RAB LIGHTING W22-S-30 Field Adjustable Wall Pack Installation Guide

May 15, 2024
RAB Lighting

RAB-logo

RAB LIGHTING W22-S-30 Field Adjustable Wall Pack

RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-product-
image

Product Information

Specifications

  • Model Variants: W22-S-30, W22-M-60/W22-M-100, W22-L-150
  • Color Temperature: Field-adjustable
  • Power Options: Field-adjustable
  • Photocell: On/Off option

Product Usage Instructions

Mounting Instructions

  1. Loosen the (2) Philip Screws on the right side of the housing.
  2. Remove the Housing Back Plate by disconnecting the connector between the driver and the LED board. Peel off the protective film on Foam Gasket and place it onto the Housing Back Plate.
  3. Mount the Housing Back Plate with the attached Foam Gasket to the surface using the provided Junction Box Drill Pattern. Use a drill to open the mounting holes to the desired pattern. Wire the housing leads to supply wires using UL listed wire connectors according to NEC and local codes. Push all wires into the Housing Black Plate.
  4. For Conduit Entry, remove the conduit cap using a screwdriver. Feed supply wires through the conduit opening with a suitable connector. Wire the housing leads to supply wires using UL listed wire connectors according to NEC and local codes. Push all wires into the Housing Back Plate.
  5. Replace the Front Housing onto the Hinge Pins and reconnect the connector between the driver and LED board. Attach the Front Housing ground wire to the supply ground. Secure the Front Housing to the Housing Back Plate by tightening the (2) Phillip Screws on the right side of housing.

Field Adjustment

  1. Locate Selector Switches on the side of Housing and remove Selector Switch Cover Plug.
  2. Select Color Temperature (CCT), Power (W), and/or Photocell On/Off position by sliding the respective switch to the desired value.
  3. Replace Selector Switch Cover Plug.

Beam Angle Adjustment
Use a 5/16 Allen Wrench to adjust the desired Beam/Optic Angle as shown in Fig. 6.

Wire Guard Accessory
(Wire Guard Accessory, Model # W22-S-WG, W22-M-WG, and W22-L-WG sold separately).

FAQ

  • Q: How do I adjust the color temperature and power settings?
    A: Follow the instructions provided in the Field Adjustment section of the manual to change the Color Temperature (CCT) and Power (W) settings.

  • Q: Can I purchase additional accessories for this product?
    A: Yes, you can purchase Wire Guard Accessories (Model # W22-S-WG, W22-M-WG, and W22-L-WG) separately for added protection.

INSTRUCTIONS

FIELD-ADJUSTABLE W22™ INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well- designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig-
\(1\)

IMPORTANT

  • READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
  • RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
  • WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.
  • Suitable for wet locations.
  • CAUTION: For proper weatherproof function all gaskets must be seated properly and all screws inserted and tightened firmly. Apply weatherproof silicone sealant around the edge of the Housing Back Plate where it meets the wall. This is especially important with an uneven mounting surface. Silicone all plugs and unused conduit entries.

MOUNTING

  1. Loosen (2) Philip Screws on right side of housing as shown in Fig. 1.
  2. Remove the Housing Back Plate (Fig. 2) by disconnecting connector between the driver and the LED board. Peel off the protective film on Foam Gasket and place onto the Housing Back Plate (Fig. 2).
  3. Mount Housing Back Plate with attached Foam Gasket to surface using the provided Junction Box Drill Pattern as shown in Fig. 3 and 4. Use a drill to open the mounting holes to the desired pattern. Wire the housing leads to supply wires using UL listed wire connectors according to NEC and local codes (Fig. X). Push all wires into the Housing Black Plate.
  4. For Conduit Entry, remove conduit cap using a screw driver (Fig. 3). Feed supply wires through conduit opening with suitable connector (by others). Wire the housing leads to supply wires using UL listed wire connectors according to NEC and local codes (Fig. 9). Push all wires into the Housing Back Plate.
  5. Replace the Front Housing onto the Hinge Pins (Fig 3) and reconnect the connector between the driver and LED board. Attach the Front Housing ground wire to the supply ground. Secure the Front Housing to the Housing Back Plate by tightening (2) Phillip Screws on the right side of housing as shown in Fig. 1. Be careful not to pinch any wires between the front and rear housings.RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig- \(2\) RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig- \(3\)

FIELD ADJUSTMENT
Follow instructions below to change fixture Color Temperature (CCT), Power (W) and/or Photocell On/Off option from the factory settings:

Factory Settings: Max wattage, 4000K, Photocell/OFF

  1. Locate Selector Switches on side of Housing as shown in Fig. 5. and remove Selector Switch Cover Plug.
  2. Select Color Temperature (CCT), Power (W) and/or Photocell On/Off position by sliding the respective switch to the desired value (Fig. 5).
  3. Replace Selector Switch Cover Plug.

BEAM ANGLE ADJUSTMENT
Follow instructions below to change fixture Beam/Optic Angle to increase or reduce light angle. Beam/Optic selectable options are 0°/15°/30°/45°.

