RAB Lighting WP1 Premium Wall Packs Instructions
- June 1, 2024
- RAB Lighting
Table of Contents
RAB Lighting WP1 Premium Wall Packs
Specifications:
- Model: WP1LED
- Dimensions: 8 1/2″ (216mm) x 6 3/4″ (172mm)
- 0-10V Dimmable
- Universal voltage driver: 120V – 277V, 50/60 Hz
FAQ
Q: Can I recess mount this fixture?
A: No, the fixture should not be recessed. Mount it on a wall with the lens facing down as instructed.
Q: What is the voltage range for dimming?
A: The universal voltage driver allows operation between 120V to 277V for dimming purposes.
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND
THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining fixture.
No user serviceable parts inside. CAUTION: For proper weatherproof function
all gaskets must be seated properly and all screws inserted and tightened
firmly. Apply weatherproof silicone sealant around the edge of the housing
where it meets the wall. This is especially important with an uneven wall
surface. Silicone all plugs and unused conduit entries.
MOUNTING
Fixture should not be recessed. Mount fixture on a wall with lens facing down as shown above. Use the Drill Template on the inside back surface of the housing to match most standard junction boxes or lag bolt housing to the mounting surface using locations as shown in Fig. 1.
- Open fixture Door Lens by loosening (4) screws. Remove LED Board as shown in Fig. 2.
- Prepare the Housing by drilling out the appropriate holes.
- Line up the Housing in desired location and mount securely using mounting hardware (by others). Caulk bolt/screw heads.
- Wire the Fixture leads to the supply wires using UL listed wire connectors according to NEC and local codes (Fig. 3).
- Replace the LED Board. Close Door Lens and tighten the (4) screws.
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. For 0-10V dimming, follow the wiring directions as shown in Fig. 3.
-
For Junction Box Mount, feed wires through silicone wiring plug into the junction box.
-
Connect the black fixture lead to the LINE supply lead.
-
Connect the white fixture lead to the COMMON supply lead.
-
Connect the GROUND wire from fixture to supply ground.
Do NOT connect the GROUND of the dimming fixture to the output. -
Connect the purple fixture lead to the (V+) DIM lead.
-
Connect the pink fixture lead to the (V-) DIM lead.
-
Cap the yellow fixture lead, if present. Do NOT connect.
TROUBLESHOOTING
- Check that the line voltage at the fixture is correct. Refer to wiring directions.
- Is the fixture grounded properly?
- Be sure the photocell, if used, is functioning properly.
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.
- Clean lens with non-abrasive glass cleaning solution.
- Do not open the fixture to clean the LED. Do not touch the LED.
DIMENSIONS
WIRING
CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage could be present in BATTERY. To prevent high voltage from being present on output leads, inverter connector must be open. Do not join BATTERY connector until installation is complete and AC power is supplied to the emergency driver (Fig. 4).
NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver.
CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.
- Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
- If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
- If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external SWITCHED.
- Connect the WHITE/NEUTRAL fixture lead to the WHITE/NEUTRAL supply line.
- For 0-10V Dimming, connect DIM (+) and DIM (-) to the supply DIM (+) and DIM (-).
- Connect GROUND lead from the fixture to the supply ground. Do not connect GROUND to the output leads.
- All unused lead must be capped and insulated.
- After installation is complete, supply AC power to the fixture and connect the BATTERY.
- When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
- Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the test button.
- After the battery has charged for 24 hours, a long duration test FIG. 4
OPERATION
- When AC power is applied, the charging indicator light is illuminated, indicating that the BATTERY is being charged.
- When power fails, the standby power automatically switches to emergency power (internal battery), operating at reduced illumination. Not all LED boards will illuminate with standby power. The emergency driver supplies 8W of power in standby power for a minimum of 90 minutes.
- When AC power is restored, the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
- Visually inspect the charging indicator light monthly. It should be illuminated.
- Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
- Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
- Is the fixture grounded properly?
- If the charging indicator light does not illuminate after pressing the test button, check if battery is connected properly.
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>