Osily Ventilation OSEF Extractor Fan with Humidity Sensor User Manual
- June 10, 2024
- Osily Ventilation
Table of Contents
OSEF Extractor Fan with Humidity Sensor
User Manual
AXIAL FAN
OSEF Extractor Fan with Humidity Sensor
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the OSEF unit and all its
modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
READ THE USER’S MANUAL CAREFULLY BEFORE PROCEEDING WITH INSTALLATION WORKS.
COMPLIANCE WITH THE MANUAL REQUIREMENTS ENSURES RELIABLE OPERATION AND LONG
SERVICE LIFE OF THE UNIT.
KEEP THE USER’S MANUAL AVAILABLE AS LONG AS YOU USE THE UNIT. YOU MAY NEED TO
REREAD THE INFORMATION ON THE PRODUCT SERVICING.
All user’s manual requirements as well as the provisions of all the applicable
local and national construction, electrical, and technical norms and standards
must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to
1000 V are allowed for installation. The present user’s manual should be
carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing!
Deformation of the casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances. Connection to the mains
must be made through a disconnecting device, which is integrated into the
fixed wiring system in accordance with the wiring rules for design of
electrical units, and has a contact separation in all poles that allows for
full disconnection under overvoltage category III conditions.
Ensure that the unit is switched off from the supply mains before removing the
guard.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
DELIVERY SET
Fan
Screws and dowels
Plastic screwdriver (only for the models with a timer)
User’s manual
Packing
box| — 1 pc.
— 4 pcs.
— 1 pc.
— 1 pc.
— 1 pc.
---|---
BRIEF DESCRIPTION
The product is an axial fan for exhaust ventilation of small and medium-sized
premises.
The fan is designed for connection to Ø 100 mm air ducts depending on the
model.
OPERATION GUIDELINES
The fan is rated for connection to single-phase AC power mains.
Power supply parameters are stated on the unit packaging and/or the label on
the unit casing.
Ingress protection rating against access to hazardous parts and water ingress
is IP44.
The fan is rated for operation at ambient temperatures ranging from +1 °C to
+40 °C.
The unit is rated as a Class II (220-240 V, 50 Hz/220 V, 60 Hz) electrical
appliance and requires no grounding.
WARNING! Do not operate the fan outside the specified temperature range.
DESIGNATION KEY
INSTALLATION
The fan is designed for wall mounting (with motors on sliding and ball
bearings) or ceiling mounting and can be used to discharge air directly
outside through a round duct or through a duct system.
In case of installation through a duct system, select the duct cross section
in accordance with the fan size (Fig. 1).
-
When installing the fan with direct air discharge outside through the wall, be sure to install a ventilation grille with louvre shutters or a ventilation hood on the outside to prevent rainfall, snow, leaves, branches, etc. from entering the duct.
To reduce the risk of condensate forming in the duct, the space between the hole in the wall and the duct must be insulated.
Install the air duct with the minimum slope of 1…2° downwards to the outer wall side for condensate removal (Fig 2). -
The duct system should not exceed 5 meters and have more than two bends.
-
During ceiling installation, vertical air discharge upwards is not allowed even if there is a protective outer hood on the roof.
For ceiling mounting and air discharge to the roof, the duct system must include a condensate drain (Fig. 3).
A condensate drain is not included in the delivery set of the fan and can be ordered separately.
Check the fan for any visible damages of the impeller and the casing before starting installation. The casing internals must be free of any foreign objects which can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the casing may result in the motor jam and excessive noise. Mount the fan on the wall or ceiling using four dowels with screws (included in the delivery set).
Dowels and screws are designed for concrete and brick walls. If the walls are made of another material (drywall, wood, etc.), use the fasteners appropriate for these materials to fasten the fan (not supplied with the fan and must be purchased separately).
WARNING! When the fan is equipped with a non-return valve, operation of the fan without a valve is prohibited.
The fan mounting sequence is shown in Fig. 4-12.
The fan wiring diagrams are shown in Fig. 13-14.
Terminal designations on wiring diagrams:
L — line
N — neutral
S — timer control line
S1 — external switch
QF — automatic circuit breaker
WARNING! The power cable may only be laid through the hole in the
casing provided by the manufacturer (Fig. 13). Laying the power cable
through a manually drilled hole will not be the liability of the manufacturer
and will void the warranty. The wires must be stripped of insulation by a
maximum of 8 mm (Fig. 13).
After installation, pass this User’s manual to the end user for reading.
ELECTRONICS OPERATION ALGORITHM
The fan with the CT timer activates upon control voltage application to the
S input terminal by the S1 external switch (e.g. indoor light switch).
After the control voltage is off, the fan continues to operate within the
time set by the timer ranging from 2 to 30 minutes.
The fan with the timer and the humidity sensor CH – the fan starts after
the control voltage is supplied to the input terminal S or if indoor humidity
level H exceeds the set point adjustable from ~60 % to ~90 %.
After the control voltage is off or the humidity level has decreased, the fan
will keep running within the time set by the turnoff delay timer ranging from
2 to 30 minutes.
— To adjust the fan turn-on delay time, turn the control knob clockwise to
increase and counter-clockwise to decrease the turn-on delay time
respectively, adjustable from 0 up to 2 minutes.
— To adjust the fan turn-off delay time, turn the control knob clockwise to
increase and counter-clockwise to decrease the turn-off delay time
respectively, adjustable from 2 up to 30 minutes.
H — To adjust the humidity set point, turn the control knob H
clockwise to increase and counter-clockwise to decrease the humidity sensor
set point, adjustable from 60 % up to 90 %.
The fan delivery set includes a specially designed plastic screwdriver for fan
settings adjustments.
Use it to change the turn-on and turn-off delay time and the humidity set
point.
DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR ADJUSTMENT OPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD.
TECHNICAL MAINTENANCE
The fan maintenance periodicity is at least once per 6 months.
Maintenance steps:
- Disconnect the fan from power supply and make sure electricity has been turned off (Fig. 15).
- Remove the front and the decorative panels, wipe the fan with a dry cloth or a brush (Fig. 16).
- Clean the front panel under running water (Fig. 17).
- Wipe the fan surfaces dry.
- Cover the fan with the front panel.
- Connect power supply to the fan (Fig. 18).
WARNING! Do not allow water or liquid come into contact with electric components!
TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|
When the unit is connected to power mains, the fan does not rotate and does
not respond to any controls.| No power supply.| Make sure the power supply
line is connected correctly, otherwise troubleshoot the connection error.
Internal connection fault.| Contact the Seller.
Low air flow.| The ventilation system is clogged.| Clean the ventilation
system.
Increased noise, vibration.| The impeller is clogged.| Clean the impeller.
The fan is not secured well or is not mounted properly.| Troubleshoot the
installation error
The ventilation system is clogged.| Clean the ventilation system.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 ˚С to +40 ˚С and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility.
We hereby declare that the product complies with the provisions of
Electromagnetic Compatibility (EMC) Directive 2014/30/ EU of the European
Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the
European Parliament and of the Council and CE-marking Council Directive
93/68/EEC. This certificate is issued following test carried out on samples
of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 60 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s
manual with the purchase date stamp, and the payment paperwork certifying the
purchase. The unit model must comply with the one stated in the user’s
manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
YESSS_Electrical_215EN-01