LS XGL-PSRA Programmable Logic Controller Installation Guide
- June 9, 2024
- LS
Table of Contents
LS XGL-PSRA Programmable Logic Controller Installation Guide
This installation guide provides simple function information or PLC control. Please read carefully this data sheet and manuals before using products. Especially read precautions then handle the products properly.
Safety Precautions
■ Meaning of warning and caution label
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
WARNING
CAUTION indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
It may also be used to alert against unsafe practices
WARNING
- Do not contact the terminals while the power is applied.
- Be sure there are no foreign metallic matters.
- Do not manipulate the battery(charge, disassemble, hitting, short, soldering).
CAUTION
- Be sure to check the rated voltage and terminal arrangement before wiring
- When wiring, tighten the screw of terminal block with the specified torque range
- Do not install the flammable things on surroundings
- Do not use the PLC in the environment of direct vibration
- Except expert service staff, do not disassemble or fix or modify the product
- Use the PLC in an environment that meets the general specifications contained in this datasheet.
- Be sure that external load does not exceed the rating of output module.
- When disposing of PLC and battery, treat it as industrial waste.
- I/O signal or communication line shall be wired at least 100mm away from a highvoltage cable or power line.
Operating Environment
■ To install, observe the below conditions.
Applicable Support Software
- For system configuration, the following version is necessary.
- XGI CPU : V3.9 or above
- XGK CPU : V4.5 or above
- XGR CPU : V2.6 or above
- XG5000 Software : V4.0 or above
Accessories and Cable Specifications
- Check Profibus Connector contained in the box
- Usage : Profibus Communication Connector
- Item : GPL-CON
- When using Pnet communication, shielded twisted pair cable shall be used with consideration of communication distance and speed.
- Manufacturer : Belden or the maker of equivalent material specification below
- Cable Specification
Parts Name and Dimension (mm)
- This is front part of the Module. Refer to each name when operating the system. For more information, refer to user’s manual.
■ LED details
Installing / Removing Modules
■ Here describes the method to attach each module to the base or remove it.
-
Installing module
① Insert a fixed projection of the lower part Of PLC into the module fixed hole of base
② Slide the upper part of module to fix to the base, and then fit it to the base by using the module fixed screw.
③ Pull the upper part of module to check if it is installed to the base completely. -
Removing module
① Loosen the fixed screws of the upper part of module from the base
② By pressing the hook, pull the upper part of module from the axis of the lower part of module
③ By lifting the module upward, remove the loading lever of module from the fixing hole
Wiring
- Connector structure and wiring method
- Input line: green line is connected to A1, red line is connected to B1
- Output line: green line is connected to A2, red line is connected to B2
- Connect shield to clamp of shield
- In case of installing the connector at terminal, install the cable at A1, B1
- For more information about wiring, refer to user manual.
Warranty
- Warranty period 18 months after the production date.
- Scope of Warranty 18-month warranty is available except:
- The troubles caused by improper condition, environment or treatment except the instructions of LS ELECTRIC.
- The troubles caused by external devices
- The troubles caused by remodeling or repairing based on the user’s own discretion.
- The troubles caused by improper usage of the product
- The troubles caused by the reason which exceeded the expectation from science and technology level when LS ELECTRIC manufactured the product
- The troubles caused by natural disaster
- Change in specifications Product specifications are subject to change without notice due to continuous product development and improvement.
LS ELECTRIC Co., Ltd.
10310001113 V4.4 (2021.11)
• E-mail: automation@ls-electric.com
- Headquarter/Seoul Office Tel: 82-2-2034-4033,4888,4703
- LS ELECTRIC Shanghai Office (China) Tel: 86-21-5237-9977
- LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China) Tel: 86-510-6851-6666
- LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam) Tel: 84-93-631-4099
- LS ELECTRIC Middle East FZE (Dubai, U.A.E.) Tel: 971-4-886-5360
- LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands) Tel: 31-20-654-1424
- LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan) Tel: 81-3-6268-8241
- LS ELECTRIC America Inc. (Chicago, USA) Tel: 1-800-891-2941
• Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnamdo, 31226, Korea
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>