Acuity Brands LIL LED Wall Pack User Manual

June 10, 2024
Acuity Brands

Acuity Brands LIL LED Wall Pack User Manual
Acuity Brands LIL LED Wall Pack

LED IMPORTANT SAFETY INSTRUCTIONS

  • hock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels.
  • Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
  • Installation and service of luminaires should be performed by a qualified licensed electrician.
  • Maintenance of the luminaires should be performed by person(s) familiar with the luminaires’ construction and operation and any hazards involved. Regular fixture maintenance programs are recommended.
  • It will occasionally be necessary to clean the outside of the refractor/lens. Frequency of cleaning will depend on ambient dirt level and minimum light output which is acceptable to user. Refractor/lens should be washed in a solution of warm water and any mild, non-abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly become dirty on the inside, wipe refractor/lens and clean in above manner, replacing damaged gaskets as necessary.
  • DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced.
  • Recycle: For information on how to recycle LED electronic products, please visit www.epa.gov.
  • These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, this matter should be referred to Acuity Brands Lighting, Inc.

WARNING RISK OF ELECTRIC SHOCK

  • Disconnect or turn off power before installation or servicing.
  • Verify that supply voltage is correct by comparing it with the luminaire label information.
  • Make all electrical and grounded connections in accordance with the National Electrical Code (NEC) and any applicable local code requirements.
  • All wiring connections should be capped with UL approved recognized wire connectors.

CAUTION RISK OF INJURY

  • Wear gloves and safety glasses at all times when removing luminaire from carton, installing, servicing or performing maintenance.
  • Avoid direct eye exposure to the light source while it is on.

WARNING RISK OF BURN

  • Allow lamp/fixture to cool before handling. Do not touch enclosure or light source.
  • Do not exceed maximum wattage marked on luminaire label.
  • Follow all manufacturer’s warnings, recommendations and restrictions for: driver type, burning position, mounting locations/methods, replacement and recycling.

CAUTION RISK OF FIRE

  • Keep combustible and other materials that can burn, away from lamp/lens.
  • Do not operate in close proximity to persons, combustible materials or substances affected by heat or drying.

CAUTION: RISK OF PRODUCT DAMAGE

  • Never connect components under load.
  • Do not mount or support these fixtures in a manner that can cut the outer jacket or damage wire insulation.
  • Unless individual product specifications deem otherwise: Never connect an LED product to dimmer packs, occupancy sensors, timing devices, or other related control devices. LED fixtures must be powered directly off a switched circuit.
  • Unless individual product specifications deem otherwise: Do not restrict fixture ventilation. Allow for some volume of airspace around fixture. Avoid covering LED fixtures with insulation, foam, or other material that will prevent convection or conduction cooling.
  • Unless individual product specifications deem otherwise: Do not exceed fixtures maximum ambient temperature.
  • Only use fixture in its intended location.
  • LED products are Polarity Sensitive. Ensure proper Polarity before installation.
  • Electrostatic Discharge (ESD): ESD can damage LED fixtures. Personal grounding equipment must be worn during all installation or servicing of the unit.
  • Do not touch individual electrical components as this can cause ESD, shorten lamp life, or alter performance.
  • Some components inside the fixture may not be serviceable. In the unlikely event your unit may require service, stop using the unit immediately and contact an ABL representative for assistance.
  • Always read the fixtures complete installation instructions prior to installation for any additional fixture specific warnings.
  • Verify that power distribution system has proper grounding. Lack of proper earth ground can lead to fixture failure and may void warranty

INSTALLATION DIAGRAMS

INSTRUCTION
INSTRUCTION
INSTRUCTION
INSTRUCTION
INSTRUCTION
INSTRUCTION
INSTRUCTION
INSTRUCTION

Little Wall Pack

TOOLS REQUIRED FOR INSTALLATION (not included)

TOOL

INSTALLATION INSTRUCTIONS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WARNING: When using electrical equipment, basic safety precautions should always be used including the following: This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved. Neutral wire is required for three phase input.

CAUTION – Regarding EL Models:

  • Battery is rechargeable Ni-Cd type and must be recycled or disposed of properly. Do not use this battery driver with accessory equipment other than recommended by manufacturer; failure to follow this may cause an unsafe condition.
  • Do not use battery driver for other than intended use. Not suitable for high-risk task area lighting.
  • Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
  • Do not mount near gas or electric heaters.

STEP 1: PREPARE FOR INSTALLATION

  1. Disconnect Power. AC power must be off before proceeding with assembly or installation. Always disconnect power during installation or maintenance. Ensure the power is OFF and disconnected by turning off the circuit breaker or by removing the appropriate fuse at the fuse box.
  2. Before installation, ensure the input power is 120-277VAC, 60Hz and supply wires are rated for at least 90°C (194°F).
  3. Review installation diagrams (Figures 1-4).
  4. Carefully remove fixture components and parts pack included for assembly. Check to ensure all parts are included. Account for small parts and destroy packing material, as these may be hazardous to children.
  5. Gather required tools

CAUTION: Do not rely on wall switch alone to turn off power. Turning the power off to the light switch alone is not sufficient to prevent electrical shock

STEP 2: ELECTRICAL CONNECTIONS

Note: Assistance may be required to support fixture during installation.