Factory Settings: 45°

  1. Locate Beam/Optic Angle Selector on the side of Housing as shown in Fig. 6 and select desired Beam/Optic Angle using 5/16” Allen Wrench (provided).

WIRE GUARD ACCESSORY

(Wire Guard Accessory, Model # W22-S-WG, W22-M-WG and W22-L-WG sold separately).

  1. Align Wire Guard onto Fixture as shown in Fig. 7.
  2. Secure Wire Guard to Fixture with (4) Screws (provided) as shown in Fig. 8.RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig- \(7\)

0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. Units ordered with /480 suffix are 480V, 50 or 60Hz ONLY. For 0-10V dimming follow the wiring directions as shown in Fig. 9.

  1. Connect the black fixture lead to the LINE supply lead.
  2. Connect the white fixture lead to the COMMON supply lead.
  3. Connect the GROUND wire from fixture to supply ground.
  4. Connect the purple fixture lead to the (V+) DIM lead.
  5. Connect the pink fixture lead to the (V-) DIM lead.

NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink) to line voltage or supply ground.RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig-
\(8\)

CLEANING & MAINTENANCE

CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.

  1. Do not open fixture to clean the LED. Do not touch the LED.
  2. Clean lens with non-abrasive glass cleaning solution.

TROUBLESHOOTING

  1. Check that the line voltage at the fixture is correct. Refer to wiring directions.
  2. Is the fixture grounded properly?

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

BATTERY BACKUP MODELS

WIRING (WS22-S)

  • Note: W22-S (Small) Model has an external battery backup module as shown in Fig. 11.
  • CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY. To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join BATTERY connector until installation is complete.
  • NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver. Reference Fig.10 for wiring diagram.
  • CAUTION: Do not use any supply voltage other than 120-277V, 50/60Hz.
  1. Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
  2. If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
  3. If using a SWITCHED circuit, connect SWITCHED HOT lead to the switch.
  4. For 0-10V dimming, connect DIM (+) purple and DIM (-) pink leads to 0-10V dimming connection.
  5. All unused leads must be capped and insulated.
  6. When power is on, the fixture should be ON and the CHARGING INDICATOR LIGHT should illuminate to indicate the battery is charging.
  7. Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the Test Button as shown in Fig. 11.
  8. After the battery has charged for 24 hours, a long duration test can be performed by disconnecting power to the fixture.
    RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig-
\(9\)

OPERATION

  1. When AC power is applied the charging indicator light is illuminated indicating that the BATTERY is being charged.
  2. When power fails the standby power automatically switches to emergency power operating at reduced illumination.
  3. When AC power is restored the emergency driver automatically returns to charging mode.

MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:

  1. Visually inspect the charging indicator light monthly. It should be illuminated
  2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
  3. Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.

TROUBLESHOOTING

  1. Be sure the fixture is grounded properly.
  2. If the charging indicator light does not illuminate after pressing and releasing the Test Button (Fig. 11), check power and check if battery is connected properly.RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig- \(10\)

WIRING (W22-M, W22-L)

  • Note: W22-M (Medium) and W22-L (Large) Models have an internal battery back up module.
  • CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY. To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join BATTERY connector until installation is complete.
  • NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver. Reference Fig.12 for wiring diagram.
  • CAUTION: Do not use any supply voltage other than 120-277V, 50/60Hz.
  1. Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
  2. If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
  3. If using a SWITCHED circuit, connect SWITCHED HOT lead to the switch.
  4. For 0-10V dimming, connect DIM (+) purple and DIM (-) pink leads to 0-10V dimming connection.
  5. All unused leads must be capped and insulated.
  6. When power is on, the fixture should be on and the CHARGING INDICATOR LIGHT should illuminate to indicate the battery is charging.
  7. Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the Test Button as shown in Fig. 13 located on bottom of the Housing Back Plate.
  8. After the battery has charged for 24 hours, a long duration test can be performed by disconnecting power to the fixture.RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig- \(11\)

OPERATION

  1. When AC power is applied the charging indicator light is illuminated indicating that the BATTERY is being charged.
  2. When power fails the standby power automatically switches to emergency power (internal battery) operating at reduced illumination.
  3. When AC power is restored the emergency driver automatically returns to charging mode.

MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:

  1. Visually inspect the charging indicator light monthly. It should be illuminated
  2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
  3. Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.

TROUBLESHOOTING

  1. Be sure the fixture is grounded properly.
  2. If the charging indicator light does not illuminate after pressing and releasing the Test Button (Fig. 13), check power and check if battery is connected properly.

RAB-LIGHTING-W22-S-30-Field-Adjustable-Wall-Pack-fig-
\(12\)

© 2024 RAB LIGHTING Inc.
W22 S-M-L 0124 P-100815

  • Easy Answers
    rablighting.com
    Visit our website for product info

  • Tech Help Line
    Call our experts: 888 722-1000

  • e-mail
    Answered promptly – sales@rablighting.com

  • Free Lighting Layouts
    Answered online or by request

RAB WARRANTY: RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty .

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

RAB Lighting User Manuals

Related Manuals