserve capacity is compared to the gallons capacity remaining immediately
prior to the preset regeneration time. A regeneration will occur if the actual
reserve capacity is less than the gallons capacity remaining. The actual
reserve capacity is calculated by using the estimated reserve capacity and
adjusting it up or down for actual usage.
The estimated reserve capacity for a given day of the week is the maximum
value stored for the last three non-trivial water usages (i.e. more than 20
gallons/day) in seven day intervals.
OEM General Instructions
The control valve offers multiple procedures that allow the valve to be
modified to suit the needs of the installation. These procedures are:
- OEM Softener Setup
- OEM Filter Setup
- Installer Displays & Settings
- User Displays & Settings
- Diagnostics
- Valve History
These procedures can be accessed in any order. Details on each of the
procedures are provided on the following pages.
At the discretion of the manufacturer, the field technician can access all
settings. To “lock out” access to diagnostic and valve history displays and
modifications to settings except hardness, day override, time of regeneration
and time of day by anyone but the manufacturer, press , NEXT, , and SET
CLOCK in sequence after settings are made. To “unlock”, so other displays can
be viewed and changes can be made, press , NEXT, , and SET CLOCK in
sequence.
When in operation normal user displays such as time of day, gallons remaining
or days remaining before regeneration are shown. When stepping through a
procedure, if no buttons are pressed within five minutes the display returns
to a normal user display. Any changes made prior to the five minute time out
are incorporated. The one exception is current flow rate display under the
diagnostic procedure. The current flow rate display has a 30 minute time out
feature.
To quickly exit OEM Softener Setup, OEM Filter Setup, Installer Display
Settings, Diagnostic or Valve History press SET CLOCK.
Any changes made prior to the exit are incorporated.
When desired, all information in Diagnostics may be reset to zero when the
valve is installed in a new location. To reset to zero, press NEXT and
simultaneously to go to the Service/OEM 1 screen, and release. Press and
simultaneously to
reset diagnostic values to zero. Screen will return to User Display.
Sometimes it is desirable to have the valve initiate and complete two
regenerations within 24 hours and then return to the preset regeneration
procedure. It is possible to do a double regeneration if the control valve is
set to “NORMAL” or “NORMAL + on 0” in
Step 8S or Step 7F. To do a double regeneration:
- Press REGEN once. REGEN TODAY will flash on the display.
- Press and hold REGEN for three seconds until the valve regeneration initiates.
Once the valve has completed the immediate regeneration, the valve will regenerate one more time at the preset regeneration time.
OEM Softener System Setup
This is a quick reference setup procedure. See OEM Softener System Setup
Detail for more information on available settings.
STEP 1S – Press NEXT and simultaneously for 3 seconds. If screen in step 2S
does not appear in 5 seconds the lock on the valve is activated. To unlock
press , NEXT, , and SET CLOCK in sequence, then press NEXT and
simultaneously for 3 seconds.
STEP 2S – Choose Softening using or . Press NEXT to go to Step 3S. Press
REGEN to exit OEM Softener System Setup.
STEP 3S – Set Refill option using or :
- “PoST” to refill the brine tank after the final rinse; or
- “PrE” to refill the brine tank two hours before the regeneration time set.
Press NEXT to go to Step 4S. Press REGEN to return to previous step.
STEP 4S – Program Code: Enter the desired program code from Table 2 or Table
3.
Prior to selecting a Program Code, verify the correct valve body, main piston,
regenerant piston, and stack are being used, and that the injector or injector
plug(s) are in the correct locations. See Compliance Table in WS1 and WS1.25
Drawings and Service Manual.
Press NEXT to go to Step 5S. Press REGEN to return to previous step.
STEP 5S – Enter the ion exchange capacity in grains of hardness as calcium
carbonate for the system based on test data using or . Press NEXT to go to
Step 6S. Press REGEN to return to previous step.
STEP 6S – Enter the pounds of salt per regeneration using or .
Press NEXT to go to Step 7S. Press REGEN to return to previous step.
STEP 7S – Set Gallons Capacity using or :
-
“AUTO” (reserve capacity automatically estimated and gallons capacity automatically calculated from grains capacity and water hardness);
-
“oFF” (regeneration based on day override); or
-
number of gallons (20 to 50,000).
