PS-POU1K2B9A Power Solid RM Online UPS User Manual
- October 30, 2023
- POWER SOLID
Table of Contents
PS-POU1K2B9A Power Solid RM Online UPS
Product Information
The product is an Uninterruptible Power Supply (UPS) that provides emergency power to connected equipment in the event of a power outage. The UPS contains lethal voltages and all repairs and service should be performed by authorized service personnel only. The UPS also carries live voltage even when not connected to an AC supply. The manual contains important safety instructions, installation and setup information, troubleshooting steps, storage and maintenance guidelines, and product specifications.
Product Usage Instructions
- Important Safety Warning: Before using the UPS, read all safety information and operating instructions carefully. Comply with all warnings and operating instructions in the manual.
- Transportation: Only transport the UPS in its original package to protect against shock and impact.
- Preparation: Allow at least two hours for the UPS to acclimate to the environment before installing it to prevent condensation. The UPS system must be absolutely dry before installation.
- Installation and Setup: Refer to section 2 of the manual for rear panel view and setup instructions.
- Troubleshooting: Refer to section 4 of the manual for troubleshooting steps if the UPS malfunctions or does not operate properly.
- Storage and Maintenance: Refer to section 5 of the manual for storage and maintenance guidelines.
- Specifications: Refer to section 6 of the manual for product specifications.
- Disposal: Do not discard the UPS or batteries in the trash. The product contains sealed, lead-acid batteries that must be disposed of properly. Contact your local recycling/reuse or hazardous waste center for more information. Do not discard waste electrical or electronic equipment (WEEE) in the trash. Contact your local recycling/reuse or hazardous waste center for proper disposal.
SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during
installation and maintenance of the UPS and batteries. Please read all
instructions before operating the equipment and save this manual for future
reference.
DANGER
The UPS contains LETHAL VOLTAGES. All repairs and service should be performed
by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
WARNING
- The UPS contains its own energy source (batteries). The UPS output may carry live voltage even when the UPS is not connected to an AC supply
- To reduce the risk of fire or electric shock, install the UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (90% maximum).
- To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection in accordance with the National Electrical Code (NEC), ANSI/NFPA 70.
- Output overcurrent protection and disconnect switch must be provided by others.
- To comply with international standards and wiring regulations, the sum of the leakage current of the UPS and the total equipment connected to the output of the UPS must not have an earth leakage current greater than 3.5 mA.
- If the UPS requires any type of transportation, verify that the UPS is unplugged and turned off and then disconnect the UPS internal battery connector.
CAUTION
- Batteries can present a risk of electrical shock or burn from high short-circuits current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries.
- Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
- Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Symbol Conventions
- The symbols that may be found in this document are defined as follows.
Symbol | Description |
---|---|
Indicates an imminently hazardous situation which, if not avoided, will |
result in death or serious injury.
| Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
| Indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
| Indicates a potentially hazardous situation which, if not avoided, could
result in equipment damage, data loss, performance deterioration, or
unanticipated results.
NOTICE is used to address practices not related to personal injury.
| Calls attention to important information, best practices and tips.
NOTE is used to address information not related to personal injury, equipment
damage, and environment deterioration.
| This symbol indicates that you should not discard the UPS or the UPS
batteries in the trash. This product contains sealed, lead‐acid batteries and
must be disposed of properly. For more information, contact your local
recycling/reuse or hazardous waste center.
| This symbol indicates that you should not discard waste electrical or
electronic equipment (WEEE) in the trash. For proper disposal, contact your
local recycling/reuse or hazardous waste center.
Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully
Transportation
Please transport the UPS system only in the original package to protect
against shock and impact.
Preparation
- Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
- Do not install the UPS system near water or in moist environments.
- Do not install the UPS system where it would be exposed to direct sunlight or near heater.
- Do not block ventilation holes in the UPS housing.
Installation
- Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
- Place cables in such a way that no one can step on or trip over them.
