Osily OSEF100-BS Ventilation Base Extractor Fan Instruction Manual

June 10, 2024
osily

Osily OSEF100-BS Ventilation Base Extractor Fan Instruction Manual

This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the OSEF unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.

PLEASE READ THE USER’S MANUAL CAREFULLY PRIOR TO INSTALLING, CONNECTION TO POWER MAINS AND OPERATING THE UNIT.
THE MANUFACTURING COMPANY SHALL NOT BE RESPONSIBLE FOR DAMAGE TO HEALTH AND PROPERTY OF THE CUSTOMER CAUSED BY THE CUSTOMER’S VIOLATING THE USER’S MANUAL. FOLLOW THE USER’S MANUAL REQUIREMENTS TO ENSURE DURABLE OPERATION OF THE UNIT, ITS MECHANICAL AND ELECTRICAL RELIABILITY. KEEP THIS USER’S MANUAL.

All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation. The present user’s manual should be carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing!
Deformation of the casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not\ allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances. Connection to the mains must be made through a disconnecting device, which is integrated into the fixed wiring system in accordance with the wiring rules for design of electrical units, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.
Ensure that the unit is switched off from the supply mains before removing the guard.

THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.

DELIVERY SET

  • Fan — 1 pc.
  • Screws and dowels — 4 pcs.
  • Plastic screwdriver (only for the models with a timer) — 1 pc.
  • User’s manual — 1 pc.
  • Packing box — 1 pc.

BRIEF DESCRIPTION

The unit described herein is an axial fan for exhaust ventilation of small and medium sized utility spaces.
The fan is designed for connection to Ø 100 mm air ducts, depending on the model.

OPERATION GUIDELINES

The fan is rated for connection to single-phase AC power mains.
Power mains parameters are stated on the unit packaging and/or the label on the unit casing.
Hazardous parts access and water ingress protection rating: IP34

WARNING! IP is indicated for an assembled unit.
The fan is rated for operation at the ambient temperature ranging from +1 °C up to +40 °C.

WARNING! Do not operate the fan outside the specified temperature range.

The unit is rated as the Class II (220-240 V, 50 Hz/220 V, 60 Hz) or the Class lll (12 V/50 Hz) electrical appliance and requires no grounding.

DESIGNATION KEY

DESIGNATION KEY

MOUNTING

The fan is designed for wall (with the motors on ball and slide bearings) or ceiling mounting and can be used for direct outdoor air exhaust through a round duct or a duct system.
In case of installation through a duct system, select the duct cross section in accordance with the fan size (Fig. 1).
Mounting Instruction

  1. When installing the fan with direct air discharge outside through the wall, be sure to install a ventilation grille with louvre shutters or a ventilation hood on the outside to prevent rainfall, snow, leaves, branches, etc. from entering the duct.
    To reduce the risk of condensate forming in the duct, the space between the hole in the wall and the duct must be insulated.
    Install the air duct with the minimum slope of 1…2° downwards to the outer wall side for condensate removal (Fig 2).
    Mounting Instruction

  2. The duct system should not exceed 5 meters and have more than two bends.
    3. During ceiling installation, vertical air discharge upwards is not allowed even if there is a protective outer hood on the roof.
    For ceiling mounting and air discharge to the roof, the duct system must include a condensate drain (Fig. 3).
    Mounting Instruction

A condensate drain is not included in the delivery set of the fan and can be ordered separately.

Check the fan for any visible damages of the impeller, the casing and the grille before starting installation. The casing internals must be free of any foreign objects which can damage the impeller blades.
While mounting the unit, avoid compression of the casing!
Deformation of the casing may result in the motor jam and excessive noise.
Mount the fan on the wall or ceiling using four dowels with screws (included in the delivery set).
Dowels and screws are designed for concrete and brick walls.
If the walls are made of the other material (drywall, wood,etc.), use the fasteners appropriate for these materials to fasten the fan (not supplied with the fan and must be purchased separately).

WARNING! When the fan is equipped with a non-return valve, operation of the fan without this valve is prohibited.

The fan mounting sequence is shown in Fig. 4-11.
Mounting Instruction
Mounting Instruction
Mounting Instruction
Mounting Instruction
Mounting Instruction
Mounting Instruction
Mounting Instruction
Mounting Instruction
The fan wiring diagrams are shown in Fig. 12-14.
Mounting Instruction


Terminal designations on the wiring diagrams

L : line/~12 V
N : neutral/~12 V
LT: timer control line
S: external switch
QF : double pole circuit breaker

WARNING! The power cable may only be laid through the hole in the casing provided by the manufacturer.
Laying the power cable through a manually drilled hole will not be the liability of the manufacturer and will void the warranty. The wires must be stripped of insulation by a maximum of 8 mm. After installation, pass this User’s manual to the end user for reading.