See Setting Options Table for more detail. Press NEXT to go to Step 8S. Press REGEN to return to previous step.
STEP 8S – Set Regeneration Time Option using or : -
“NORMAL” means regeneration will occur at the preset time;
-
“on 0” means regeneration will occur immediately when the gallons capacity reaches 0 (zero); or
-
“NORMAL + on 0” means regeneration will occur at one of the following: the preset time when the gallons capacity falls below the reserve or the specified number of
-
days between regenerations is reached whichever comes first; or
-
after 10 minutes of no water usage when the gallon capacity reaches 0 (zero). See Setting Options Table for more detail. Press NEXT to exit OEM Softener System Setup. Press REGEN to return to previous step.
Setting Options Table
Filters should only use shaded options
Volume Capacity | Regeneration Time Option | Day Override | Result4 |
---|---|---|---|
**** AUTO | **** NORMAL | **** oFF | Reserve capacity automatically estimated. |
Regeneration occurs when volume capacity falls below the reserve capacity at
the next Regen Set Time
AUTO| NORMAL| Any number| Reserve capacity automatically
estimated. RegenerationoccursatthenextRegenSetTimewhenvolumecapacity
fallsbelowthereservecapacityorthespecifiednumberofdaysbetween regenerations is
reached.
Any number| NORMAL| oFF| Reserve capacity not automatically
estimated.
Regeneration occurs at the next Regen Set Time when volume capacity reaches 0.
oFF| **** NORMAL| Any number| Reserve capacity not automatically
estimated.
Regeneration occurs at the next Regen Set Time when the specified number of days between regenerations is reached.
Any number| **** NORMAL| Any number| Reserve capacity not
automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity reaches 0
or the specified number of days between regenerations is reached.
**** AUTO| **** On 0| **** oFF| Reserve capacity not
automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0.
Timeofregenerationwillnotbeallowedtobesetbecauseregeneration will always occur
when volume capacity reaches 0.
Any number| On 0| oFF| Reserve capacity not automatically
estimated.
Regeneration occurs immediately when volume capacity reaches 0.
Timeofregenerationwillnotbeallowedtobesetbecauseregeneration will always occur
on 0.
AUTO| NORMAL+on0| ****
**** oFF
| Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve capacity at
the next Regen Set Time or regeneration occurs after 10 minutes of no water
usage when volume capacity reaches 0.
**** AUTO| **** NORMAL+on0| Any number| Reserve capacity
automatically estimated.
RegenerationoccursatthenextRegenSetTimewhenvolumecapacity
fallsbelowthereservecapacityorthespecifiednumberofdaysbetween
regenerationsisreachedorregenerationoccurs after 10 minutesof no water usage
when volume capacity reaches 0.
Any number| NORMAL+on0| Any number| Reserve capacity not
automatically estimated.
Regeneration occurs at the next Regen Set Time when the specified
numberofdaysbetweenregenerationsisreachedorregenerationoccurs after 10 minutes
of no water usage when volume capacity reaches 0.
OEM Filter System Setup
This is a quick reference setup procedure. See OEM Filter System Setup Detail for more information on available settings.
STEP 1F – Press NEXT and simultaneously for 3 seconds. If screen in step 2F
does not appear in 5 seconds the lock on the valve is activated. To unlock
press , NEXT, , and SET CLOCK in sequence, then press NEXT and
simultaneously for 3 seconds.
STEP 2F – Choose Filtering using or . Press NEXT to go to step 3F. Press
REGEN to exit OEM Filter System Setup.
STEP 3F – Set Refill option using or :
• “PoST” to refill the brine tank after the final rinse; or
• “PrE” to refill the brine tank two hours before the regeneration time set.
Press NEXT to go to step 4F. Press REGEN to return to previous step.
STEP 4F – Program code: Enter the desired program code from Table 2, Table 5
or Table 6.
Prior to selecting a Program Code, verify the correct valve body, main piston,
regenerant piston, and stack are being used, and that the injector or injector
plug(s) are in the correct locations. See Compliance Table in WS1 and WS1.25
Drawings and Service Manual. Press NEXT to go to Step 5F. Press REGEN to
return to previous step.
STEP 5F – Enter “oFF” if regenerant is not used (i.e. backwash only) or enter
the refill volume (in gallons) using or . Press NEXT to go to step 6F.
Press REGEN to return toprevious step.
STEP 6F – Set Gallons Capacity using or :
• “oFF” (regeneration based on day override); or
• number of gallons (20 to 50,000).
See Setting Options Table for more detail. Press NEXT to go to step 7F. Press
REGEN to return to previous step.
STEP 7F – Set Regeneration Time Option using or :
- “NORMAL” means regeneration will occur at the preset time;
- “on 0” means regeneration will occur immediately when the gallons capacity reaches 0 (zero); or
- “NORMAL + on 0” means regeneration will occur at one of the following:
- the preset time when the specified number of days between regenerations is reached; or
- after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
This display will not appear is Step 6F is set to oFF. See Setting Options Table for more detail. Press NEXT to exit OEM Filter System Setup. Press REGEN to return to previous step.
Installer Display Settings
STEP 1I – Press NEXT and simultaneously for 3 seconds.
STEP 2I – Hardness: Set the amount of hardness in grains of hardness as
calcium carbonate per gallon using or . The default is 20 with value ranges
from 1 to 150 in 1 grain increments. Note: The grains per gallon can be
increased if soluble iron needs to be
reduced. This display will show “–nA–” if “FILTER” is selected in Step 2F or
if ‘AUTO’ is not selected in Step 7S. Press NEXT to go to step 3I. Press REGEN
to exit Installer Display Settings.
STEP 3I – Day Override: When gallon capacity is set to off, sets the number of
days between regenerations. When gallon capacity is set to AUTO or to a
number, sets the maximum number of days between regenerations. If value set to
“oFF” regeneration initiation is based solely on gallons used. If value is set
as a number (allowable range from 1 to 28) a regeneration initiation will be
called for on that day even if sufficient number of gallons were not used to
call for a regeneration. Set Day Override using or :
• number of days between regeneration (1 to 28); or
• “oFF”.
See Setting Options Table for more detail on setup. Press NEXT to go to step
4I. Press REGEN to return to previous step.
STEP 4I – Next Regeneration Time (hour): Set the hour of day for regeneration
using or . AM/PM toggles after 12. The default time is 2:00 a.m. This
display will show “REGEN on 0 GAL” if “on 0” is selected in Step 8S or Step
7F. Press NEXT to go to step 5I. Press REGEN to return to previous step.
STEP 5I – Next Regeneration Time (minutes): Set the minutes of day for
regeneration using or . This display will not be shown if “on 0” is
selected in Step 8S or Step 7F. Press NEXT to exit Installer Display Settings.
Press REGEN to return to previous
step.
To initiate a manual regeneration immediately, press and hold REGEN for three
seconds.
The system will begin to regenerate immediately. The control valve may be
stepped through the various regeneration cycles by pressing REGEN .
User Display Settings
General Operation
When the system is operating one of two displays will be shown. Pressing NEXT
will alternate between the displays. One of the displays is always the current
timeof day. The second display is one of the following: daysremaining or
gallons remaining. Days remaining is thenumber of days left before the system
goes through a regeneration cycle. Capacity remaining is the number ofgallons
that will be treated before the system goes througha regeneration cycle. The
user can scroll between the displays as desired.
If the system has called for a regeneration that will occur at the preset time
of regeneration, the words REGEN TODAY will appear on the display.
When water is being treated (i.e. water is flowing through the system) the
word “Softening” or “Filtering” flashes on the display if a water meter is
installed.
Regeneration Mode
Typically a system is set to regenerate at a time of low water usage. An
example of a time with low water usage is when a household is asleep. If
there is a demand for water when the systemis regenerating, untreated water
will be used.
When the system begins to regenerate, the display will change to include
information about the step of the regeneration process and the time remaining
for that step to be completed. The system runs through the steps automatically
and will reset itself to provide treated water when the regeneration has been
completed.
Manual Regeneration
Sometimes there is a need to regenerate the system sooner than when the system
calls for it, usually referred to as manual regeneration. There may be a
period of heavy water usage because of guests or a heavy laundry day.
