Sunricher Micro Smart Dimmer SR-ZV9040A-B Manual
- June 8, 2024
- SUNRICHER
Table of Contents
- Sunricher
- Micro Smart Dimmer
- SKU: SR-ZV9040A-B
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 10: Enable/disable to detect load after re-power on
- Parameter 11: Wiring type
- Parameter 12: Load type
- Parameter 13: Enable/disable over current protection
- Parameter 14: Power automatic report absolute threshold, unit is W
- Parameter 15: Power automatic report percentage threshold, unit is %
- Parameter 2: Saving load state before power failure
- Parameter 21: Power metering automatic report time cycle, unit is second
- Parameter 22: Energy metering automatic report time cycle, unit is second
- Parameter 23: Voltage metering automatic report time cycle, unit is
- Parameter 24: Current metering automatic report time cycle, unit is
- Parameter 3: Enable/disable to send the basic report
- Parameter 4: Default fade time
- Parameter 5: Setting minimum brightness value
- Parameter 6: Setting maximum brightness value
- Parameter 7: Choose MOSFET driving type
- Parameter 8: External switch type
- Parameter 9: Enable/disable external switch to be added to and removed
- Technical Data
- Supported Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Sunricher
Micro Smart Dimmer
SKU: SR-ZV9040A-B
Quickstart
This is a
secure
Light Dimmer
for
U.S. / Canada / Mexico.
To run this device please connect it to your mains power supply.
To add this device to your network execute the following action:
1. Set primary controller/gateway into inclusion mode (Please refer to your
primary controllers manual on how to turn your controller into inclusion).2.
Power on the in-wall dimmer and set it into inclusion mode. There are two
methods to set the in-wall dimmer into inclusion mode:1)Repower on the dimmer,
it will be set into inclusion mode automatically, and waiting to be
included.2)Triple press the action button on the dimmer, it will set the
dimmer into inclusion mode.The connected light will stay solid on for 3
seconds to indicate successful inclusion.
Please refer to the
Manufacturers
Manual for more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
The micro smart dimmer is a Z-Wave device designed to work with various types of light sources. It may beconnected to two-wire or three-wire configuration so it can operate with or without neutral lead. Thedimmer can switch or dim connected light source either through Z-Wave devices or through the wallswitch connected directly to it. The smart dimmer is equipped with an algorithm of smart light sourcedetection which makes configuration easier and ensures high compatibility of the device. It may be usedas a switch with non-dimmable light sources (in 3-wire connection).
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Press and hold down the action button for over 10 seconds, the dimmer will be reset to factory defaults.Note: Factory reset is not recommended for exclusion, please use this procedure only if the primary controller/gateway is missing or otherwise inoperable.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
1. Set primary controller/gateway into inclusion mode (Please refer to your primary controllers manual on how to turn your controller into inclusion).2. Power on the in-wall dimmer and set it into inclusion mode. There are two methods to set the in-wall dimmer into inclusion mode:1)Repower on the dimmer, it will be set into inclusion mode automatically, and waiting to be included.2)Triple press the action button on the dimmer, it will set the dimmer into inclusion mode.The connected light will stay solid on for 3 seconds to indicate successful inclusion.
Exclusion
There are two exclusion methods:Method 1: Exclusion from the primary controller/gateway as follows:1. Set the primary controller/gateway into exclusion mode (Please refer to your primary controllers manual on how to set your controller into exclusion).2. Triple press the action button, the dimmer will be set to exclusion mode, and waiting to be excluded, then the dimmer will be excluded from the network.Method 2: Factory reset the dimmer will force it to be excluded from a network. (please refer to the part Factory Reset of this manual)Note: Factory reset is not recommended for exclusion, please use this procedure only if the primary controller/gateway is missing or otherwise inoperable.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 5| dimmer, send u0022Device Reset Locally Notification CCu0022 to
associateddevices of this group to report factory reset information.2. When
load state changes, send u0022Basic Report CCu0022 to associateddevices of
this group.3. When a load over current is detected, send u0022Over-
currentdetectedu0022 to Lifeline.4. When a mains voltage drop is detected,
send u0022Voltage drop/driftu0022 to Lifeline.5. When over temperature is
detected, send Emergency shutoffstatusu0022 to Lifeline.
