MW PW M -90 series Constant Voltage PWM Output LED Driver Owner’s Manual
- June 9, 2024
- MW
Table of Contents
MW PW M -90 series Constant Voltage PWM Output LED Driver
Features
- Constant Voltage PWM style output
- Emergency lighting application is available according to IEC61347-2-13
- Built-in active PFC function and class II design
- Class 2 power unit(except PWM-90-12)
- No load power consumption <0.5W
- Fully encapsulated with IP67 level
- Function: 3 in 1 dimming (dim-to-off); DAL/DALI-2
- Minimum dimming level 0.2% for DALI type
- Typical lifetime>50000 hours and 5 years warranty
Applications
- LED strip lighting
- Indoor LED lighting
- LED decorative lighting
- LED architecture lighting
- Industrial lighting
GTIN CODE
MW Search: htps:/www.meanwell.com/serviceGTIN.aspx
Description
PWM-90 series is a 90W LED AC/DC LED driver featuring the constant voltage mode with PWM style output, which is able to maintain the brightness homogeneity when driving all kinds of LED strips.PWM-90 operates from 90~305VAC and offers models with different rated voltage ranging between 12V and 48V. Thanks to the high efficiency up to 90.5%, with the fanless design, the entire series is able to operate for -40C+85C case temperature under free air convection. The entire series is rated with IP67 ingress protection level and is suitable to work for dry, damp or wet locations. PWM-90 is equipped with a dimming function that varies the duty cycle of the output, providing great flexibility for LED strips applications.
Model Encoding
SPECIFICATION
MODEL | PWM-90-12 | PWM-90-24 | PWM-90-36 | PWM-90-48 |
---|
OUTPUT
| DC VOLTAGE| 12V| 24V| 36V| 48V
RATED CURRENT| 7.5A| 3.75A| 2.5A| 1.88A
RATED POWER| 90W| 90W| 90W| 90.24W
DIMMING RANGE| 0 ~ 100%
PWM FREQUENCY (Typ.)| 1.47kHz for Blank/DA-Type, 2.5kHz for
DA2-Type
SETUP, RISE TIME Note.2
Note.9
| 500ms, 80ms/ 115VAC or 230VAC
HOLD UP TIME (Typ.)| 16ms/115VAC or 230VAC
INPUT
| VOLTAGE RANGE Note. 3| 90 ~ 305VAC 127 ~ 431VDC
(Please refer to “STATIC CHARACTERISTIC” section)
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| PF>0.98/115VAC, PF>0.96/230VAC, PF>0.92/277VAC @
full load
(Please refer to “POWER FACTOR (PF) CHARACTERISTIC” section)
TOTAL HARMONIC DISTORTION| THD< 20%(@load≧60%/115VAC, 230VAC; @load≧75%/277VAC)
(Please refer to “TOTAL HARMONIC DISTORTION” section)
EFFICIENCY (Typ.)| 88%| 90.5%| 90.5%| 90.5%
AC CURRENT (Typ.)| 0.95A / 115VAC 0.5A / 230VAC 0.4A /
277VAC
INRUSH CURRENT (Typ.)| COLD START 60A(twidth=550 μs measured at 50%
Ipeak) at 230VAC ; Per NEMA 410
MAX. NO. of PSUs on 16A CIRCUIT BREAKER| 3 units (circuit breaker of
type B) / 6 units (circuit breaker of type C) at 230VAC
LEAKAGE CURRENT| <0.25mA / 277VAC
| <0.5W
PROTECTION
| OVERLOAD| 108 ~ 130% rated output power
Hiccup mode, recovers automatically after fault condition is removed
SHORT CIRCUIT| Shut down o/p voltage, re-power on to recover(except for
DA2-type)
Hiccup mode,recovers automatically after fault condition is removed (only for DA2-type)
OVER VOLTAGE
| 15 ~ 17V| 28 ~ 34V| 41 ~ 46V| 54 ~ 60V
Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, re-power on to recover
ENVIRONMENT
| WORKING TEMP.| Tcase=-40 ~ +85℃ (Please refer to “ OUTPUT LOAD vs
TEMPERATURE” section)
MAX. CASE TEMP.| Tcase=+85℃
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +80℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along X,
Y, Z axes
SAFETY & EMC
| ****
SAFETY STANDARDS Note.5
| UL8750(except for DA-Type), CSA C22.2 No. 250.13-12; ENEC BS EN/EN61347-1, BS EN/EN61347-2-13 independent, BS EN/EN62384, IP67,BIS IS15885(for 12,24,48 Blank Type only), EAC TP TC 004,GB19510.1, GB19510.14 approved;
Design refer to BS EN/EN60335-1;According to BS EN/EN61347-2-13 appendix J suitable for emergency installations
DALI STANDARDS| IEC62386-101, 102, 207,251 for DA/DA2-Type only,Device
type 6(DT6)
WITHSTAND VOLTAGE| I/P-O/P:3.75KVAC; I/P-DA:1.5KVAC; O/P-DA:1.5KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION Note.6| Compliance to BS EN/EN55015, BS EN/EN61000-3-2
Class C (@load≧60%) ; BS EN/EN61000-3-3,GB17743 and GB17625.1,EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11; BS
EN/EN61547, light industry level (surge immunity Line-Line 2KV), EAC TP TC 020
OTHERS
| MTBF| 2394.5K hrs min. Telcordia SR-332 (Bellcore) ; 224.2K
hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 1716337.5mm (LWH)
PACKING| 0.77Kg; 18pcs/14.9Kg/0.97CUFT
NOTE|
-
All parameters NOT specially mentioned are measured at 230VAC input, rated current and 25C of ambient temperature.