- Do not connect domestic appliances such as hair dryers to UPS output sockets.
- The UPS can be operated by any individuals with no previous experience.
- Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
- Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
- Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
- When installing the equipment, it should ensure that the sum of the leakage current of the
- UPS and the connected devices does not exceed 3.5mA.
Operation
- Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
- The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
- In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
- Prevent no fluids or other foreign objects from inside of the UPS system.
Maintenance, service and faults
- The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
- Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
- Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
- Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
- Caution – risk of electric shock. The battery circuit is not isolated from the input voltage.
- Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
- Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
- Remove wristwatches, rings and other metal objects
- Use only tools with insulated grips and handles.
- When changing batteries, install the same number and same type of batteries.
- Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
- Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes.
- It may be toxic.
- Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
- Do not dismantle the UPS system.
Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
Rear panel view
- AC input
- Input circuit breaker
- USB communication port
- RS-232 communication port
- SNMP intelligent slot (option)
- External battery connection (For long back up models)
- Output receptacles
- Output terminal
Setup the UPS
Step 1: External battery wires
Please connect external batteries as below chart. (For long back up models)
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid
using extension cords. The power cord is supplied in the UPS package.
Step 3: UPS output connection
-
For socket-type outputs, simply connect devices to the outlets.
-
For terminal-type input or outputs, please follow below steps for the wiring configuration:
-
Remove the small cover of the terminal block
-
Suggest using AWG14 or 2.1mm2 power cords for 3KVA
(200/208/220/230/240VAC models). Suggest using AWG12-10 or 3.3mm2-5.3mm2 power cords for 3KVA (100/110/115/120/127VAC models). Please also install a circuit breaker (40A) between the mains and AC input of UPS in 3KVA (100/110/115/120127VAC models) for safety operation. Upon completion of the wiring configuration, please check whether the wires are securely affixed. -
Upon completion of the wiring configuration, please check whether the wires are securely affixed.
-
Put the small cover back to the rear panel.
-
Communication connection
Communication port:
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options. PS. USB port and RS-232 port can’t work at the same time
Step 7: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the
UPS.
Note: The battery charges fully during the first five hours of normal
operation. Do not expect full battery run capability during this initial
charge period.
Step 8: Install software
For optimal computer system protection, install UPS monitoring software to
fully configure UPS shutdown.
- Insert the included installation CD into CD-ROM drive and then follow the on-screen instructions to proceed software installation. If there no screen shows 1 minute after inserting the CD, please execute setup.exe file for initiating software installation.
- If you don’t have CD, The program can be set up by downloading the www.powersolid.vn or http://www.power-software-download.com web site. You run the setup.exe file after downloading the program
- Follow the on-screen instructions to install the software.
- When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.
Operations
Button operation
Button | Function |
---|---|
ON/Mute Button |
- Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.
- Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system. But it’s not applied to the situations when warnings or errors occur.
- Up key: Press this button to display previous selection in UPS setting mode.
- Switch to UPS self-test mode: Press ON/Mute buttons for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
OFF/Enter Button|
- Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
- Confirm selection key: Press this button to confirm selection in UPS setting mode.
Select Button|
- Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, input current, battery voltage, battery current, battery capacity, ambient temperature, output voltage, output frequency, load current and load percent. It will return back to default display when pausing for 10 seconds.
- Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when Standby or Bypass mode.
- Down key: Press this button to display next selection in UPS setting mode.
ON/Mute + Select Button|
- Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter to bypass mode. This action will be ineffective when the input voltage is out of acceptable range.
