This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the OSEF unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
READ THE USER’S MANUAL CAREFULLY BEFORE PROCEEDING WITH INSTALLATION
WORKS.
COMPLIANCE WITH THE MANUAL REQUIREMENTS ENSURES RELIABLE OPERATION AND
LONG
SERVICE LIFE OF THE UNIT.
KEEP THE USER’S MANUAL AVAILABLE AS LONG AS YOU USE THE UNIT. YOU MAY NEED
TO
REREAD THE INFORMATION ON THE PRODUCT SERVICING.
All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation. The present user’s manual should be carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing!
Deformation of the casing may result in motor jam and excessive
noise.
Misuse of the unit and any unauthorised modifications are not
allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities,
sticky substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment
containing spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation.
The Company reserves the right to modify the technical
characteristics, design, or configuration of its products at any time in
order to incorporate the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
This unit is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision
or instruction concerning use of the unit by a person responsible for
their safety.
Children should be supervised to ensure that they do not play with
the unit.
Precautions must be taken to avoid the back-flow of gases into the
room from the open flue of gas or other fuel-burning appliances.
Connection to the mains must be made through a disconnecting
device, which is integrated into the fixed wiring system in accordance
with the wiring rules for design of electrical units, and has a contact
separation in all poles that allows for full disconnection under
overvoltage category III conditions.
Ensure that the unit is switched off from the supply mains before
removing the guard.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
DELIVERY SET
Fan – 1 pc.
Screws with dowels – 4 pcs.
Plastic screwdriver – 1 pc. (only for the models with a timer)
User’s manual – 1 pc.
Packing box – 1 pc.
BRIEF DESCRIPTION
The product is an axial fan for exhaust ventilation of small and medium-sized
premises heated in winter. The design of the fan
may include a back valve that prevents air from flowing into the room when the
fan is off. The fan is designed for connection
to ø100 mm air ducts.
OPERATION GUIDELINES
The fan is rated for connection to 220-240 V/50 Hz single-phase AC power
mains, depending on the model type. For more
detailed information, see the casing sticker. Ingress protection rating
against access to hazardous parts and water ingress is IP44.
The manufacturer’s recommended operating temperature range is from +1 °C to +
40 °C.
The unit is rated as a Class II (220-240 V/ 50 Hz) electric appliance.
DESIGNATION KEY
OSEF 100 TS
Additional options:
TS: base model
CT: turn-off delay timer
CH: humidity sensor and turn-off delay timer
Outlet duct diameter [mm] Fan series
MOUNTING
The fan can be mounted to the ceiling or onto a wall with air extraction into a ventilation shaft or a matching diameter round air duct (Fig. 2). The fan installation steps are given on Fig. 3-11. Electric connection diagrams are given on Fig. 12-13.
Connection diagram terminal key:
L — line
N — neutral
S — external switch
QF — automatic switch
LT — timer control line
ELECTRONIC SYSTEM OPERATION ALGORITHM
The CT model fans equipped with a timer are activated by control voltage application to input terminal S by an external switch (e.g. indoor light switch). Upon control voltage removal the fan continues to operate for the period of time set by the timer within the range from 2 to 30 minutes.
The CH model fans equipped with a timer and a humidity sensor are activated by control voltage application to input terminal S or on exceeding the pre-set humidity level H adjustable within the ~60 % to ~90 % range. Upon control voltage removal or a decrease of humidity level H the fan continues to operate for the period of time set by the timer within the range from 2 to 30 minutes.
— To adjust the fan activation delay time, turn the Ton potentiometer knob clockwise (+) or counter-clockwise (-) which sets the activation delay time within the range from 0 to 2 minutes.
— To adjust the fan deactivation delay time, turn the Toff potentiometer knob clockwise (+) or counter-clockwise (-) which sets the activation delay time within the range from 2 to 30 minutes.
— To adjust the humidity sensor threshold value turn the H potentiometer knob clockwise (+) or counter-clockwise (-) which sets the threshold value within the range from 60 % to 90 %.
THE TIMER CIRCUIT IS LIVE.
MAKE SURE THE FAN IS DISCONNECTED FROM POWER SUPPLY.
The fan is supplied with a special plastic screwdriver. Use the
screwdriver to adjust the fan activation or deactivation delay
time or the humidity sensor threshold value.
DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR ADJUSTMENT
OPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD.
MAINTENANCE
To clean the unit from any dust and dirt which may accumulate on the surfaces (Fig. 14-17), use a soft cloth and a brush soaked in a mild detergent solution. Avoid spilling liquid on the electrical components. Wipe the cleaned surfaces dry.
TROUBLESHOOTING
Problem
|
Possible reasons
|
Troubleshooting
---|---|---
When the unit is connected to power mains, the fan does not rotate and does not respond to any controls.
|
No power supply.
|
Make sure the power supply line is connected correctly, otherwise troubleshoot the connection error.
Internal connection fault.
|
Contact the Seller.
Low air flow.
|
The ventilation system is clogged.
|
Clean the ventilation system.
Increased noise, vibration.
|
The impeller is clogged.
|
Clean the impeller.
The fan is not secured well or is not mounted properly.
|
Troubleshoot the installation error.
The ventilation system is clogged.
|
Clean the ventilation system.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5 °C up to + 40 °C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5 °C up to + 40 °C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/ EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 60 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its
intended use by the user within the
guaranteed period of operation. The faults are eliminated by means of
replacement or repair of the unit components or a specific part of such unit
component.
The warranty repair does not include:
• routine technical maintenance
• unit installation/dismantling
• unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT.