RAB Lighting CRLEDFA-4R-12S-9CCT-UNV-WS 4 Inch 6 Inch 8 Inch 10 Inch Recessed Commercial Downlight FA Instructions
- June 9, 2024
- RAB Lighting
Table of Contents
- IMPORTANT
- WHAT’S IN THE BOX
- TOOLS NEEDED
- OPTIONAL ACCESSORIES
- OPTIONAL ACCESSORIES (cont’d)
- INSTALLATION WITH EXISTING FRAME
- INSTALLATION WITHOUT EXISTING FRAME
- INSTALLATION WITH EMERGENCY BATTERY BACKUP
- MIN.LUMINAIRE DIMENSION
- DIMENSIONAL DRAWINGS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
RAB Lighting CRLEDFA-4R-12S-9CCT-UNV-WS 4 Inch 6 Inch 8 Inch 10 Inch
Recessed Commercial Downlight FA Instructions
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAINTHESE INSTRUCTIONS FOR FUTURE REFERENCE
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY APERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNINGS:
- Risk of electrical shock. Disconnect power at fuse or circuit breaker before installing or servicing.
- To prevent early lamp failure, lamp should only be installed in operating environments ranging between-30°C and +40°C (-22°F and+104°F).
- No user serviceable parts inside. To avoid electrical shock do not disassemble product.
- Risk of fire or electric shock, LED Retrofit Kit installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
- Risk of fire or electric shock, Install this kit only in luminaires that have the construction features and min dimensions shown in below and where the input rating of the retrofit kit does not exceed the input rating of the luminaire.
- Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation
- To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
- Installers should not disconnect existing wires from lampholder terminals to make new connections at lampholder terminals, Instead installers should cut existing lampholder leads away from the lampholder and make new electrical connections to lampholder lead wires by employing applicable connectors.
- This device is not intended for use with emergency exits.
- Min.90°C supply conductors
- Installers should examine all parts that are not intended to be replaced by the retrofit kit for damage and replace any damaged parts prior to installation of the retrofit kit.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
WHAT’S IN THE BOX
- Downlight **(1)
**
- MC connector **(1)
**
- Wire Nuts **(5)
**
-
Lumi Sticker (1)
-
Template (1)
TOOLS NEEDED
This LED Recessed Kit requires very few tools for installation. A screwdriver and a pair of wirecutters will help to install the downlight to a J Box or housing.
OPTIONAL ACCESSORIES
Goof Ring
Visit rablighting.com for the downlight accessory compatibility lists.
DL4-6GOOF/R/P/CRLEDFA For use with 6″ ceiling hole applications
DL6-8GOOF/R/P/CRLEDFA For use with 8″ ceiling hole applications
DL8-10GOOF/R/P/CRLEDFA For use with 10″ ceiling hole applications
DL8-12GOOF/R/P/CRLEDFA For use with 12″ ceiling hole applications
DL10-12GOOF/R/P/CRLEDFA For use with 12″ ceiling hole applications
Plate
DLPLATE/C3468R/NB Mounting plate with nailer bar
OPTIONAL ACCESSORIES (cont’d)
Frame
DLFRAME/C6R
DLFRAME/C8R
INSTALLATION WITH EXISTING FRAME
- Shut power OFF to the fixture.
- Remove CFL, Incandescent or HID lamp. **(Fig.1)
**
-
Remove reflector from rough-in (mounting frame). (Fig.2)
-
Remove socket assembly from reflector. (Fig.3)
-
Remove J-Box metal plate with existing lamp ballast. Do not dispose. Disconnect all wires from the ballast. (Fig.4)
-
Remove the existing lamp metal conduit (MC) cable from the J-Box. (Fig.5)
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance. -
Select desired lumen and CCT level using switch on driver box. (Fig.6)
-
Fasten the LED retrofit kit MC cable to the 1-Box. (Fig.7)
-
Wire nut the ground (green) wire in the junction box. Wire nut the black input wire with the black wire from the MC cable and wire nut the white input wire with the white wire from the MC cable. Wire nut the purple input wire with the purple wire from the MC cable and wire nut the pink input wire with the pink wire from the MC cable. If the purple and pink wires are not in use, cap these with wire nuts. (Fig.8)
-
Install the junction box cover plate (with lamp ballast still attached to it). (Fig.9)
-
Install the retrofit kit in the rough-in by lifting upward both retention tabs. Push the kit until it sits flush against the ceiling. (Fig.10)
-
Turn power ON and start saving $$.
INSTALLATION WITHOUT EXISTING FRAME
-
Use template inside box to cut hole in ceiling. (Fig.11)
-
Select desired lumen and CCT level using switch on driver box. (Fig.12)
-
Shut power OFF to the fixture. Fasten the LED kit MC cable to a junction box with MC connector. Wire nut the ground (green) wire in the junction box. Wire nut the black input wire with the black wire from the MC cable and wire nut the white input wire with the white wire from the MC cable. Wire nut the purple input wire with the purple wire from the MC cable and wire nut the pink input wire with the pink wire from the MC cable. If the purple and pink wires are not In use, cap these with wire nuts.(Fig.13)
-
Install junction box cover plate. **(Fig.14)
Note: **These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
-
Install the LED kit by lifting both retention tabs upward. (Fig.15)
-
Push the kit until it sits flush against the ceiling. (Fig.16)
INSTALLATION WITH EMERGENCY BATTERY BACKUP
Take the Emergency Battery Backup System and snap in the MC cable from the
EMBB into the J-Box. Fasten the LED retrofit kit MC cable to the
J-Box. In the J-box, use wire nuts to do the wire connections as illustrated
in the diagram below. Make sure EMBB is grounded. Please visit
rablighting.com to view the emergency battery backup compatibility list.
MIN.LUMINAIRE DIMENSION
DIMENSIONAL DRAWINGS
CRLEDFA-4R-12S-9CCT-UNV-WS
CRLEDFA-6R-24S-9CCT-UNV-WS
CRLEDFA-8R-33S-9CCT-UNV-WS
CRLEDFA-10R-43S-9CCT-UNV-WS
Easy Answers
rablighting.com Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail Answered promptly – sales@rablighting.com