  1. Pull out the supply wires and house grounding wire from the junction box.

  2. Open the fixture by loosening the bottom screw (Figure 2). This separates the front housing from the back plate. Note if installing with BB Model: Remove back plate from Conduit Entry Wiring Box, install silicon gasket to groove, then install Wiring Box to standard or PE models using screws provided.

  3. Run the supply wires through the center hole in the back plate (Figure 2) and secure the back plate to the junction box using the provided screws and the slots in the back plate. Use the open slots that best fit the junction box.
    Note: When using electrical conduit for supply wires (instead of junction box), connect the conduit directly to the back plate center hole or conduit entry ports (on EL and BB Models). The center hole and conduit entry ports are set up to accept ½” electrical conduit. Then secure back plate to the wall using wall anchors (not included).

  4. Connect fixture leads to junction box leads (Figure 3). Note for EL Models: Power to the battery needs to be supplied using an un-switched power source (Figure 3). Power for regular illumination can be either switched or un-switched as needed.
    a. Connect ground wire (green) from fixture to grounding conductor of supply circuit and secure with wire nut. For proper wire connections, place wire nut over wires and twist clockwise until tight.
    b. Connect neutral wire (white) from fixture to neutral wire of supply circuit and secure with wire nut.
    c. Connect hot wire (black) wire from fixture to hot wire of supply circuit and secure with a wire nut.
    d. For EL Models: Connect the battery leads for battery backup function to be activate

STEP 3: INSTALL HOUSING

  1. Close the fixture by “hanging” the front housing to the back plate with the two tabs on the back plate (Figure 2). Then push the housing towards the back plate and tighten screw at the bottom of the fixture.
  2. Apply caulking to the perimeter of the fixture between the housing and the wall (top and two sides) leaving the bottom side clear of any caulking (Figure 4). Caulking will prevent any water coming down the wall from entering the fixture.

STEP 4: RESTORE POWER

  1. Restore power at the main fuse or circuit breaker box.
  2. Check operation of fixture.

Note for PE Models: Test fixture at night or block Photocell to turn fixture on. Cover the photo sensor with electrical tape, then turn power on and allow a couple of minutes for the sensor to activate the fixture. Then remove the electrical tape and the fixture will start to operate automatically when the ambient light is low enough.

Note for EL Models: When power is supplied to the battery the test button will light up indicating the battery is charging. Allow the battery to charge for at least 24 hours, then perform a short test by pushing the test button. The fixture will switch to battery mode and deliver about half the normal illumination. After the battery is fully charged (at least 48 hours of continuous power) a full 90 minute test can be performed by cutting power to the fixture.

PRODUCT MAINTENANCE

  1. Turn off power to fixture. Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.
  2. Dust fixture with a clean and soft, dry cloth.
  3. Wipe fixture clean with a damp cloth as needed. Do not use any cleaners with harsh chemicals, solvents, or abrasives. Do not use abrasive materials such as scouring pads or powders, steel wool or abrasive paper.
  4. Allow fixture to dry completely before power is restored.

Note: There are no user serviceable parts inside fixture. Do not touch LED’s.

Note for EL Models: It is recommended and required by applicable code to test battery ballast to ensure proper function of the system. Push the test switch for thirty (30) seconds every thirty (30) days to ensure  the battery driver is functioning by illuminating the light source. Conducta ninety (90) minutes discharge test one (1) time per year; LED light source should be illuminated for a minimum of ninety (90) minutes .

ISTINGS: UL certified to US and Canadian safety standards; Wet location listed (wall mount only).

5-YEAR LIMITED WARRANTY: Failure to follow any of these instructions could void product warranties. For a complete listing of product Terms and Conditions, please visit www.acuitybrands.com. Acuity Brands Lighting, Inc. assumes no responsibilities for claims arising out of improper or careless installation or handling of its products.

TROUBLESHOOTING GUIDE

Problem: Corrective Action:
Fixture will notilluminate. 1. Verify photocell is working properly by

covering it to block light from entering (light should turn on) (PE Models Only).
2. Verify line voltage is correct.
3. Check wiring and connections.
4. Verify power supply is on at switch and breaker.
5. Test or replace switch.
Fixture will notturn off.| Verify photocell is working properly by shining a flashlight into it (light should turn off) (PE Models Only).
Circuit breaker trips when fixture is illuminated.| Check wire connections. Ensure wires are not crossed and power wire is not grounding out. Consult electrician.
Light flickering or light is cycling on and off.| 1. Eliminate reflective surfaces or reposition fixture.
2. Check wiring and connections.
3. Test or replace switch.
4. Consult electrician.