To initiate
a manual regeneration at the preset delayed regenerationtime, when the
regeneration time option is set to “NORMAL” or “NORMAL + on 0”, press and
release REGEN. The words “REGENTODAY” will flash on the display to indicate
that the system will regenerate at the preset delayed regeneration time. If
you pressed REGEN in error, pressing the button again will cancel the request.
Note: If the regeneration time option is set to “on 0” there is no set delayed
regeneration time so “REGEN TODAY” will not activate if “REGEN” button is
pressed.
To initiate a manual regeneration immediately, press and hold REGEN for three
seconds. The system will begin to regenerate immediately. The request cannot
be cancelled.
Note: For softeners, if brine tank does not contain salt, fill with salt
and wait at least two hours before regenerating.
Set Time of
Day
The user can also set the time of day. Time of day should only need to be set
after power outages lasting more than 8 hours, if the battery has been
depleted and a power outage occurs, or when daylight saving time begins or
ends. If a power outage lasting more than 8 hours occurs, the time of day will
flash on and off which indicates the time of day should be reset. If a power
outage lasts less than 8 hours and the time of day flashes on and off, the
time of day should be reset and the battery replaced.
STEP 1U – Press SET CLOCK.
STEP 2U – Current Time (hour): Set the hour of the day using or . AM/PM
toggles after 12. Press NEXT to go to step 3U.
STEP 3U – Current Time (minutes): Set the minutes of the day using or .
Press NEXT to exit Set Clock. Press REGEN to return to previous step.
Power Loss
If the power goes out, the system will keep time for up to 8 hours or until
the battery is depleted. If a power outage of more than 8 hours occurs, the
time of day will flash on and off which indicates the time of day should be
reset. The system will remember the rest. If a power outage lasts less than 8
hours and the time of day flashes on and off, the non rechargeable battery
should be replaced.
Error Message
If the word “ERROR” and a number are alternately flashing on the display
contact the OEM for help. This indicates that the valve was not able to
function properly.
Diagnostics
STEP 1D – Press and simultaneously for three seconds. If screen in step 2D
does not appear in 5 seconds the lock on the valve is activated. To unlock
press , NEXT, , and SET CLOCK in sequence, then press and simultaneously
for 3 seconds.
STEP 2D
– Days, since last regeneration: This display shows the days since the last
regeneration occurred. Press NEXT to go to Step 3D. Press REGEN to exit
Diagnostics. STEP 3D – Gallons, since last regeneration: This display shows
the number of gallons that have been treated since the last regeneration. This
display will equal zero if a water meter is not installed. Press NEXT to go to
Step 4D. Press REGEN to return to previous step. STEP 4D – Gallons, reserve
capacity used for last 7 days: If the valve is set up as a softener, a meter
is installed and Set Gallons Capacity is set to “Auto,” this display shows 0
day (for today) and flashes the reserve capacity. Pressing will show day 1
(which would be yesterday) and flashes the reserve capacity used. Pressing
again will show day 2 (the day before yesterday) and the reserve capacity.
Keep pressing to show the gallons for days 3, 4, 5 and 6. can be pressed
to move backwards in the day series. Press NEXT at any time to go to Step 5D.
Press REGEN to return to previous step.
STEP 5D – Gallons, 63 day usage history: This display shows day 1 (for
yesterday) and flashes the number of gallons treated yesterday. Pressing
will show day 2 (which would be the day before yesterday) and flashes the
number of gallons treated on that day. Continue to press to show the maximum
number of gallons treated for the last 63 days. This display will show dashes
if a water meter is not installed. Press NEXT at any time to go to Step 6D.
Press REGEN to return to previous step.
STEP 6D – Flow rate, current: Turn the water on at one or more taps in the
building. The flow rate in gallons per minute will be displayed. If flow stops
the value will fall to zero in a few seconds. This display will equal zero if
a water meter is not installed. Press NEXT to go to Step 7D. Press REGEN to
return to previous step.
STEP 7D – Flow rate, maximum last seven days: The maximum flow rate in gallons
per minute that occurred in the last seven days will be displayed. This
display will equal zero if a water meter is not installed. Press NEXT to go to
Step 8D. Press REGEN to return to previous step.