LCD Panel
| Display| Function
---|---|---
| Remaining backup time information
| | Indicates the remaining backup time in pie chart.
| | Indicates the remaining backup time in numbers. H: hours, M: minute,
S: second
| Fault information
| | Indicates that the warning and fault occurs.
| | Indicates the warning and fault codes, and the codes are listed in
details in 3-5 section.
| Mute operation
| | Indicates that the UPS alarm is disabled.
| Output & Battery voltage information
| | Indicates the output voltage, frequency or battery voltage. Vac:
output voltage, Vdc: battery voltage, Hz: frequency
| Display| Function
Load information|
| Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.|
**| Indicates overload.|
Short| Indicates the load or the UPS output is short circuit.|
Mode operation information|
**| Indicates the UPS connects to the mains.|
| Indicates the battery is working.|
| Indicates the bypass circuit is working.|
| Indicates the ECO mode is enabled.|
| Indicates the Inverter circuit is working.|
| Indicates the output is working.|
Battery information|
| Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76-100%.|
| Indicates the battery is fault.|
| Indicates low battery level and low battery voltage.|
Input & Battery voltage information|
****| Indicates the input voltage or frequency or battery voltage. Vac: Input
voltage, Vdc: battery voltage, Hz: input frequency|
Audible Alarm
Battery Mode | Sounding every 4 seconds |
---|---|
Low Battery | Sounding every seconds |
Overload | Sounding every second |
Fault | Continuously sounding |
Bypass Mode | Sounding every 10 seconds |
LCD display wordings index
Abbreviation | Display content | Meaning |
---|---|---|
ENA |
ENA
| Enable
DIS|
**DIS**
| Disable
ESC|
ESC
| Escape
HLS|
HLS
| High loss
LLS|
LLS
| Low loss
BAT|
BAT
| Battery
CF|
CF
| Converter
TP|
TP
| Temperature
CH|
CH
| Charger
FU|
FU
| Bypass frequency unstable
EE|
EE
| EEPROM error
UPS Setting
There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives. Refer to below table.
Parameter 2 and parameter 3 are the setting options or values for each
program.
Output voltage setting
Interface | Setting |
---|---|
**** | **** |
Parameter 3: Output voltage
You may choose the following output voltage:
200: presents output voltage is 200Vac 208: presents output voltage
is 208Vac 220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
Frequency Converter enable/disable
Interface | Setting |
---|---|
**** | Parameter 2 & 3: Enable or disable converter mode. You may choose |
the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
Output frequency setting
Interface | Setting |
---|
| Parameter 2 & 3: Output frequency setting. You may set the initial
frequency on battery mode: BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz If converter mode is enabled,
you may choose the following output frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
ECO enable/disable
Interface | Setting |
---|---|
**** | Parameter 3: Enable or disable ECO function. You may choose the |
following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
05: ECO voltage range setting
Interface | Setting |
---|
| Parameter 2 & 3: Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2. The setting range in parameter 3 is from +7V to +24V of the nominal voltage. (Default: +12V)
LLS: Low loss voltage in ECO mode in parameter 2. The setting range in parameter 3 is from -7V to -24V of the nominal voltage. (Default: -12V)
06: Bypass enable/disable when UPS is off
Interface | Setting |
---|---|
**** | Parameter 3: Enable or disable Bypass function. You may choose the |
following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
07: Bypass voltage range setting
Interface | Setting |
---|
| Parameter 2 & 3: Set the acceptable high voltage point and acceptable
low voltage point for Bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
230-264: setting the high voltage point in parameter 3 from 230Vac to
264Vac. (Default: 264Vac)
LLS: Bypass low voltage point
170-220: setting the low voltage point in parameter 3 from 170Vac to
220Vac (Default: 170Vac)
08: Autonomy limitation setting
Interface | Setting |
---|
| Parameter 3: Set up backup time on battery mode for general outlets.
0-999: setting the backup time in minutes from 0-999 for general outlets
on battery mode.
0: When setting as “0”, the backup time will be only 10 seconds.
999: When setting as “999”, the backup time setting will be disabled.
(Default)
3-6. Operating Mode Description
Operating mode | Description | LCD display |
---|---|---|
Online mode | When the input voltage is within acceptable range, UPS will |
provide pure and stable AC power to output. The UPS will also charge the
battery at online mode.|
ECO mode| Energy saving mode:
When the input voltage is within voltage regulation range, UPS will bypass
voltage to output for energy saving.|
Frequency Converter mode| When input frequency is within 40 Hz to 70 Hz, the
UPS can be set at a constant output frequency, 50 Hz or 60 Hz.