The unit with a protection rating against access to hazardous parts and water ingress IP34 is allowed to be installed in zone 2, according to IEC 60364-7-701:2019.
MOUNTING INSTRUCTION

CAUTION! The unit must be installed at a distance of at least 2.3 m from the floor.
Diminsion

ELECTRONIC SYSTEM OPERATION ALGORITHM

The BT model fans equipped with a timer are activated by control voltage application to input terminal LT by an external switch S (e.g. indoor light switch). After the control voltage is off, the fan continues to operate within the set time period adjustable from 2 to 30 minutes by the timer. For the ST model, the fan is turned on/off with an internal cord switch.
The fan with a timer and a humidity sensor BH — the fan starts after the control voltage is supplied to the input terminal
LT or if indoor humidity level H exceeds the set point adjustable from ~60 % to ~90 %. After the control voltage is off or the humidity level H has decreased, the fan will keep running within the time, set by the turn-off delay timer, ranging from 2 to 30 minutes.
T off __to adjust the fan turn-off delay time, turn the control knob Toff clockwise to increase and counter-clockwise to decrease the turn-off delay time, adjustable from 2 up to 30 minutes.
H
to adjust the humidity set point, turn the control knob H clockwise to increase and counter-clockwise to decrease the humidity sensor set point, adjustable from 60 % up to 90 %.

The fan delivery set includes a specially designed plastic screwdriver for fan settings adjustments.
Use it to change the turn-on and turn-off delay time and the humidity set point.

ELECTRONIC SYSTEM

DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR  ADJUSTMENTOPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD.

TECHNICAL MAINTENANCE

The fan maintenance periodicity is at least once per 6 months.
Maintenance steps:

  • disconnect the fan from power supply and take steps to avoid unauthorized power supply connection (Fig. 15);
    Cleaning Instruction

  • remove decorative and front panels and clean the fan with a soft dry cloth or a brush (Fig. 16);
    Cleaning Instruction

  • wash the front panel under running water (Fig. 17);
    Cleaning Instruction

  • wipe the fan surfaces dry;

  • attach the front panel to the fan;

  • connect power supply (Fig. 18)
    Cleaning Instruction

WARNING! Do not allow water or liquid come into contact with electric components!

TROUBLESHOOTING

Problem Possible reason Troubleshooting

When the unit is connected to power mains, the fan does not rotate and does not respond to any controls.| No power supply| Make sure the power supply line is connected correctly, otherwise troubleshoot the connection error.
Internal connection fault| Contact the Seller
Low air flow.| The ventilation system is clogged.| Clean the ventilation system.
Noise, vibration| The impeller is clogged.| Clean the impeller
The fan is not secured well or is not mounted properly.| Troubleshoot the installation error.
The ventilation system is clogged.| Clean the ventilation system.

STORAGE AND TRANSPORTATION REGULATIONS

  • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.
  • Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
  • Follow the handling requirements applicable for the particular type of cargo.
  • The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
  • Avoid sharp blows, scratches, or rough handling during loading and unloading.
  • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/ EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 60 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.

The warranty repair does not include:

  • routine technical maintenance
  • unit installation/dismantling
    unit setup

To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.

The manufacturer’s warranty does not apply to the following cases:

  • User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
  • Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
  • User’s failure to ensure timely technical maintenance of the unit.
  • External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
  • Redesign or engineering changes to the unit.
  • Replacement and use of any assemblies, parts and components not approved by the manufacturer.
  • Unit misuse.
  • Violation of the unit installation regulations by the user.
  • Violation of the unit control regulations by the user.
  • Unit connection to power mains with a voltage different from the one stated in the user’s manual.
  • Unit breakdown due to voltage surges in power mains.
  • Discretionary repair of the unit by the user.
  • Unit repair by any persons without the manufacturer’s authorization.
  • Expiration of the unit warranty period.
  • Violation of the unit transportation regulations by the user.
  • Violation of the unit storage regulations by the user.
  • Wrongful actions against the unit committed by third parties.
  • Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
  • Missing seals if provided by the user’s manual.
  • Failure to submit the user’s manual with the unit purchase date stamp.
  • Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT.

USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.

Quality Inspector’s Stamp

Sold by (name and stamp of the seller)

Manufacture Date

Purchase Date

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

osily User Manuals

Related Manuals