-
De-rating may be needed under low input voltages. Please refer to “STATIC CHARACTERISTIC” sections for details.
-
Length of set up time is measured at first cold start. Turning ON/OFF the driver may lead to increase of the set up time.
-
The driver is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected
by the complete installation, the final equipment manufacturers must re- qualify EMC Directive on the complete installation again. -
This series meets the typical life expectancy of >50,000 hours of operation when Tcase, particularly c)point (or TMP, per DLC), is about 75C or less.
-
Please refer to the warranty statement on MEAN WELLs website at http://www.meanwell.com
-
The ambient temperature derating of 3.5 C/1000m with fanless models and of 5 CH000m with fan models for operating altitude higher than 2000m(65O0f).
-
For any application note and IP water proof function installation caution, please refer our user manual before using.
https://www.meanwell.com/Upload/PDF/LED_EN.pdf -
Based on IEC 62386-101/102 DALI power on timing and interruption regulations, the set up time needs to test with a DALI controller which
can support for DALI power on function, otherwise the set up time wil be higher than 0.5 second for DA type.
- Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
DIMMING OPERATION
- DIM+ for Blank-Type
- DA+ for DA/DA2-type
- DIM- for Blank-Type
- DA- for DA/DA2-type
NOTE: DA /DA2-Type is no distinction between “+” and “-” poles
Dimming principle for PWM style output
- Dimming is achieved by varying the duty cycle of the output current.
Output DC current
- Duty cycle(%) = TON/T×100%
- Output PWM frequency: 1.47kHz for Blank/DA-Type 2.5kHz for DA2-Type
3 in 1 dimming function (for Blank-Type)
- Apply one of the three methodologies between DIM+ and DIM-: 0 ~ 10VDC, or 10V PWM signal or resistance.
- Dimming source current from power supply: 100μA (typ.)
Applying additive 0 ~ 10VDC
Applying additive 10V PWM signal (frequency range 100Hz ~ 3KHz)
Applying additive resistance
Note
- Min. duty cycle of output current is about 0.15%, and the dimming input is about 6KΩ or 0.6VDC, or 10V PWM signal with 6% duty cycle.
- The duty cycle of output current could drop down to 0% when dimming input is less than 6KΩ or less than 0.6VDC, or 10V PWM signal with duty cycle less than 6%.
DALI Interface (primary side; for DA/DA2-Type)
- Apply DALI signal between DA+ and DA-.
- DALI protocol comprises 16 groups and 64 addresses.
- First step is fixed at 0.2% of output
OUTPUT LOAD vs TEMPERATURE
STATIC CHARACTERISTIC/ POWER FACTOR (PF) CHARACTERISTIC
- De-rating is needed under low input voltage.
TOTAL HARMONIC DISTORTION (THD)
- 48V Model, Tcase at 75℃
EFFICIENCY vs LOAD
PWM-90 series possess superior working efficiency that up to 90.5% can be reached in field applications.
- 48V Model, Tcase at 75℃
LIFETIME
Block Diagram
Mechanical Specification
Blank-Type
- Case No: PWM-90P
- Unit: mm
DA/DA2-Type
Recommend Mounting Direction
Installation Manual
Connection for Blank-type
Cautions
- Before commencing any installation or maintenance work, please disconnect the power supply f ‧ rom the utility. Ensure that it cannot be re-connected inadvertently!
- Keep proper ventilation around the unit and do not stack any object on it. Also a 10-15 cm clearance must be kept when the adjacent device is a heat source.
- Mounting orientations other than standard orientation or operate under high ambient temperature may increase the internal component temperature and will require a de-rating in output current.
- Current rating of an approved primary /secondary cable should be greater than or equal to that of the unit. Please refer to its specification.
- For LED drivers with waterproof connectors, verify that the linkage between the unit and the lighting fixture is tight so that water cannot intrude into the system.
- For dimmable LED drivers, make sure that your dimming controller is capable of driving these units.PWM series require 0.15mA each unit.
- Tc max. is identified on the product label. Please make sure that temperature of Tc point will not exceed limit.
- DO NOT connect “DIM- to Vo-“.
- Suitable for indoor use or outdoor use without direct sunlight exposure. Please avoid immerse in the water over 30 minutes.
- The power supply is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.
User’s Manual
Documents / Resources
| MW
PW M -90 series Constant Voltage PWM Output LED
Driver
[pdf] Owner's Manual
PW M -90 series Constant Voltage PWM Output LED Driver, PW M -90 series,
Constant Voltage PWM Output LED Driver, Output LED Driver
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>