The UPS will still charge battery under this mode.|
Battery mode| When the input voltage is beyond the acceptable range or power
failure and alarm is sounding every 4 second, UPS will backup power from
battery.|
Bypass mode| When input voltage is within acceptable range but UPS is
overload, UPS will enter bypass mode or bypass mode can be set by front panel.
Alarm is sounding every 10 second.|
Standby mode| UPS is powered off and no output supply power, but still can
charge batteries.| ****
3-7. Faults Reference Code
Fault event| Fault code| Icon| Fault event| Fault
code| Icon
---|---|---|---|---|---
Bus start fail| 01| x| Inverter output short| 14|
Bus over| 02| x| Battery voltage too high| 27|
Bus under| 03| x| Battery voltage too low| 28|
Bus unbalance| 04| x| Over temperature| 41| x
Inverter soft start failure| 11| x| Overload| 43|
Inverter voltage high| 12| x| Charger failure| 45| x
Inverter voltage Low| 13| x| | | ****
3-8. Warning indicator
Warning | Icon (flashing) | Alarm |
---|---|---|
Low Battery | Sounding every second | |
Overload | Sounding twice every second | |
Battery is not connected | Sounding every second | |
Over Charge | Sounding every second | |
Over temperature | Sounding every second | |
Charger failure | Sounding every second | |
Battery fault | Sounding every second | |
Out of bypass voltage range | Sounding every second | |
Bypass frequency unstable | Sounding every second | |
EEPROM error | ![PS-POU1K2B9A-Power-Solid-RM-Online- |
UPS-59](https://manuals.plus/wp-content/uploads/2023/06/PS-POU1K2B9A-Power- Solid-RM-Online-UPS-59.png)| Sounding every second
Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom | Possible cause | Remedy |
---|---|---|
No indication and alarm even though the mains is normal. | The AC input power | |
is not connected well. | Check if input power cord |
firmly connected to the mains.
The AC input is connected to the UPS output.| Plug AC input power cord to AC
input correctly.
The icon and flashing on LCD display and alarm is sounding every second.| The
external or internal battery is incorrectly connected.| Check if all batteries
are connected well.
Fault code is shown as 27 and the icon is lighting on LCD
display and alarm is continuously sounding.| Battery voltage is too high or
the charger is fault.| Contact your dealer.
Fault code is shown as 28 and the icon is lighting on LCD display and alarm
is continuously sounding.| Battery voltage is too low or the charger is
fault.| Contact your dealer.
The icon and is flashing on LCD display and alarm is sounding twice every
second.| UPS is overload| Remove excess loads from UPS output.
UPS is overloaded. Devices connected to the UPS are fed directly by the
electrical network via the Bypass.| Remove excess loads from UPS output.
After repetitive overloads, the UPS is locked in the Bypass mode. Connected
devices are fed directly by the mains.| Remove excess loads from UPS output
first. Then shut down the UPS and restart it.
Fault code is shown as 43 and The icon is lighting on LCD display and alarm
is continuously sounding.| The UPS shut down automatically because of overload
at the UPS output.| Remove excess loads from UPS output and restart it.
Symptom| Possible cause| Remedy
Fault code is shown as 14 and the icon is lighting on LCD display and alarm
is continuously sounding.| The UPS shut down automatically because short
circuit occurs on the UPS output.| Check output wiring and if connected
devices are in short circuit status.
Fault code is shown as 01, 02, 03, 04, 11, 12, 13, 41 and 45 on LCD display
and alarm is continuously sounding.| A UPS internal fault has occurred. There
are two possible results:
- The load is still supplied, but directly from AC power via bypass.
- The load is no longer supplied by power.
| Contact your dealer.