STEP 8D – Gallons, total used since last reset: The total number of gallons
used since last reset will be displayed. This display will equal zero if a
water meter is not installed. Press NEXT to go to Step 9D. Press REGEN to
return to previous step.
STEP 9D – Days, total number since last reset: The total number of days the
control valve has been in service since last reset will be displayed. Press
NEXT to go to Step 10D. Press REGEN to return to previous step.
STEP 10D – Regenerations, total number since last reset: The total number of
regenerations that have occurred since last reset will be displayed. Press
NEXT to exit Diagnostics. Press REGEN to return to previous step.
When desired, all information in Diagnostics may be reset to zero when the
valve is installed in a new location. To reset to zero, press NEXT and
simultaneously to go to the Service/ OEM screen, and release. Press and
simultaneously to reset diagnostic values to zero. Screen will return to user
display.
Valve
History
STEP 1VH – Press and simultaneously for three seconds and release. Then
press and simultaneously and release. If screen in step 2VH does not
appear in 5 seconds the lock on the valve is activated. To unlock press ,
NEXT, , and SET CLOCK in sequence, then press and simultaneously for 3
seconds and release. Then press and simultaneously and release.
STEP 2VH – Software Version: This display shows the software version of the
valve. Press NEXT to go to Step 3VH. Press REGEN to exit Valve History. STEP
3VH 5 – Flow rate, maximum since startup: This display shows the maximum flow
rate in gallons per minute that has occurred since startup. This display will
equal zero if a water meter is not installed. Press NEXT to go to Step 4VH.
Press REGEN to return to previous step.
STEP 4VH – Gallons, total used since start-up: This display shows the total
gallons treated since startup. This display will equal zero if a water meter
is not installed. Press NEXT to go to Step 5VH. Press REGEN to return to
previous step.
STEP 5VH – Days, total since start-up: This display shows the total days since
startup. Press NEXT to go to Step 6VH. Press REGEN to return to previous step.
STEP 6VH – Regenerations, total number since start-up: This display shows the
total number of regenerations that have occurred since startup. Press NEXT to
go to Step 7VH. Press REGEN to return to previous step.
STEP 7VH – Error Log: This display shows a history of the last 10 errors
generated by the control during operation. Press or to review each error
recorded. Press NEXT to exit Valve History. Press REGEN to return to previous
step.
Front Cover and Drive Assembly
Drawing No. | Order No. | Description | Quantity |
---|---|---|---|
1 | V3175-01 | WS1 FRONT COVER ASY | 1 |
2 | V3107-01 | WS1 MOTOR | 1 |
3 | V3002-A | WS1 DRIVE BRACKET ASY | 1 |
4 | V3108CS-03BOARD | WS1/125 CS PCB XMEGA SMT REPL | 1 |
5 | V3110 | WS1 DRIVE REDUCING GEAR 12X36 | 3 |
6 | V3109 | WS1 DRIVE GEAR COVER | 1 |
Not Shown | V3186-06 | WS1 POWER SUPPLY 15VDC HOCP | 1 |
Power Supply | U.S. | International | |
--- | --- | --- | |
Supply Voltage | 100-120 VAC | 100-240 VAC | |
Supply Frequency | 50/60 Hz | 50/60 Hz | |
Output Voltage | 15 VDC | 15 VDC | |
Output Current | 500 mA | 500 mA |
Revision History:
1/27/2017
PAGE 16:
- Drawing number parts 2, 3, 5 and 6 may be purchased as a complete assembly, part V3002.
9/21/2017
PAGE 4:
Updates to table and drawing – Bracket and Spring Clip / Power Supply
10/9/2018
PAGE 16:
Updated Power Supply info
6/11/2020
PAGE 16:
Removed #7 V3106-01 from table and drawing.
Not Shown | V3186-06 | WS1 POWER SUPPLY 15VDC HOCP | 1 |
---|
Ranger Water Solutions is a trademark of Charger Water Treatment Products
8150 N. Lehigh Ave, Morton Grove, IL 60053
www.chargerwater.com/FAQ
Form No. V3115CS • 6/11/2020
U.S. Patent: 6,776,901
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>