---|---|---
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 10: Enable/disable to detect load after re-power on
Enable/disable to detect load after re-power on(detect load type, minimum
brightness,maximum brightness)Note: When the device does not belong to
anynetwork, load detection will be enabled everytime after re-power on. When
the device hasalready been added to a network, load detectionwill be
disabled.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | disable |
---|---|
1 | enable to detect every time after re-power on |
2 | enable to detect only after first re-power on |
Parameter 11: Wiring type
Wiring typeNote: this parameter is read only
Size: 1 Byte, Default Value: 0
SettingDescription
0 | unknown |
---|---|
1 | 2 Wire With No Neutral |
2 | 3 Wire With Neutral |
Parameter 12: Load type
Load typeNote: this parameter is read only
Size: 1 Byte, Default Value: 0
SettingDescription
0 | unknown |
---|---|
1 | resistive |
2 | inductive |
3 | capacitive |
Parameter 13: Enable/disable over current protection
Enable/disable over current protection (over 1.5A for 20 seconds
continuously)
Size: 1 Byte, Default Value: 1
SettingDescription
0 | disable |
---|---|
1 | enable |
Parameter 14: Power automatic report absolute threshold, unit is W
Power automatic report absolute threshold, unit is WWhen power changes above
the absolutethreshold, immediately report current power value
Size: 2 Byte, Default Value: 10
SettingDescription
0 – 32767| When power changes above the absolute threshold, immediately report
current power value
---|---
Parameter 15: Power automatic report percentage threshold, unit is %
Power automatic report percentage threshold, unit is %When power changes
above the percentage threshold, immediately report current power value
Size: 1 Byte, Default Value: 20
SettingDescription
0 – 100| When power changes above the percentage threshold, immediately report
current power value
---|---
Parameter 2: Saving load state before power failure
Saving load state before power failure
Size: 1 Byte, Default Value: 2
SettingDescription
0 | shutoff load |
---|---|
1 | turn on load |
2 | save load state before power failure |
Parameter 21: Power metering automatic report time cycle, unit is second
Power metering automatic report time cycle, unit is second
Size: 4 Byte, Default Value: 600
SettingDescription
5 – 2678400 | Power metering automatic report time cycle, unit is second |
---|
Parameter 22: Energy metering automatic report time cycle, unit is second
Energy metering automatic report time cycle, unit is second
Size: 4 Byte, Default Value: 1800
SettingDescription
5 – 2678400 | Energy metering automatic report time cycle, unit is second |
---|
Parameter 23: Voltage metering automatic report time cycle, unit is
second
Voltage metering automatic report time cycle, unit is second
Size: 4 Byte, Default Value: 3600
SettingDescription
5 – 2678400 | Voltage metering automatic report time cycle, unit is second |
---|
Parameter 24: Current metering automatic report time cycle, unit is
second
Current metering automatic report time cycle, unit is second
Size: 4 Byte, Default Value: 3600
SettingDescription
5 – 2678400 | Current metering automatic report time cycle, unit is second |
---|
Parameter 3: Enable/disable to send the basic report
Enable/disable to send the basic report to the Lifeline when the load state
changed (When value set as 1, re-power on the dimmer, it will send Basic
report automatically
Size: 1 Byte, Default Value: 1
SettingDescription
0 | Disable to send Basic report |
---|---|
1 | Enable to send Basic report |
Parameter 4: Default fade time
Default fade time (unit is second)
Size: 1 Byte, Default Value: 1
SettingDescription
0 | Instantly |
---|---|
1 – 127 | 1 second (0x01) to 127 seconds (0x7F) in 1 second resolution. |
Parameter 5: Setting minimum brightness value
Setting minimum brightness value
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 50 | the bigger the value is, the higher the loads minimum brightness is |
---|
Parameter 6: Setting maximum brightness value
Setting maximum brightness value
Size: 1 Byte, Default Value: 100
SettingDescription
0 – 100 | the maximum brightness value |
---|
Parameter 7: Choose MOSFET driving type
Choose MOSFET driving type
Size: 1 Byte, Default Value: 0
SettingDescription
0 | trailing edge |
---|---|
1 | leading edge |
Parameter 8: External switch type
External switch type
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Push button switch |
---|---|
1 | normal on/off switch |
2 | 3-way switch |
Parameter 9: Enable/disable external switch to be added to and removed
from a network
Enable/disable external switch to be added to and removed from a network
(when enables this function, triple press the external switch within 1.5
seconds to be added to or removed from a network)
Size: 1 Byte, Default Value: 1
SettingDescription
0 | disable |
---|---|
1 | enable |
Technical Data
Hardware Platform | ZM5101 |
---|---|
Device Type | Light Dimmer Switch |
Network Operation | Always On Slave |
Firmware Version | HW: 1 FW: 1.06 |
Z-Wave Version | 6.71.03 |
Certification ID | ZC10-19046454 |
Z-Wave Product Id | 0x0330.0x0201.0xD00C |
Supported Notification Types | Power ManagementSystem |
Firmware Updatable | Updatable by Consumer by RF |
Supported Meter Type | Electric Energy |
Security V2 | S2_UNAUTHENTICATED |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Supported Command Classes
- Association Grp Info V3
- Association V2
- Basic V2
- Configuration
- Device Reset Locally
- Firmware Update Md V4
- Manufacturer Specific V2
- Meter V3
- Notification V8
- Powerlevel
- Scene Activation
- Scene Actuator Conf
- Security
- Security 2
- Supervision
- Switch Multilevel V4
- Transport Service V2
- Version V2
- Zwaveplus Info V2
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>