Battery backup time is shorter than nominal value| Batteries are not fully
charged| Charge the batteries for at least 5 hours and then check capacity. If
the problem still persists, consult your dealer.
| Batteries defect| Contact your dealer to replace the battery.
Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life
(3~5 years at 25°C ambient temperature) has been exceeded, the batteries must
be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to
your dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a
cool, dry location.
During storage, recharge the battery in accordance with the following table:
Storage Temperature | Recharge Frequency | Charging Duration |
---|---|---|
-25°C – 40°C | Every 3 months | 1-2 hours |
40°C – 45°C | Every 2 months | 1-2 hours |
Specifications
Model Tower UPS| ONLINE 1kVA ONLINE -L 1kVA| ONLINE 2kVA ONLINE -L
2kVA| ONLINE 3kVA ONLINE -L 3kVA
---|---|---|---
**CAPACITY*| 1000VA/800W| 2000VA/1600W| 3000VA/2400W
INPUT
Voltage Range| Low Line Transfer| 160VAC/140VAC/120VAC/110VAC±5% (Ambient
Temp.<350C) ( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % /
60 % – 0)
Low Line Comeback| 175VAC/155VAC/135VAC/125VAC ± 5 % (Ambient Temp.<350C) (
based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)
High Line Transfer| 300 VAC ± 5 %
High Line Comeback| 290 VAC ± 5 %
Frequency Range| 40Hz ~ 70 Hz
Phase| Single phase with ground
Power Factor| ≧ 0.99 @ nominal voltage (input voltage)
OUTPUT**
Output voltage| 200/208/220/230/240VAC
AC Voltage Regulation| ± 1% (Batt. Mode)
Frequency Range| 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Batt. Mode)| 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Overload| Ambient Temp.<350C 105%~110%: UPS shuts down after 10 minutes at
battery mode or transfer to bypass when the utility is normal
110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal
130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal
Current Crest Ratio| 3:1
Harmonic Distortion| ≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
Transfer Time| AC Mode to Batt. Mode| Zero
Inverter to Bypass| 4 ms (Typical)
Waveform (Batt. Mode)| Pure Sinewave
EFFICIENCY
AC Mode| 88%| 89%| 90%
Battery Mode| 83%| 87%| 88%
BATTERY
Standard Model
| Battery Type| 12V/9AH| 12V/9AH| 12V/9AH
Numbers| 2| 4| 6
Recharge Time| 4 hours recover to 90% capacity (Typical)
Charging Current| (1m.0aAx.)
Charging Voltage| 2D7C.4±V1%| 54.7 VDC ±1%| 82.1 VDC ± 1%
Long-run Model
| Battery Type| Depends of the external battery
Number| 2| 4| 6
Charging Current| 1/2..00AA/4.0A/6.0 A (max.)
Charging Voltage| 2D7C.4±V1%| 54.7 VDC ±1%| 2.1 VDC ± 1%
Charging method| 3 stage charging (CC -> CV -> FV)
PHYSICAL
Standard Model| Dimension, D X W X H| 282 x 145 x 220 (mm)| 397×145 x 220
(mm)| 421 x 190 x 318 (mm)
Net Weight (kgs)| 9.8| 17| 27.6
Long-run Model*| Dimension, D X W X H (mm)| 282 x 145 x 220 (mm)| 397 x 145 x
220 (mm)| 421 x 190 x 318 (mm)
Net Weight (kgs)| 4.1| 6.8| 7.4
ENVIRONMENT
Operation Temperature| 0ºC to 40ºC
Operation Humidity| 20-95 % RH @ 0- 40°C (non-condensing)
Noise Level| Less than 50dBA @ 1 Meter (With fan speed control)
MANAGEMENT
Smart RS-232 or USB| Supports Windows® 2000/2003/XP/Vista/2008/7,
Linux, Unix and MAC
Optional SNMP| Power management from SNMP manager and web browser
- Derate capacity to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100VAC, 200VAC or 208VAC.
- Product specifications are subject to change without further notice.